MA Fire Alarm flashcards
MA Fire Alarm · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- MGL c. 148, § 27
- Massachusetts statute requiring a permit from the head of the local fire department before a fire alarm system is installed or altered; plans and specifications may be required as part of the submittal.
- 527 CMR 1.00
- The Massachusetts Comprehensive Fire Safety Code, which adopts NFPA 1 and NFPA 101 with state amendments and references NFPA 72 for fire alarm design, installation, testing, and maintenance.
- 527 CMR 12.00
- The Massachusetts Electrical Code; it adopts NFPA 70 with Massachusetts amendments, and the amendment text supersedes the model code text wherever the two conflict.
- Systems Contractor Class C license
- Massachusetts electrical license class that authorizes a business entity to contract for fire alarm, security, and telecommunications system work performed by licensed technicians under that contractor.
- NFPA 72 Chapter 14
- The chapter covering inspection, testing, and maintenance of fire alarm systems, including the frequency tables for initiating devices, control equipment, notification appliances, and batteries.
- NEC Article 760
- The National Electrical Code article governing fire alarm wiring: permitted conductor and cable types, power-limited and non-power-limited circuits, marking, and installation requirements.
- FPLP cable substitution
- Plenum-rated fire alarm cable may replace riser-rated FPLR or general-purpose FPL cable, but the reverse substitution is never permitted because of smoke and flame spread ratings.
- UL 864 listing
- The product standard for fire alarm control units and related equipment; a control unit must be listed to UL 864 to be acceptable for protected-premises fire alarm service.
- Signal priority order
- Alarm signals take precedence over supervisory signals, which take precedence over trouble signals; a new higher-priority condition is annunciated distinctly and overrides the lower-priority display.
- Conventional zone area limit
- A single conventional initiating zone may not exceed 22,500 square feet (2,090 square meters) of protected floor area, with further limits for unusual building configurations.
- Addressable signaling line circuit
- A supervised data pathway that carries digital information between the control unit and individually identified devices, allowing point-specific annunciation, status reporting, and device-level control.
- Spot smoke detector spacing
- On a smooth ceiling, spot-type smoke detectors are typically spaced 30 feet (9.1 meters) apart and 15 feet from walls, covering about 900 square feet per detector.
- Class B initiating circuit
- A two-wire supervised initiating device circuit with an end-of-line resistor; a single open conductor disables every device located beyond the break in the circuit.
- Manual pull station height
- Manual fire alarm boxes are mounted 42 to 48 inches above the finished floor, within 5 feet of the exit doorway, and along the normal path of egress travel.
- Duct smoke detector
- A detector listed for air duct mounting with a sampling tube spanning the duct width; often required for air-handling units over 2,000 cfm serving more than one story.
- Alarm verification
- A feature that delays alarm processing, typically not more than 60 seconds total, until a second detection confirms the alarm, reducing nuisance alarms caused by transient smoke.
- Public mode audibility
- Notification in public mode must produce at least 65 dBA, or 10 dBA above the average ambient sound level, measured 10 feet (1.5 meters) from the appliance.
- Temporal-three pattern
- The standard evacuation tone: 0.5 second on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, then 1.5 seconds off, repeated continuously as the evacuation signal.
- Visible appliance mounting height
- Visible notification appliances are mounted with the lens between 80 and 96 inches above the finished floor, unless the listing or a specific application permits otherwise.
- Sleeping area audibility
- In sleeping areas the fire alarm must sound at least 75 dBA at the pillow level, or 15 dBA above the ambient sound level, whichever is greater.
- Signaling line circuit supervision
- The addressable data loop must be supervised for opens, shorts, and grounds, and installed within the manufacturer's limits for total resistance, capacitance, and device quantity.
- Class A pathway
- A circuit arrangement with a redundant path returning to the control unit, so that a single open conductor or ground fault does not prevent alarm signal processing.
- Ground fault detection
- Control units must detect and annunciate a ground fault on fire alarm circuits as a trouble condition, identifying the affected circuit where the panel design supports it.
- Transponder
- A remotely located interface unit that monitors initiating circuits and controls notification circuits, reporting status to the main control unit over a supervised communication pathway.
- Secondary power duration
- Battery secondary power must operate the system for 24 hours of standby followed by 5 minutes of alarm; emergency voice alarm systems require 15 minutes of alarm operation.
- Battery capacity formula
- Battery ampere-hours equal 1.2 times the sum of standby current times 24 hours plus alarm current times alarm duration, where 1.2 is the aging and derating allowance.
- Primary power connection
- The fire alarm branch circuit must be dedicated, marked "FIRE ALARM CIRCUIT CONTROL," and must not pass through a GFCI device, dimmer, or switched receptacle.
- Battery recharge time
- After a full discharge, the charger must restore the secondary battery to rated capacity within 48 hours, with charger performance verified during inspection and testing.
- Smoke detector sensitivity test
- Detector sensitivity is checked within one year of installation and at least every alternate year thereafter, unless the detector is listed as self-testing with automatic compensation.
- Record of Completion
- The NFPA 72 document, prepared and signed by the installing contractor, recording the installed system configuration, device list, and results of acceptance testing.
- Semiannual test items
- Waterflow switches and valve supervisory (tamper) switches are tested at least semiannually, while initiating devices, control equipment, and notification appliances are tested annually.
- Reacceptance testing
- Testing performed after any addition, modification, or repair of system equipment, covering the affected devices and their interfaces with the remainder of the fire alarm system.