MA Fire Alarm study materials
MA Fire Alarm study resources

MA Fire Alarm key terms

MA Fire Alarm · Get comfortable with the vocabulary.

Massachusetts Comprehensive Fire Safety Code (527 CMR 1.00)

Massachusetts regulation that adopts and amends the model fire and building codes for the Commonwealth, including when fire alarm systems must be installed and how they must be maintained.

Related: Permit to Install, Authority Having Jurisdiction
Fire Alarm Systems Contractor License

A Massachusetts business credential authorizing a company to contract for the installation, alteration, servicing, and maintenance of fire alarm systems, with a licensed technician responsible for the work.

Related: Fire Alarm Systems Technician License
Fire Alarm Systems Technician License

An individual Massachusetts credential, obtained by examination, that lets a person install, service, and test fire alarm systems while employed by a licensed contractor, with renewal tied to continuing education.

Related: Fire Alarm Systems Contractor License
Permit to Install

Written local approval required before fire alarm installation or alteration begins in many Massachusetts communities, letting the fire department track the project and schedule inspections and the acceptance test.

Related: Authority Having Jurisdiction, Acceptance Test
NFPA 72

The National Fire Alarm and Signaling Code; the model standard governing design, installation, inspection, testing, and maintenance of detection, alarm, and emergency communication systems, referenced by Massachusetts regulations.

Related: NFPA 101, Record of Completion
NEC Article 760

The article of NFPA 70 covering fire alarm systems, setting rules for power-limited and non-power-limited circuits, permitted cable types such as FPL, and installation methods for fire alarm wiring.

Related: NFPA 72, Primary Power
NFPA 101

The Life Safety Code; a model code that assigns detection, alarm, and egress requirements by occupancy type, helping designers decide which fire alarm features a given building needs.

Related: NFPA 72
Listed

Described in a nationally recognized testing laboratory's published directory after the product passed that laboratory's tests for its intended fire alarm use, typically Underwriters Laboratories.

Related: Authority Having Jurisdiction
Authority Having Jurisdiction

The person or agency with legal authority to enforce code and approve fire alarm installations; in Massachusetts this is usually the local fire chief, fire prevention officer, or state fire marshal's designee.

Related: Permit to Install, Listed
Conventional (Zone) System

A fire alarm configuration in which the control unit cannot identify individual devices; it reports alarm or trouble by circuit or zone, so responders must search the area to find the activated device.

Related: Addressable System
Addressable System

A system in which every initiating device and module has a unique address, so the control unit displays the exact device and location that is in alarm, trouble, or supervisory condition.

Related: Signaling Line Circuit, Conventional (Zone) System
Alarm Signal

The output of the control unit indicating that fire or another emergency has been detected, which causes notification appliances in the designated areas to sound and flash.

Related: Supervisory Signal, Trouble Signal
Supervisory Signal

A signal showing that a system component is off-normal in a way that may reduce protection but does not indicate fire, such as a closed sprinkler valve or low air pressure on a dry system.

Related: Trouble Signal, Valve Tamper Switch
Trouble Signal

A signal indicating a fault in the alarm system itself, such as open or grounded wiring, lost primary power, a removed device, or a failed circuit card, that could prevent it from working.

Related: Supervisory Signal, Supervised Circuit
Smoke Detector

An initiating device that senses combustion particles and signals the control unit; photoelectric units respond to visible smoke, ionization units to smaller particles from flaming fires.

Related: Heat Detector, Duct Smoke Detector
Heat Detector

A device that responds to abnormal temperature, either by reaching a fixed setpoint, by a rapid rate of rise, or both; used where smoke detectors would nuisance alarm.

Related: Smoke Detector
Duct Smoke Detector

A detector that samples air moving through an HVAC duct and, on sensing smoke, sends an alarm that typically shuts down the air handler to limit smoke spread.

Related: Smoke Detector, Fire Alarm Control Unit
Manual Fire Alarm Box

A hand-operated initiating device, installed along exit paths and near exits at code-specified heights and spacing, that anyone can pull to transmit an alarm signal.

Related: Alarm Signal
Waterflow Switch

A device that senses water moving in a sprinkler pipe after a head operates and sends an alarm, usually after a delay to avoid false alarms from pressure surges.

Related: Valve Tamper Switch, Alarm Signal
Valve Tamper Switch

A supervisory device that watches the position of a sprinkler control valve and reports to the control unit when the valve is moved from its fully open position.

Related: Supervisory Signal
Monitor Module

An addressable interface that connects conventional devices or dry contacts to the signaling line circuit so each monitored point is individually identified at the control unit.

Related: Signaling Line Circuit, Addressable System
Notification Appliance Circuit

The output circuit that powers and controls horns, strobes, and speakers; it is supervised so that opens, shorts, and grounds are reported as trouble conditions.

Related: Supervised Circuit, Candela
Candela

The unit for rating how much light a visible notification appliance produces; required ratings depend on room size, mounting height, and whether the space is sleeping or public.

Related: Synchronization, Notification Appliance Circuit
Sound Pressure Level

The loudness of audible notification, measured in decibels; code requires it to exceed average ambient sound by a margin and to reach minimums in occupiable and sleeping areas.

Related: Intelligibility, Notification Appliance Circuit
Intelligibility

How well occupants can understand voice messages from an emergency communication system, measured by a recognized speech intelligibility metric and required by NFPA 72 for voice systems.

Related: Emergency Voice/Alarm Communication System
Emergency Voice/Alarm Communication System

A system using speakers and voice messages instead of, or in addition to, horns, allowing live or prerecorded instructions and staged evacuation for large or high-rise buildings.

Related: Intelligibility, Synchronization
Synchronization

Coordinated flashing of visible appliances in a field of view, required so strobes flash together within a set time window to reduce seizure risk.

Related: Candela
Fire Alarm Control Unit

The main control panel that receives signals from initiating devices, decides what to do, operates notification and output circuits, and monitors its own wiring for faults.

Related: Signaling Line Circuit, Trouble Signal
Signaling Line Circuit

The addressable data circuit linking the control unit to addressable detectors, modules, and other devices; it carries both power and digital messages and is supervised for faults.

Related: Addressable System, Class A Pathway
Class A Pathway

A circuit style in which the outgoing and return paths are separated, so one open conductor does not stop devices beyond the break from operating, though the fault is still reported.

Related: Class B Pathway, Supervised Circuit
Class B Pathway

A circuit style in which the conductors run out and back on the same path, so a single open disables all devices beyond the break while the control unit shows a trouble.

Related: Class A Pathway
Supervised Circuit

A circuit arranged so the control unit detects opens, shorts, and grounds, typically by monitoring a small current through an end-of-line device at the far end.

Related: Trouble Signal, Class B Pathway
Primary Power

The normal commercial power supply to the fire alarm control unit, taken from a dedicated branch circuit that is marked and protected against accidental shutoff.

Related: Secondary Power, NEC Article 760
Secondary Power

Backup energy, usually rechargeable batteries or a generator, that keeps the system working for code-specified standby and alarm periods when normal power is lost.

Related: Primary Power, Standby Battery Calculation
Standby Battery Calculation

A worksheet that totals quiescent current for the standby period plus alarm current for the alarm period, applies derating and aging factors, and yields the required battery capacity.

Related: Secondary Power
Acceptance Test

The initial performance test after installation, witnessed by the authority having jurisdiction, verifying that every device, circuit, and output works as the design intends.

Related: Record of Completion, Permit to Install
Record of Completion

An NFPA 72 form, filled out and signed at acceptance, that documents the installed system, device quantities, and test results and stays available on the premises.

Related: Acceptance Test, NFPA 72
Sensitivity Test

A periodic check, using a calibrated instrument or the manufacturer's listed method, that a smoke detector still responds within its rated sensitivity range.

Related: Smoke Detector, Acceptance Test
Impairment

A condition in which all or part of a fire alarm system is out of service for repair or testing, requiring notification of the fire department and often a fire watch until restored.

Related: Trouble Signal, Authority Having Jurisdiction