Refrigeration Principles and System Components

  • One ton of refrigeration equals 12,000 Btu/h, 200 Btu/min, or 3.517 kW.

  • Sensible airflow equation: Qs = 1.08 × CFM × ΔT, where Qs is Btu/h and ΔT is dry-bulb difference in °F.

  • Total airflow equation: Qt = 4.5 × CFM × Δh, where Δh is enthalpy difference in Btu/lb.

  • Compression ratio = discharge pressure (psia) ÷ suction pressure (psia); use absolute pressure, not gauge pressure.

  • Superheat = suction line temperature − evaporator saturation temperature at suction pressure; subcooling = condensing saturation temperature − liquid line temperature.

  • The metering device creates the pressure drop; the evaporator absorbs heat; the condenser rejects heat; the compressor raises pressure and temperature.

  • Saturation temperature increases as pressure increases for a pure refrigerant; zeotropic blends have bubble and dew points and measurable glide.

  • A deep vacuum is measured in microns; 25,400 microns equals 1 in Hg, and 500 microns is a common dehydration target.

Quick reference

Heating Systems: Gas, Oil, Electric and Hydronic

  • Natural gas heating value is about 1,000 Btu/ft³; propane vapor is about 2,500 Btu/ft³ and No. 2 fuel oil about 140,000 Btu/gal.

  • For water, hydronic heat output Q = 500 × GPM × ΔT; 1 GPM at 20°F ΔT delivers about 10,000 Btu/h.

  • Electric resistance heat: 1 watt = 3.413 Btu/h; a 5 kW heater delivers about 17,065 Btu/h.

  • Furnace temperature rise is found from Q = 1.08 × CFM × ΔT; compare measured rise with the nameplate range.

  • Typical natural gas manifold pressure is about 3.5 in. w.c.; typical LP manifold pressure is about 10–11 in. w.c.

  • Combustion requires roughly 10 ft³ of air per ft³ of natural gas at stoichiometric conditions; excess air is supplied for safe combustion.

  • A residential hot-water boiler commonly uses a 30 psig pressure relief valve; the relief valve must not be capped or plugged.

  • Oil burner nozzles are rated in gallons per hour; No. 2 oil at 140,000 Btu/gal and 1 GPH yields about 140,000 Btu/h input.

  • Hydronic expansion tanks accommodate water volume change; precharge and system fill pressure must match design.

Quick reference

Air Distribution, Ventilation and Indoor Air Quality

  • CFM = duct velocity in ft/min × duct cross-sectional area in ft².

  • Velocity pressure: VP = (V ÷ 4005)² in. w.c. for standard air at about 0.075 lb/ft³.

  • External static pressure equals supply static plus return static, measured with a manometer.

  • A common duct design friction rate is 0.1 in. w.c. per 100 ft of equivalent length.

  • MERV ratings: MERV 8 captures coarse particles; MERV 13 captures finer particles and may increase pressure drop.

  • ASHRAE Standard 62.1 addresses commercial ventilation; Standard 62.2 addresses residential ventilation.

  • Continuous residential bathroom exhaust is commonly 20 cfm; intermittent operation is commonly 50 cfm.

  • CO2 concentration is a ventilation indicator; outdoor air is about 400 ppm and indoor targets often range from 600 to 1,000 ppm.

Quick reference

Electrical Controls, Motors and Troubleshooting

  • Ohm's law: E = I × R; power: P = E × I = I² × R.

  • In a series circuit current is common; in a parallel circuit voltage is common.

  • Measure voltage in parallel with the load, current in series with the circuit, and resistance with power removed.

  • Locked-rotor current for induction motors is typically about 5–7 times running full-load current.

  • A run capacitor is rated in microfarads and stays in the circuit; a start capacitor is switched out after startup.

  • Low-voltage thermostat terminals: R = 24 V power, W = heat, Y = cooling, G = fan, C = common.

  • A contactor coil is a control load; the coil voltage must match the control transformer output.

  • Discharge capacitors before testing; use a meter rated for the voltage and verify zero stored voltage.

  • Motor overload protection is sized to motor nameplate current and service factor, not to the branch-circuit breaker alone.

Quick reference

Code, Safety

  • EPA Section 608 certification is required to service, repair, or dispose of appliances containing regulated refrigerants.

  • Knowingly venting regulated refrigerant to the atmosphere is prohibited; recover refrigerant before opening a system.

  • ASHRAE Standard 15 governs refrigerant safety classifications, occupancy, and machinery-room requirements.

  • A CO alarm should be installed outside sleeping areas and on each level of a home with combustion appliances.

  • Gas piping must include a shutoff valve and a sediment trap ahead of the appliance controls.

  • Electrical disconnects must be within sight of and readily accessible from the equipment served.

  • Lockout/tagout requires isolating all energy sources and verifying zero energy before service work.

  • Flue and vent terminations must maintain manufacturer and code clearances from windows, doors, and air intakes.

  • Recovery cylinders must be DOT-approved, labeled, and filled no more than 80% by weight.

Quick reference

Installation Practices and Business/Licensing Requirements

  • Manual J calculates residential heating and cooling loads; Manual S selects equipment; Manual D designs ducts.

  • A permit and inspection are generally required for new HVAC installations, replacements, and gas piping changes.

  • A written contract should state scope, price, payment schedule, warranty, and change-order procedure.

  • Change orders should be documented in writing before additional work is performed.

  • Lien rights allow unpaid contractors to file a claim against property; deadlines vary by state.

  • OSHA requires fall protection, eye protection, and safe ladder use on construction sites.

  • Commissioning verifies airflow, refrigerant charge, temperature rise, and controls operation against design.

  • Warranty terms should identify labor coverage, parts coverage, and required maintenance.

  • A startup checklist records model and serial numbers, static pressure, voltage, amperage, and refrigerant pressures.

Quick reference

Refrigeration Principles and System Components

  • One ton of refrigeration equals 12,000 Btu/h, 200 Btu/min, or 3.517 kW.

  • Sensible airflow equation: Qs = 1.08 × CFM × ΔT, where Qs is Btu/h and ΔT is dry-bulb difference in °F.

  • Total airflow equation: Qt = 4.5 × CFM × Δh, where Δh is enthalpy difference in Btu/lb.

  • Compression ratio = discharge pressure (psia) ÷ suction pressure (psia); use absolute pressure, not gauge.

  • Superheat = suction line temperature − evaporator saturation temperature at suction pressure; subcooling = condensing saturation temperature − liquid line temperature.

  • The metering device creates the pressure drop; the evaporator absorbs heat; the condenser rejects heat; the compressor raises pressure and temperature.

  • Saturation temperature increases as pressure increases for a pure refrigerant; zeotropic blends have bubble and dew points and measurable glide.

  • A deep vacuum is measured in microns; 25,400 microns equals 1 in Hg, and 500 microns is a common dehydration target.

Quick reference

Heating Systems: Gas, Oil, Electric and Hydronic

  • Natural gas heating value is about 1,000 Btu/ft³; propane vapor is about 2,500 Btu/ft³ and No. 2 fuel oil about 140,000 Btu/gal.

  • For water, hydronic heat output Q = 500 × GPM × ΔT; 1 GPM at 20°F ΔT delivers about 10,000 Btu/h.

  • Electric resistance heat: 1 watt = 3.413 Btu/h; a 5 kW heater delivers about 17,065 Btu/h.

  • Furnace temperature rise = 1.08 × CFM × ΔT; compare measured rise with the nameplate range.

  • Typical natural gas manifold pressure is about 3.5 in. w.c.; typical LP manifold pressure is about 10–11 in. w.c.

  • Combustion requires roughly 10 ft³ of air per ft³ of natural gas at stoichiometric conditions; excess air is supplied for safe combustion.

  • A residential hot-water boiler commonly uses a 30 psig pressure relief valve; the relief valve must not be capped or plugged.

  • Oil burner nozzles are rated in gallons per hour; No. 2 oil at 140,000 Btu/gal and 1 GPH yields about 140,000 Btu/h input.

  • Hydronic expansion tanks accommodate water volume change; precharge and system fill pressure must match design.

Quick reference

Air Distribution, Ventilation and Indoor Air Quality

  • CFM = duct velocity in ft/min × duct cross-sectional area in ft².

  • Velocity pressure: VP = (V ÷ 4005)² in. w.c. for standard air at about 0.075 lb/ft³.

  • External static pressure equals supply static plus return static, measured with a manometer and corrected for probe.

  • A common duct design friction rate is 0.1 in. w.c. per 100 ft of equivalent length.

  • MERV ratings: MERV 8 captures coarse particles; MERV 13 captures finer particles and may increase pressure drop.

  • ASHRAE Standard 62.1 addresses commercial ventilation; 62.2 addresses residential ventilation.

  • Continuous residential bathroom exhaust is commonly 20 cfm; intermittent operation is commonly 50 cfm.

  • CO2 concentration is a ventilation indicator; outdoor air is about 400 ppm and indoor targets often range 600–1,000 ppm.

  • Return air, supply air, and outdoor air dampers must be balanced to maintain design static pressure and airflow.

Quick reference

Electrical Controls, Motors and Troubleshooting

  • Ohm's law: E = I × R; power: P = E × I = I² × R.

  • In a series circuit current is common; in a parallel circuit voltage is common.

  • Measure voltage in parallel with the load, current in series with the circuit, and resistance with power removed.

  • Locked-rotor current for induction motors is typically about 5–7 times running full-load current.

  • A run capacitor is rated in microfarads and stays in the circuit; a start capacitor is switched out after startup.

  • Low-voltage thermostat terminals: R = 24 V power, W = heat, Y = cooling, G = fan, C = common.

  • A contactor coil is a control load; the coil voltage must match the control transformer output.

  • Discharge capacitors before testing; use a meter rated for the voltage and verify zero stored voltage.

  • Motor overload protection is sized to motor nameplate current and service factor, not to the branch-circuit breaker alone.

Quick reference

Code, Safety

  • EPA Section 608 certification is required to service, repair, or dispose of appliances containing regulated refrigerants.

  • Knowingly venting regulated refrigerant to the atmosphere is prohibited; recover refrigerant before opening a system.

  • ASHRAE Standard 15 governs refrigerant safety classifications, occupancy, and machinery-room requirements.

  • A CO alarm should be installed outside sleeping areas and on each level of a home with combustion appliances.

  • Gas piping must include a shutoff valve and a sediment trap ahead of the appliance controls.

  • Electrical disconnects must be within sight of and readily accessible from the equipment served.

  • Lockout/tagout requires isolating all energy sources and verifying zero energy before service work.

  • Flue and vent terminations must maintain manufacturer and code clearances from windows, doors, and air intakes.

  • Recovery cylinders must be DOT-approved, labeled, and filled no more than 80% by weight.

Quick reference

Installation Practices and Business/Licensing Requirements

  • Manual J calculates residential heating and cooling loads; Manual S selects equipment; Manual D designs ducts.

  • A permit and inspection are generally required for new HVAC installations, replacements, and gas piping changes.

  • A written contract should state scope, price, payment schedule, warranty, and change-order procedure.

  • Change orders should be documented in writing before additional work is performed.

  • Lien rights allow unpaid contractors to file a claim against property; deadlines vary by state.

  • OSHA requires fall protection, eye protection, and safe ladder use on construction sites.

  • Commissioning verifies airflow, refrigerant charge, temperature rise, and controls operation against design.

  • Warranty terms should identify labor coverage, parts coverage, and required maintenance.

  • A startup checklist records model/serial numbers, static pressure, voltage, amperage, and refrigerant pressures.