32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Tonnage definition
One ton of refrigeration equals 12,000 Btu per hour, which is the heat absorption rate needed to melt one ton of ice in 24 hours.
Superheat calculation
Superheat is the suction-line temperature minus the evaporator saturation temperature at the measured suction pressure; it indicates how much vapor is leaving the evaporator.
Compression ratio
Compression ratio equals discharge absolute pressure divided by suction absolute pressure; use psia, not psig, because gauge pressure ignores atmospheric pressure.
Metering device function
The metering device reduces refrigerant pressure from the liquid line to the evaporator, controlling refrigerant flow and creating the low-temperature saturation condition needed for heat absorption.
Zeotropic blend glide
A zeotropic refrigerant blend changes temperature as it evaporates or condenses at constant pressure; the difference between bubble point and dew point is called temperature glide.
Evacuation target
A vacuum of 500 microns is a common dehydration target; 25,400 microns equals one inch of mercury, and lower absolute pressure removes moisture faster.
Natural gas heating value
Natural gas contains roughly 1,000 Btu per cubic foot, so a furnace input of 100,000 Btu/h requires about 100 cubic feet of gas per hour.
Hydronic heat formula
For water, heat output equals 500 times flow in gallons per minute times temperature drop in degrees Fahrenheit; one gallon per minute at 20°F provides about 10,000 Btu/h.
Electric heat conversion
One watt of electric resistance heat produces 3.413 Btu per hour; multiply heater kilowatts by 3,413 to find Btu/h output.
Furnace temperature rise
Temperature rise is the supply-air temperature minus return-air temperature; it should fall within the furnace nameplate range at the designed airflow.
Manifold pressure
Natural gas manifold pressure is typically about 3.5 inches water column, while liquefied petroleum gas is typically about 10 to 11 inches water column; nameplate values govern.
Boiler relief valve
A residential hot-water boiler commonly has a 30 psig pressure relief valve; it must remain uncapped and piped to a safe discharge location.
Airflow equation
Cubic feet per minute equals duct velocity in feet per minute multiplied by duct cross-sectional area in square feet; use this to check airflow through a known duct size.
Velocity pressure formula
For standard air, velocity pressure in inches of water column equals velocity in feet per minute divided by 4,005, then squared.
External static pressure
External static pressure is the sum of supply and return static pressures measured at the equipment; it represents the resistance the blower must overcome.
MERV rating
Minimum Efficiency Reporting Value rates a filter's particle capture; higher MERV captures smaller particles but usually increases pressure drop and fan energy.
ASHRAE 62.2
ASHRAE Standard 62.2 sets residential ventilation and acceptable indoor air quality requirements, including whole-house and local exhaust rates.
Ohm's law
Ohm's law states that voltage equals current times resistance; power equals voltage times current, and also current squared times resistance.
Thermostat terminals
In a conventional low-voltage thermostat, R supplies 24 volts, W calls for heat, Y calls for cooling, G runs the fan, and C is common.
Run capacitor
A run capacitor remains in the motor circuit during operation and is rated in microfarads; it helps maintain phase shift and motor torque.
Locked-rotor current
Locked-rotor current is the high current drawn when a motor rotor is stationary; for induction motors it is typically five to seven times full-load current.
Contactor coil
A contactor coil is an electromagnetic control load that closes the contactor when energized; its voltage must match the control transformer output.
Capacitor discharge
Before testing a capacitor, remove power and discharge it through a resistor; verify zero voltage with a meter rated for the circuit.
EPA Section 608
EPA Section 608 certification is required for technicians who service, repair, or dispose of appliances containing regulated refrigerants; venting refrigerant is prohibited.
ASHRAE Standard 15
ASHRAE Standard 15 establishes refrigerant safety requirements, including refrigerant classification, occupancy limits, and machinery-room design.
CO alarm placement
Carbon monoxide alarms should be installed outside sleeping areas and on each level of a home containing combustion appliances, following manufacturer instructions.
Lockout/tagout
Lockout/tagout isolates electrical or other energy sources with locks and tags and verifies zero energy before maintenance, preventing accidental startup.
Recovery cylinder fill
A refrigerant recovery cylinder must not be filled above 80 percent of its water capacity by weight; overfilling can cause hydrostatic rupture.
Manual J
Manual J is the ACCA method for calculating residential heating and cooling loads from building envelope, orientation, windows, occupancy, and infiltration data.
Manual D
Manual D is the ACCA method for sizing and designing residential duct systems based on available static pressure and room airflow requirements.
Change order
A change order is a written modification to a contract that documents added or deleted work, price adjustment, and schedule impact before work proceeds.
Commissioning
Commissioning verifies that installed equipment and controls operate according to design, including airflow, refrigerant charge, temperature rise, and safety controls.