ME Fire Sprinkler flashcards
ME Fire Sprinkler · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 13 scope
- Design and installation standard for automatic sprinkler systems in commercial, industrial, and institutional occupancies. It sets hazard classification, density/area criteria, pipe sizing, and acceptance testing requirements.
- Light hazard density
- Design density of 0.10 gpm/ft² over a 1,500 ft² remote area, applied to occupancies such as offices, schools, and churches where fuel load and heat release are low.
- Ordinary Hazard Group 2
- Occupancy classification requiring 0.20 gpm/ft² over 1,500 ft² at the low end of the curve. Examples include mercantile, parking garages, and moderate-hazard manufacturing.
- K-factor formula
- Sprinkler discharge follows Q = K times the square root of P, where Q is gpm and P is psi. A K=5.6 head at 7 psi flows about 14.8 gpm.
- Minimum sprinkler pressure
- The hydraulically most remote sprinkler must have at least 7 psi (0.5 bar) residual pressure. Lower pressure is not permitted even if the calculated flow still meets density.
- Sprinkler spacing limits
- Maximum spacing is 15 ft for light and ordinary hazard and 12 ft for extra hazard. Maximum protection area per head is 225, 130, and 100 ft² respectively.
- Hanger spacing rule
- Hangers are required at intervals not exceeding 12 ft for pipe 1 inch and smaller, and 15 ft for larger pipe, with support near the end of each pipe section.
- NFPA 13R limits
- Residential sprinkler standard limited to occupancies four stories or fewer above grade. Buildings exceeding that height require full NFPA 13 design.
- NFPA 25 purpose
- Inspection, testing, and maintenance standard for water-based fire protection systems. It governs ongoing upkeep of a system installed under NFPA 13, not its original design.
- NFPA 1 Fire Code role
- Umbrella fire code that references NFPA 13, 14, 20, 24, 25, and 72. It sets the occupancy-level requirement for sprinklers and defers technical detail to those standards.
- NFPA 72 scope
- National Fire Alarm and Signaling Code. It covers waterflow switch and valve tamper switch monitoring, alarm transmission, and notification appliance requirements for sprinkler systems.
- NFPA 20 scope
- Standard for the installation of stationary pumps for fire protection. It governs fire pump sizing, driver selection, controllers, and acceptance flow testing.
- NFPA 24 scope
- Standard for private fire service mains and their appurtenances. It covers underground piping, hydrants, gate valves, and the water supply connection to the sprinkler riser.
- NFPA 14 scope
- Standard for standpipe and hose systems. Combined standpipe and sprinkler systems must be hydraulically calculated for both demands at the same time.
- Adopted edition rule
- The NFPA edition cited in the State Fire Marshal's adopted rule governs a project, even if a newer edition has been published. Always confirm the edition in force.
- NFPA 13D scope
- Limited-drawing standard for one- and two-family dwellings and manufactured homes. It permits omission of sprinklers in certain small spaces such as some closets and bathrooms.
- State Fire Marshal authority
- Maine's Fire Marshal, within the Department of Public Safety, administers fire prevention, cause-and-origin investigation, plan review, and licensing of sprinkler-related work statewide.
- Fire hazard correction order
- Statutory power of the State Fire Marshal to order abatement of a fire hazard. Failure to comply can lead to enforcement action, penalties, or closure of the premises.
- Licensed sprinkler contractor
- Installation, alteration, and maintenance of sprinkler systems in Maine is regulated work. Contractors must hold the license issued through the State Fire Marshal's Office.
- Occupancy permit linkage
- Approval to occupy a building depends on completion and acceptance of required fire protection, including sprinklers. Unprotected required systems block lawful occupancy.
- Plan submission requirement
- Plans and specifications for required sprinkler systems must be submitted to the State Fire Marshal or designated authority for review before installation begins, with fees set by rule.
- Fire investigation duty
- The Fire Marshal investigates cause and origin of fires, with heightened authority for fatal, suspicious, or large-loss fires. Findings may support enforcement or criminal referral.
- Local versus state authority
- Municipal fire departments handle scene control and pre-incident planning. Code adoption and statewide enforcement rest with the State Fire Marshal unless a town has its own ordinance.
- License discipline process
- Suspension or revocation of a sprinkler contractor license follows statutory due process through the Fire Marshal's Office, including notice and an opportunity to be heard.
- Hydrostatic test requirement
- System piping is tested at 200 psi for two hours, or at 50 psi above working pressure when working pressure exceeds 150 psi, before acceptance.
- Main drain flow test
- Acceptance and annual test confirming water supply adequacy. Static and residual pressure readings at the riser are compared against the hydraulic calculation to detect supply degradation.
- Waterflow alarm test
- Verifies that a sustained flow equivalent to one sprinkler activates the waterflow switch and transmits an alarm within the required time delay, typically 30 to 90 seconds.
- Spare sprinkler stock
- At least six spare sprinklers plus a wrench must be kept on site, or the number on any single floor if greater, stored in a cabinet near the riser.
- Impairment notification
- Before shutting down a system, notify the authority having jurisdiction, building owner, and fire department. Document the impairment and post a fire watch if protection is lost.
- Shutdown permit content
- A shutdown or hot work permit records the reason, affected area, start and end times, assigned fire watch, and verification that protection was restored afterward.
- Gauge replacement interval
- NFPA 25 requires gauges to be replaced or recalibrated every five years. Gauges are also compared during inspections to detect a failed or drifting gauge.
- Record retention rule
- Inspection and test records must be retained at least one year, and the most recent records must be available on site for review by the authority having jurisdiction.