ME Fire Sprinkler key terms
ME Fire Sprinkler · Get comfortable with the vocabulary.
- Design Density
- Related: Hydraulic Calculation, Design Area
The minimum amount of water, expressed in gallons per minute, that must flow onto each square foot of protected floor area during a fire. It sets the hydraulic starting point for sprinkler calculations.
- Design Area
- Related: Design Density, Hydraulic Calculation, Remote Area
The remotest area of sprinkler coverage, measured in square feet, that must be assumed to be flowing simultaneously when sizing pipe and water supply. Its size can be reduced for certain ceiling and sprinkler configurations.
- Hydraulic Calculation
- Related: Design Density, Water Supply Curve, Safety Margin
The mathematical procedure that sums friction losses, elevation changes, and fitting losses through pipe to confirm the water supply can deliver the required pressure and flow at the most demanding sprinklers.
- Water Supply Curve
- Related: Hydraulic Calculation, Safety Margin, Residual Pressure
A graph or table showing the static pressure, residual pressure, and available flow from a public main, tank, or other source, used to judge whether the supply exceeds system demand.
- Safety Margin
- Related: Water Supply Curve, Hydraulic Calculation
The extra pressure or flow kept in reserve between the sprinkler system demand and the available water supply, so that normal supply fluctuations do not leave the system inadequate.
- Residual Pressure
- Related: Water Supply Curve, Safety Margin
The pressure remaining at a test hydrant or gauge while water is flowing, as opposed to static pressure with no flow. It is the value used to plot the water supply curve.
- Remote Area
- Related: Design Area, Hydraulic Calculation
The portion of the sprinkler system hydraulically farthest from the water supply, where pressure is lowest and which therefore governs the calculation. It often corresponds to the design area.
- Sprinkler Spacing
- Related: Coverage Area, Deflector Distance
The maximum permitted distance between adjacent sprinklers and between sprinklers and walls, governed by ceiling height, sprinkler type, and hazard classification.
- Coverage Area
- Related: Sprinkler Spacing, Branch Line
The floor area assigned to one sprinkler, found by multiplying its spacing along branch lines by the distance between branch lines. It limits how much area a single head may protect.
- Deflector Distance
- Related: Sprinkler Spacing, Obstruction
The required vertical clearance between the sprinkler deflector and the ceiling or roof above it, which allows the water spray pattern to develop properly and reach the fire.
- Branch Line
- Related: Cross Main, Coverage Area
The smaller-diameter pipe carrying water to individual sprinklers, fed by a cross main or feed main. Branch line size and the number of heads it serves affect friction loss.
- Cross Main
- Related: Branch Line, Riser
The pipe that supplies water to branch lines and runs perpendicular to them. It is fed by the feed main or riser and is sized to carry the combined flow of all attached branch lines.
- Riser
- Related: Cross Main, Riser Assembly
The vertical pipe that carries water from the supply main or riser assembly up to the sprinkler piping on each floor, including the riser nipple and associated valves and gauges.
- Riser Assembly
- Related: Riser, Main Drain
The arrangement of pipe, fittings, valves, gauges, and drains at the point where the water supply enters the sprinkler system, including the main control valve and check valve.
- Main Drain
- Related: Riser Assembly, Inspector's Test Valve
A valve and pipe connection at the low point of the system used to flush the system and to conduct the main drain flow test, which confirms that the water supply can meet demand.
- Inspector's Test Valve
- Related: Main Drain, Waterflow Alarm
A valve at the remote end of the system that, when opened, simulates the flow of a single sprinkler so the alarm-initiating device and waterflow switch can be tested.
- Waterflow Alarm
- Related: Inspector's Test Valve, Supervisory Signal
A device or switch that detects sustained water movement in the sprinkler piping and sends a signal to the fire alarm panel or monitoring company, indicating that a sprinkler has operated.
- Hazard Classification
- Related: Design Density, Ordinary Hazard
The categorization of an occupancy as light, ordinary, or extra hazard based on the quantity and combustibility of its contents, which determines design density and other requirements.
- Ordinary Hazard
- Related: Hazard Classification, Design Density
An occupancy classification for areas with moderate amounts of combustible contents or moderate dust and lint, requiring a higher design density than light hazard occupancies.
- Obstruction
- Related: Deflector Distance, Sprinkler Spacing
Any building element, such as a beam, duct, or light fixture, that can block the spray pattern of a sprinkler and may require an additional sprinkler or a change in layout.
- NFPA 13
- Related: NFPA 13R, NFPA 25, Design Density
The national standard for the design and installation of automatic fire sprinkler systems, covering occupancy classifications, hydraulic calculations, pipe sizing, and acceptance testing.
- NFPA 13R
- Related: NFPA 13, NFPA 13D
The standard for sprinkler systems in low-rise residential occupancies up to and including four stories, offering reduced requirements compared with full commercial systems.
- NFPA 13D
- Related: NFPA 13R, NFPA 13
The standard for one- and two-family dwellings and manufactured homes, designed to improve life safety rather than protect property, with limited water supply and duration requirements.
- NFPA 25
- Related: NFPA 13, Main Drain, Impairment
The standard for the inspection, testing, and maintenance of water-based fire protection systems, setting frequencies for gauges, valves, alarms, and flow tests after installation.
- NFPA 72
- Related: Waterflow Alarm, Supervisory Signal
The national fire alarm and signaling code, which governs the monitoring, transmission, and testing of sprinkler waterflow and supervisory signals connected to a fire alarm system.
- NFPA 20
- Related: Water Supply Curve, Safety Margin
The standard for stationary fire pumps, covering installation, driver types, controllers, and acceptance testing where the water supply pressure is insufficient for the sprinkler system.
- NFPA 14
- Related: NFPA 13, Riser
The standard for standpipe and hose systems, which are frequently installed alongside sprinkler systems in buildings where hose lines must reach upper floors or large areas.
- State Fire Marshal
- Related: Adopted Standard, Plan Review
The official who administers fire safety laws and rules for the state, including adoption of national standards, licensing, plan review, and enforcement of fire codes.
- Adopted Standard
- Related: State Fire Marshal, NFPA 13
A national consensus code or standard, such as NFPA 13, formally incorporated by reference into state rule so that it carries the force of law in that jurisdiction.
- Plan Review
- Related: Approved Plans, As-Built Drawings, Hydraulic Calculation
The required pre-construction examination of sprinkler drawings, calculations, and specifications by a qualified reviewer to confirm compliance before installation begins.
- Approved Plans
- Related: Plan Review, As-Built Drawings
Drawings and calculations that have been reviewed and stamped or otherwise accepted by the authority having jurisdiction, authorizing installation to proceed according to those documents.
- As-Built Drawings
- Related: Approved Plans, Plan Review
Revised drawings showing the system as actually installed, including field changes from the approved plans, submitted for record and used during future inspections and modifications.
- Authority Having Jurisdiction
- Related: State Fire Marshal, Plan Review
The organization, office, or individual responsible for approving equipment, installations, and procedures, often the state fire marshal's office or a local fire official.
- Acceptance Test
- Related: Main Drain, Hydrostatic Test, Final Inspection
The on-site testing performed when a new sprinkler system is complete, including hydrostatic pressure testing and main drain flow tests, before the system is placed in service.
- Hydrostatic Test
- Related: Acceptance Test, Final Inspection
A pressure test in which the piping is filled with water and pressurized above normal working pressure for a specified period to reveal leaks before the system is accepted.
- Final Inspection
- Related: Acceptance Test, Approved Plans
The last inspection before a certificate of occupancy or system acceptance, confirming that the installed system matches approved plans and passes required tests.
- Impairment
- Related: Shutdown Permit, Fire Watch, NFPA 25
Any condition in which a sprinkler system or portion of it is out of service or unable to perform as designed, triggering notification, a fire watch, and restoration procedures.
- Shutdown Permit
- Related: Impairment, Fire Watch
Written authorization from the authority having jurisdiction allowing a sprinkler system to be taken out of service for a defined period, with conditions for notification and restoration.
- Fire Watch
- Related: Impairment, Shutdown Permit
A temporary patrol by trained personnel, required when a sprinkler system is impaired, to detect fire and notify the fire department until protection is restored.
- Supervisory Signal
- Related: Waterflow Alarm, NFPA 72
An electronic signal indicating an abnormal condition in the sprinkler system, such as a closed control valve or low air pressure, rather than an actual fire.