MI Fire Alarm study materials
MI Fire Alarm study resources

MI Fire Alarm cheat sheet

MI Fire Alarm · Keep the key ideas within reach.

Quick reference

Fire Alarm Systems

  • A conventional (zone) system reports an alarm by zone, not by individual device; the panel identifies the zone, and devices within a zone are not individually annunciated.

  • An addressable system assigns each device a unique address, so the panel annunciates the specific device in alarm, trouble, or supervisory condition.

  • Initiating devices include manual pull stations, smoke detectors, heat detectors, duct detectors, and waterflow switches; notification appliances include horns, strobes, chimes, and speakers.

  • A supervisory signal indicates an off-normal condition of a system or protected equipment (valve closed, low air pressure); a trouble signal indicates a fault in the system itself.

  • Alarm, supervisory, and trouble signals are distinct signal types and must be visually and audibly distinguishable at the control unit.

  • Class A initiating device circuits and notification appliance circuits continue to operate with a single open or ground fault; Class B circuits do not.

  • A waterflow switch on a sprinkler system is an initiating device; a tamper switch on a control valve is a supervisory device.

  • Smoke detectors are generally cross-zoned or verified to reduce nuisance alarms; heat detectors respond to fixed temperature, rate of rise, or both.

Quick reference

Codes and Standards

  • NFPA 72 is the National Fire Alarm and Signaling Code; NFPA 70 (NEC) governs electrical installation, and NFPA 101 governs life safety.

  • NFPA 72 requires a smoke detector within 21 ft of travel along the ceiling to a wall for level ceilings, measured horizontally, unless a specific exception applies.

  • Smoke detectors are generally spaced at 30 ft (900 sq ft per detector) for smooth ceilings; heat detectors at 50 ft spacing (2500 sq ft) for the standard listing.

  • On a peaked or sloped ceiling, detectors are placed near the peak but at least 4 in. down from the peak on the slope.

  • Detectors must be at least 3 ft from supply or return air diffusers to avoid dilution of smoke.

  • Manual pull stations must be mounted between 42 in. and 48 in. above the finished floor, measured to the operating handle.

  • Notification appliance circuits must provide a sound level at least 15 dBA above ambient, or 105 dBA where ambient exceeds 105 dBA, measured 5 ft above the floor.

  • In sleeping areas, sounders must produce at least 75 dBA at the pillow, or 15 dBA above ambient, whichever is greater.

Quick reference

Electrical Fundamentals

  • Ohm's law: V = I × R, where V is volts, I is amperes, and R is ohms.

  • Power: P = V × I = I²R = V²/R, where P is watts.

  • Series circuit: total resistance is the sum of individual resistances; current is the same through all components.

  • Parallel circuit: total resistance is 1/RT = 1/R1 + 1/R2 + ...; voltage is the same across all branches.

  • End-of-line (EOL) resistor value is chosen to match the panel's supervision requirement; a shorted or open EOL causes a trouble condition.

  • A ground fault is an unintentional connection between a conductor and ground; it is detected by the panel's ground-fault monitoring and annunciated as a trouble.

  • Supervised circuits use a small supervisory current to detect opens, shorts, and grounds on the wiring between the panel and field devices.

  • Battery standby capacity is calculated as total standby current times required hours, plus alarm current times alarm duration, with a derating factor applied.

Quick reference

Inspection, Testing and Maintenance

  • NFPA 72 requires acceptance testing before a system is placed in service, and periodic inspection, testing, and maintenance thereafter.

  • Smoke detectors are tested annually (functional test with smoke or manufacturer's listed method); heat detectors are tested annually or per manufacturer.

  • Manual pull stations are tested annually by operating the mechanism and verifying alarm annunciation.

  • Notification appliances are tested annually for audibility and visibility; batteries are inspected quarterly and tested annually.

  • Waterflow switches are tested semiannually (or quarterly where supervised) by opening the inspector's test valve; tamper switches are tested semiannually.

  • Control equipment is inspected monthly or quarterly depending on system type; a record of all tests and inspections must be maintained.

  • A test of a smoke detector using canned smoke verifies the detector's response; a magnet test verifies only the detector's electronic circuit, not the sensing chamber.

  • After any modification, repair, or replacement of a device, the affected portion of the system must be retested before returning to service.

Quick reference

Fire Alarm Systems (continued)

  • A duct smoke detector is used to detect smoke in HVAC ducts and to initiate shutdown of air-handling equipment; it is not a substitute for area detection.

  • Elevator recall is a fire alarm function that, upon alarm, sends elevators to a designated landing and disables normal operation.

  • A sprinkler system's alarm check valve, when it operates, activates a waterflow switch that sends an alarm signal to the panel.

  • A trouble signal must sound at the control unit within a specified time (often 200 seconds) after a fault occurs, depending on the system type.

  • Notification appliance circuits may be Class A or Class B; Class A returns the circuit to the panel, allowing operation with a single fault.

  • A zone is a defined area of the protected premises; addressable systems may group devices into logical zones for annunciation and response.

  • The alarm silence function silences notification appliances but does not reset the system; the reset function clears the alarm condition after the initiating device returns to normal.

Quick reference

Electrical Fundamentals (continued)

  • A short circuit is a low-resistance path that bypasses the normal load, causing excessive current; it is detected as a trouble on supervised circuits.

  • An open circuit is a break in the conductor path; on a supervised circuit it is detected as a trouble condition.

  • Voltage drop along a circuit is calculated as Vdrop = I × Rconductor, where Rconductor depends on wire gauge and length.

  • Wire size is selected based on current-carrying capacity and voltage drop; 14 AWG is rated 15 A, 12 AWG is rated 20 A for typical branch circuits.

  • A transformer steps voltage up or down according to the turns ratio; power is approximately conserved (minus losses).

  • Battery charging circuits maintain standby batteries at a float voltage; a charger failure is annunciated as a trouble.

  • A relay is an electrically operated switch used to control circuits; a supervised relay output can be monitored for fault conditions.

Quick reference

Codes and Standards (continued)

  • NFPA 72 requires that a fire alarm system be installed in accordance with the manufacturer's published instructions and the applicable code edition.

  • Detectors must not be installed within 3 ft of the supply or return air diffuser, and must be at least 4 in. from the wall on a sidewall mount.

  • In corridors, smoke detectors are spaced per the ceiling height and configuration; the 30 ft spacing rule applies to smooth, level ceilings.

  • A fire alarm control unit must be located in an area that is accessible and not subject to physical damage; it must be annunciated at a constantly attended location if required.

  • The authority having jurisdiction (AHJ) approves the installation, witnesses acceptance testing, and may require additional devices or testing.

  • Plans and specifications must be submitted to the AHJ for review before installation begins in most jurisdictions.

  • Record drawings (as-builts) must be maintained and updated to reflect the installed system.

Quick reference

Inspection, Testing and Maintenance (continued)

  • Inspection is a visual examination; testing is the functional operation of a device or system; maintenance is the repair or replacement of components.

  • The annual test of a fire alarm system includes testing initiating devices, notification appliances, and control functions.

  • Sensitivity testing of smoke detectors is required to verify the detector is within its listed sensitivity range; it may be performed with a calibrated test instrument.

  • A detector that fails sensitivity testing must be cleaned, recalibrated, or replaced.

  • Records of inspection, testing, and maintenance must be retained and made available to the AHJ.

  • Testing must not leave the system impaired; if a system is taken out of service, the AHJ and occupants must be notified and a fire watch implemented where required.

  • A smoke detector's sensitivity can drift due to dirt accumulation; the detector's built-in drift compensation may delay a trouble indication until the drift exceeds the compensation range.

Quick reference

Fire Alarm Systems (final)

  • A fire alarm system's primary power source is typically the building's commercial power; a secondary source (batteries or generator) provides standby power.

  • The secondary power supply must be capable of operating the system for a specified duration (often 24 hours standby plus 5 minutes alarm) depending on the system type and code edition.

  • A fire alarm control unit monitors its primary and secondary power sources and annunciates a trouble if either fails.

  • Addressable devices communicate with the panel over a signaling line circuit (SLC); the SLC is supervised for opens, shorts, and grounds.

  • A conventional initiating device circuit is supervised by an end-of-line resistor; the panel detects a change in circuit current to identify an alarm.

  • Notification appliance circuits are supervised and may be Class A or Class B; the circuit must be capable of operating all appliances at their rated voltage.

  • A fire alarm system may interface with other systems (sprinkler, HVAC, elevator, access control) through relay modules or dedicated interfaces.

Quick reference

Electrical Fundamentals (final)

  • A resistor opposes current flow; its value in ohms determines the current for a given voltage.

  • A capacitor stores energy in an electric field; it opposes changes in voltage and is used for filtering and timing.

  • A diode allows current in one direction only; it is used for rectification and protection.

  • Alternating current (AC) reverses direction periodically; direct current (DC) flows in one direction.

  • The RMS value of a sinusoidal AC voltage is approximately 0.707 times the peak value.

  • A ground fault circuit interrupter (GFCI) detects a difference between line and neutral current and opens the circuit; it is not a substitute for a fire alarm ground-fault monitor.

  • Battery capacity is rated in ampere-hours (Ah); the available energy is approximately the Ah rating times the nominal voltage.

Quick reference

Codes and Standards (final)

  • NFPA 72 requires that smoke detectors be installed on the ceiling or, if wall-mounted, between 4 in. and 12 in. from the ceiling.

  • Detectors must be at least 3 ft from the supply or return air diffuser to avoid dilution of smoke by air movement.

  • On a sloped ceiling, detectors are placed within 3 ft of the peak, measured horizontally, but at least 4 in. down from the peak.

  • Manual pull stations must be located within 5 ft of the exit door and mounted 42 in. to 48 in. above the floor.

  • Notification appliances must be audible throughout the protected area; in sleeping areas, the sound level at the pillow must be at least 75 dBA.

  • Strobes must be visible from all points in the protected area; the candela rating and mounting height determine coverage.

  • The AHJ has the authority to interpret the code and to require additional fire alarm devices or testing.

Quick reference

Inspection, Testing and Maintenance (final)

  • Smoke detectors are tested annually; the test method must verify the detector's ability to respond to smoke, not just its electronic circuit.

  • Heat detectors are tested annually with a listed heat source or per the manufacturer's instructions.

  • Manual pull stations are tested annually by operating the mechanism and verifying the alarm signal.

  • Notification appliances are tested annually for audibility, visibility, and correct operation.

  • Batteries are inspected quarterly and tested annually; a load test verifies the battery's ability to supply the required current.

  • Waterflow switches are tested semiannually by opening the inspector's test valve; tamper switches are tested semiannually.

  • A record of all inspection, testing, and maintenance activities must be maintained and made available to the AHJ.