Zone (conventional system)
A defined area of the protected premises; a conventional panel reports alarms by zone rather than by individual device, so the exact device is not annunciated.
Addressable device
A field device with a unique address that the control unit can identify individually for alarm, trouble, and supervisory annunciation.
Supervisory signal
A signal indicating an off-normal condition of a system or protected equipment, such as a closed valve or low air pressure, distinct from alarm and trouble.
Trouble signal
A signal indicating a fault in the fire alarm system itself, such as an open circuit, ground fault, or power failure.
Class A circuit
An initiating device or notification appliance circuit that continues to operate with a single open or ground fault because the circuit returns to the panel.
Waterflow switch
An initiating device on a sprinkler system that detects water flow and sends an alarm signal to the fire alarm control unit.
NFPA 72
The National Fire Alarm and Signaling Code, which governs the installation, testing, and maintenance of fire alarm systems in the United States.
Smoke detector spacing
For smooth, level ceilings, smoke detectors are generally spaced at 30 ft, covering up to 900 square feet per detector.
Pull station height
Manual fire alarm pull stations must be mounted between 42 in. and 48 in. above the finished floor, measured to the operating handle.
Sleeping area audibility
In sleeping areas, notification appliances must produce at least 75 dBA at the pillow, or 15 dBA above ambient, whichever is greater.
Diffuser clearance
Smoke detectors must be at least 3 ft from supply or return air diffusers to prevent air movement from diluting smoke and delaying detection.
Ohm's law
The relationship V = I × R, where V is voltage in volts, I is current in amperes, and R is resistance in ohms.
Electrical power formula
Power in watts equals voltage times current (P = V × I); it also equals I²R and V²/R for resistive circuits.
Series circuit resistance
In a series circuit, total resistance is the sum of the individual resistances, and the same current flows through every component.
Parallel circuit resistance
In a parallel circuit, the reciprocal of total resistance equals the sum of the reciprocals of the branch resistances, and voltage is the same across branches.
End-of-line resistor
A resistor at the end of a supervised circuit that allows the panel to detect opens and shorts by monitoring circuit current.
Ground fault
An unintentional connection between a conductor and ground, detected by the panel's ground-fault monitoring and annunciated as a trouble condition.
Battery standby calculation
Standby capacity equals standby current times required hours plus alarm current times alarm duration, with a derating factor applied.
Acceptance test
A functional test of a newly installed fire alarm system, witnessed by the authority having jurisdiction, before the system is placed in service.
Smoke detector annual test
A yearly functional test using smoke or the manufacturer's listed method to verify the detector responds to smoke, not just its electronic circuit.
Waterflow switch test
A semiannual test performed by opening the inspector's test valve to verify the waterflow switch sends an alarm signal to the panel.
Tamper switch test
A semiannual test of the supervisory switch on a sprinkler control valve to verify it annunciates a supervisory signal when the valve is moved.
Duct smoke detector
A detector installed in an HVAC duct to sense smoke and initiate shutdown of air-handling equipment; it does not replace area smoke detection.
Elevator recall
A fire alarm function that, upon alarm, sends elevators to a designated landing and disables normal operation to protect occupants.
Alarm silence function
A control unit function that silences notification appliances without resetting the system; the alarm condition remains until reset.
Signaling line circuit
The supervised circuit over which an addressable panel communicates with field devices, monitored for opens, shorts, and grounds.
Voltage drop
The loss of voltage along a conductor, calculated as Vdrop = I × Rconductor, where resistance depends on wire gauge and length.
Open circuit
A break in the conductor path that stops current flow; on a supervised fire alarm circuit it is detected and annunciated as a trouble condition.
Short circuit
A low-resistance path that bypasses the normal load, causing excessive current; on a supervised circuit it is detected as a trouble condition.
Authority having jurisdiction
The organization or official responsible for approving fire alarm installations, witnessing acceptance tests, and enforcing the applicable code.
As-built drawings
Record drawings maintained and updated to reflect the installed fire alarm system, including device locations and circuit routing.
Sensitivity testing
A test verifying a smoke detector operates within its listed sensitivity range; detectors failing the test must be cleaned, recalibrated, or replaced.