92 psi at the Meter and a Third-Floor Shower

At a new three-story house in Ann Arbor the static water pressure measured at the meter outlet is 92 psi. The meter is a 5/8-inch meter, and the longest developed length from the meter to the third-floor shower is 130 feet of 3/4-inch copper. The shower head is 28 feet above the meter. The installer proposes to skip a pressure-reducing valve because 'the city usually runs about 60 psi,' and he plans to install a tankless water heater in the basement with a check valve on the cold inlet. At the design flow of 8 gpm, the meter and service losses total 6 psi and the pipe friction loss on this run is 9 psi. He also wants to run the last 20 feet of 1/2-inch PEX through an unconditioned attic.

1. Is a pressure-reducing valve required, and at what setting? What else does the PRV (or the check valve) make necessary?

Read the worked answer

Yes - a PRV is required. The code threshold is 80 psi: where the static pressure on the downstream side of the meter exceeds 80 psi, a pressure-reducing valve must be installed. A measurement of 92 psi triggers the requirement, and 'the city is usually about 60' is not a defense - the system must be protected against the pressure that actually exists, including nighttime surges.

Setting: adjust the PRV to a downstream pressure not exceeding 80 psi; 50 to 60 psi is the practical target. Set it high enough that the third-floor fixtures still get their minimum residual pressure (see next task) and low enough to protect fixtures, the water heater, and appliances. PRVs must be accessible and provided with a strainer, and the installation should include a means to relieve thermal expansion.

Closed system / thermal expansion: a PRV, a check valve, or a backflow preventer on the supply creates a closed system. A tankless water heater with a check valve on the cold inlet certainly does. Once the system is closed, heated water has nowhere to expand, so a listed thermal expansion tank (and often a thermal expansion relief valve) is required on the cold side of the water heater. Without it, pressure spikes on every heating cycle and can blow the T&P valve or damage the tankless unit.

2. With the PRV set at 60 psi, calculate the residual pressure at the third-floor shower. Is it adequate? Show the arithmetic.

Read the worked answer

Start from the pressure that is actually available, then subtract each loss.

  1. Available pressure downstream of the PRV: 60 psi.
  2. Elevation loss: water column pressure = 0.433 psi per foot of height. 28 ft x 0.433 = 12.1 psi
  3. Meter and service loss at 8 gpm: 6 psi
  4. Pipe friction on the 130-foot developed length at 8 gpm: 9 psi

Residual pressure at the shower:

60 - 12.1 - 6 - 9 = 32.9 psi

That is comfortably above the 8 psi minimum residual required at a shower (the fixture minimums for ordinary fixtures generally fall in the 8 psi range; flushometer valves need substantially more, roughly double). Even if the PRV were set at 50 psi, the residual would be about 22.9 psi - still acceptable.

What this tells the installer:

  • The elevation penalty is real and often forgotten. At 28 feet the column costs about 12 psi before a drop of water moves.
  • The check on a water supply design is always: available pressure minus elevation minus device losses minus friction, compared to the fixture minimum - not static pressure at the meter.
  • If the run had been much longer or the flow higher, the 3/4-inch main would be the place to look first; increasing pipe size reduces friction far more effectively than raising the PRV setting.

3. Evaluate the plan to run the last 20 feet of 1/2-inch PEX through the unconditioned attic. What are the code and practical problems, and what would you require?

Read the worked answer

Freezing. Michigan winters will freeze a pipe in an unconditioned attic. Water piping in unconditioned or exposed locations must be protected from freezing: either keep the run inside the building's thermal envelope, or insulate and protect it with listed heat trace and insulation on a thermostatically controlled circuit. Simply insulating a pipe in a vented attic does not protect it - insulation slows heat loss, it does not add heat.

Other requirements for the attic run:

  • PEX must be protected from UV light and from physical damage; in an attic it needs protection from sunlight at penetrations, and supports at the manufacturer's spacing.
  • Insulation and heat trace must not be concealed in a way that prevents inspection or replacement.
  • Provide freeze protection on the entire exposed length, not just 20 feet of it - the fixture branch's vulnerable section is the whole exposed portion.

Sizing note: if the 20-foot segment carries the full 8 gpm design flow, 1/2-inch PEX is far too small - velocity and friction loss become excessive and the shower will be noisy and weak. If it is a branch serving only the shower (roughly 2 to 2.5 gpm), 1/2-inch is normally fine. Confirm which load that segment actually carries and size it accordingly; use 3/4 inch if it carries the group load.