MI Plumber study materials
MI Plumber study resources

MI Plumber cheat sheet

MI Plumber · Keep the key ideas within reach.

Quick reference

General Regulations, Definitions, and Administration

  • A plumbing permit must be obtained before installing, altering, replacing, or repairing a plumbing system; ordinary minor repairs defined in the code are exempt.

  • "Approved" means accepted by the code official, typically supported by listing and labeling by a recognized third-party testing agency.

  • The building drain ends 30 inches outside the exterior wall; the building sewer begins at that point and runs to the public sewer or private sewage disposal system.

  • One drainage fixture unit (dfu) represents roughly 1 gallon per minute of probable discharge; water supply fixture units are derived from Hunter's probability curve.

  • No fixture drain may be smaller than 1-1/4 inches, and no drainage pipe may be smaller than the outlet of the fixture it serves.

  • The code official may require plans, specifications, and sizing computations for systems exceeding the thresholds stated in the code.

  • Plumbing work must be performed by a licensed plumber under a licensed plumbing contractor, with rough-in and final inspections required before concealment and occupancy.

  • Alternate materials, methods, and equipment require written approval from the code official before installation.

Quick reference

Drainage Systems

  • Horizontal drainage slope is 1/4 inch per foot (2 percent) for pipe 2-1/2 inches and smaller and 1/8 inch per foot (1 percent) for pipe 3 inches and larger.

  • Horizontal drainage pipe is supported at intervals from the code table (commonly 4 feet for plastic and 5 feet for cast iron); stacks are supported at the base and at each story.

  • A horizontal drain turning 90 degrees uses a long-sweep fitting or two 45-degree bends; a horizontal branch enters a vertical stack through a sanitary tee.

  • Cleanouts are required at the upper end of horizontal drains, at the base of each stack, at aggregate direction changes of 135 degrees, and within 5 feet of the building sewer.

  • Typical fixture units: water closet 3, lavatory 1, bathtub or shower 2, kitchen sink 2, washing machine 2, dishwasher 2, 2-inch floor drain 2.

  • A horizontal drain joining another horizontal drain uses a wye fitting with a 1/8 bend (combination); tees are not permitted in the horizontal position for drainage.

  • Building drains and building sewers serving water closets are minimum 3 inches and are sized by total fixture units from the code tables.

  • A backwater valve is required where the building drain is below the flood level rim of the next upstream manhole and must remain accessible.

Quick reference

Vents and Venting

  • Every trap must be protected by a vent, and the vent must connect within the maximum trap arm length permitted for that pipe size.

  • Trap arm limits at 1/4-inch slope: 1-1/4 inch = 5 feet, 1-1/2 inch = 6 feet, 2 inch = 8 feet; at 1/8-inch slope 3 inch = 12 feet and 4 inch = 16 feet.

  • A vent may not be smaller than 1-1/4 inches and may not be smaller than one-half the diameter of the drain it serves.

  • A dry vent must rise vertically, or at no more than 45 degrees from vertical, until it reaches at least 6 inches above the flood level rim of the highest served fixture.

  • A vent terminal must extend at least 6 inches above the roof, or 7 feet where the roof is used for purposes other than weather protection; in frost-closure areas the terminal is increased to 3-inch pipe.

  • Open vent terminals must be located at least 10 feet from windows, doors, and outdoor air intakes.

  • A wet vent may serve only fixtures on the same floor and must be at least 2 inches where it drains a water closet.

  • Air admittance valves are permitted only where the code allows, must be installed above the fixture flood level rim, and must remain accessible.

Quick reference

Water Supply and Distribution

  • Static pressure above 80 psi requires a pressure reducing valve; a minimum residual pressure of about 8 psi is required at fixture outlets under flow.

  • Minimum fixture supply sizes: water closet 1 inch, lavatory 3/8 inch, sink 1/2 inch, bathtub 1/2 inch, shower 1/2 inch.

  • Horizontal water pipe is supported at intervals from the code table (typically 12 feet or less); vertical pipe is supported at each floor.

  • Backflow protection: air gap for severe hazards, reduced-pressure zone assembly for high hazards, and vacuum breakers for low hazards; testable assemblies require periodic testing.

  • Water heaters require a temperature and pressure relief valve with a full-size discharge pipe flowing by gravity and terminating within 6 inches of the floor or outside the building.

  • Water service pipe must be buried below the local frost depth and protected from freezing at exposed locations.

  • The water distribution system is tested tight at not less than the working pressure before piping is concealed.

  • A main shutoff valve is required on the water service, and drain valves are provided for winterizing the system.

Quick reference

Fixtures, Fixture Fittings, and Appliances

  • Water closet clearances: 15 inches from centerline to any side wall, 30 inches center-to-center, and 21 inches of clear space in front of the bowl.

  • A lavatory requires 15 inches from its centerline to a side wall; fixtures must be spaced to allow use and cleaning.

  • Shower compartments must be at least 30 inches by 30 inches inside, drain through a minimum 2-inch drain, and have a finished curb unless designed as an accessible roll-in shower.

  • Fixtures must be constructed of smooth, nonabsorbent, corrosion-resistant material and installed to allow cleaning and access to concealed parts.

  • Each fixture must be provided with an approved water supply, a trap, and a drainage connection sized from the code tables.

  • Water heater pans are required where leakage would cause damage, with the pan drain discharging by gravity to an approved location.

  • Handwashing lavatories are required in toilet rooms and food service areas, and drinking fountains may not be located in toilet rooms.

Quick reference

Traps, Interceptors, and Special Wastes

  • Trap seal depth must be at least 2 inches and not more than 4 inches, measured between the trap weir and the top of the trap dip.

  • Each fixture must be separately trapped except for listed combinations such as a single trap serving a set of approved fixtures.

  • S-traps, bell traps, crown vents, traps with moving parts, and traps for fixtures with integral traps such as water closets are prohibited.

  • A grease interceptor is required for food service establishments and is sized by the code formula or table, with access for cleaning and periodic pumping.

  • Oil and water separators are required where flammable liquids or petroleum products may enter the drainage system and must be vented per code.

  • Sand and grit interceptors are required for vehicle service and wash areas, must be accessible, and must be vented.

  • Corrosive or high-temperature wastes require neutralization or cooling before discharge, and boiler blowdown must not enter a building drain untreated.

  • Interceptors must be provided with a vent sized and installed per the venting provisions of the code.

Quick reference

Storm Drainage

  • Storm drainage must be conveyed separately from sanitary drainage unless the authority having jurisdiction approves a combined connection.

  • Roof drains and leaders are sized from code tables using the roof area served and the 100-year, one-hour rainfall rate for the location.

  • A roof with a parapet that uses roof drains requires a secondary drain or scupper set at least 2 inches above the primary drain or low point.

  • Storm drainage pipe follows the same slope rules as sanitary: 1/4 inch per foot for 2-1/2 inches and smaller, 1/8 inch per foot for 3 inches and larger.

  • Vertical leaders and conductors must be supported at each story and at the base, and must be anchored to resist wind and water movement.

  • Subsoil and footing drains must discharge to an approved location and may not be connected to the sanitary building sewer unless specifically approved.

  • Sump pumps discharge to a storm sewer, splash block, or approved drywell; they may not discharge into the sanitary sewer unless permitted.

Quick reference

Plumbing Math, Sizing, and Isometric Analysis

  • Fall in inches = slope in inches per foot multiplied by run in feet; 1/4 inch per foot over a 20-foot run gives 5 inches of fall.

  • 45-degree offset: travel = offset x 1.414, and offset = travel x 0.707. At 22.5 degrees travel = offset x 2.613; at 60 degrees travel = offset x 1.155.

  • Pressure to head: psi = feet of water divided by 2.31, and feet of head = psi x 2.31; a 10-foot column equals about 4.33 psi.

  • Gallons contained in a pipe = 0.785 x D-squared x length divided by 231, with diameter and length measured in inches.

  • Roof runoff in gallons per minute = roof area in square feet x rainfall rate in inches per hour x 0.0104.

  • A bathroom group of water closet, lavatory, and bathtub or shower totals 6 drainage fixture units.

  • Water heater recovery gallons per hour = (Btu/hr input x efficiency) divided by (8.33 x temperature rise in degrees F).

  • Bend designations: 1/16 bend = 22.5 degrees, 1/8 bend = 45 degrees, 1/6 bend = 60 degrees, and 1/4 bend = 90 degrees.

Quick reference

Safety, Tools, and Installation Practices

  • Excavations 5 feet deep or more require a protective system such as sloping, shoring, or a trench shield, and a competent person must inspect the excavation daily.

  • Spoil and materials are kept at least 2 feet back from the trench edge, and a ladder must be within 25 feet of lateral travel in trenches 4 feet or deeper.

  • Portable ladders are set at a 4-to-1 base-to-height ratio and extend at least 3 feet above the landing surface.

  • Compressed air testing of drainage piping is limited to about 5 psi because stored energy in air can cause violent pipe failure.

  • Soldering requires lead-free solder and approved flux; tubing must be reamed and cleaned, flux residue removed, and combustibles protected during hot work.

  • Solvent cement must match the plastic pipe material, primer is applied before cement, and the joint must cure before pressure testing.

  • Plastic drainage pipe is supported at 4-foot intervals with approved hangers that do not crush or deform the pipe.

  • Entry into vaults, pits, and sewers requires a confined space permit, atmospheric testing, an attendant, and a rescue plan.

Quick reference

Fuel Gas Piping and Gas-Fired Appliances

  • Gas piping is sized by the longest-length method using total connected load in Btu/hr, gas specific gravity, and available pressure drop from the code tables.

  • Minimum gas piping size is 1/2 inch; concealed gas piping may not contain unions and may not pass through ducts, chimneys, or elevator shafts.

  • A sediment trap (drip leg) is required at each appliance, and a shutoff valve must be installed within 6 feet of the appliance in the same room.

  • Gas piping must be bonded to the premises grounding electrode system, and corrugated stainless steel tubing must be bonded per the manufacturer's instructions.

  • Gas piping is leak tested with air or inert gas at 1.5 times the working pressure, but not less than 3 psi, for at least 10 minutes.

  • Flexible appliance connectors may not exceed 6 feet, may not pass through walls, floors, or ceilings, and may not be concealed.

  • Clearance to combustibles is 6 inches for single-wall vent connectors and 1 inch for listed Type B vent.

  • Combustion air for a confined space is provided by two permanent openings or by 50 cubic feet of volume per 1,000 Btu/hr of input where infiltration is used.