MN Journeyman Electrician flashcards
MN Journeyman Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- E = I × R, where E is voltage in volts, I is current in amperes, and R is resistance in ohms. Combine with P = E × I to solve any two-variable problem.
- Voltage Drop Formula
- Single-phase: VD = 2 × K × I × L / CM. Use K = 12.9 for copper, 21.2 for aluminum. Three-phase multiplies by 1.732 instead of 2.
- Series Circuit Characteristics
- Current is identical through every element, voltages add, and total resistance equals the sum of resistances. A break anywhere stops current in the entire circuit.
- Parallel Circuit Characteristics
- Voltage is the same across all branches, branch currents add to total current, and total resistance is less than the smallest branch resistance.
- Conductor Adjustment Table
- Table 310.15(C)(1): 4-6 current-carrying conductors reduce ampacity to 80%, 7-9 to 70%, 10-20 to 50%, and 21-30 to 45%.
- NM-B Cable Restrictions
- Nonmetallic-sheathed cable is limited to normally dry locations. It is not permitted in wet locations, embedded in concrete, or in masonry voids, and must be protected from physical damage.
- EMT Support Requirements
- Electrical metallic tubing must be supported within 3 ft of each box and at intervals not exceeding 10 ft. The minimum trade size is 1/2 inch.
- Box Fill Conductor Volumes
- Article 314.16 volumes per conductor: 14 AWG = 2.00 cu in, 12 AWG = 2.25, 10 AWG = 2.50, 8 AWG = 3.00. Each device yoke counts as two of the largest conductor.
- Raceway Fill Percentages
- Chapter 9 fill limits: one conductor = 53% of interior area, two conductors = 31%, three or more conductors = 40%.
- PVC Schedule 40 Supports
- Support intervals: 3 ft for 1/2 through 1 inch trade sizes, 5 ft for 1 1/4 through 2 inch, and 6 ft for larger sizes.
- Dwelling General Lighting Load
- Dwelling units require 3 VA per square foot of floor area. Apply Table 220.42 demand factors: first 3,000 VA at 100%, next at 35%, remainder at 25%.
- Small-Appliance Branch Circuits
- At least two 20 A circuits are required for dwelling kitchen, pantry, and laundry areas. Each counts 1,500 VA in the load calculation.
- Optional Dwelling Calculation
- NEC 220.82: first 10,000 VA of the total load at 100%, the remainder at 40%, then add the larger of heating or air conditioning at 100%.
- Range Demand Table
- Table 220.55: a single range rated up to 12 kW may be calculated at 8,000 VA. Add 5% for each kW above 12 kW.
- Standard OCPD Ratings
- NEC 240.6(A) ratings include 15, 20, 25, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150, 200, 400, and 600 A. Devices must be selected from this list.
- Next-Size-Up Rule
- NEC 240.4(B) allows the next higher standard OCPD only when ampacity is not a standard rating, the device is 800 A or less, and the next rating does not exceed conductor ampacity.
- Small Conductor Protection
- NEC 240.4(D): 14 AWG copper is limited to 15 A, 12 AWG to 20 A, and 10 AWG to 30 A, unless a specific permission in 240.4(E) or (G) applies.
- AFCI Requirement
- NEC 210.12 requires arc-fault circuit-interrupter protection for 15 and 20 A branch circuits supplying outlets in dwelling living areas, bedrooms, closets, and hallways.
- GFCI Locations
- NEC 210.8 requires GFCI protection for 15 and 20 A, 125 V receptacles in bathrooms, garages, outdoors, unfinished basements, kitchens, laundry areas, and near sinks.
- Grounding Electrode System
- NEC 250.50 requires all available electrodes to be bonded together, including metal water pipe, building frame, concrete-encased electrode, ground ring, and rod electrodes.
- Equipment Grounding Conductor Size
- Table 250.122 sizes the equipment grounding conductor from the OCPD rating: 15 A = 14 AWG copper, 60 A = 10 AWG, 100 A = 8 AWG, 200 A = 6 AWG.
- Grounding Electrode Conductor Size
- Table 250.66 bases the grounding electrode conductor on the largest service conductor: 2 AWG or smaller = 8 AWG copper; 1/0-3/0 = 4 AWG; 250-500 kcmil = 2 AWG.
- Single Rod Supplement
- NEC 250.53(A)(2): a single rod, pipe, or plate electrode with resistance over 25 ohms must be supplemented by an additional electrode.
- Main Bonding Jumper
- The main bonding jumper connects the grounded service conductor to the equipment grounding conductor at the service. It is sized from Table 250.102(C)(1).
- Motor Branch Conductor Size
- Motor branch-circuit conductors must have ampacity at least 125% of the motor full-load current from Tables 430.248 through 430.250.
- Motor Short-Circuit Protection
- Table 430.52: inverse-time breaker = 250% of FLC, dual-element fuse = 175%, non-time-delay fuse = 300%. The next standard size up is permitted if needed.
- Motor Overload Protection
- NEC 430.32: overload devices are sized at 125% of FLA for motors marked 40°C or less temperature rise, and 115% for motors marked above 40°C.
- Motor Disconnect Rating
- The motor disconnecting means must be within sight of the motor and controller, lockable open, and rated at least 115% of the motor full-load current.
- Transformer Current Formula
- Primary current = kVA × 1,000 / primary voltage. For three-phase, divide by 1.732 × voltage. Secondary current uses the secondary voltage in the same formula.
- Minnesota Code Adoption
- Minnesota adopts the National Electrical Code through Minnesota Rules Chapter 1315, enforced with state amendments published by the Department of Labor and Industry.
- Minnesota Licensing Board
- The Minnesota Board of Electricity issues journeyman, master, and registered unlicensed electrician credentials and investigates complaints against licensees.
- Minnesota Journeyman Requirements
- A journeyman electrician license requires documented practical experience, typically four years or 8,000 hours, plus passage of the Board's journeyman examination.