Nightly RPZ Discharge in an Office Building with Multiple Cross-Connections

MN Plumber · Put your knowledge to work in context.

All case studies

Nightly RPZ Discharge in an Office Building with Multiple Cross-Connections

A 1-1/2-inch domestic water service enters a three-story office building and immediately passes through a reduced-pressure zone (RPZ) backflow assembly at the meter. The basement cafeteria has a carbonated beverage dispenser with a CO2 tank and a booster pump, a 1-inch irrigation line tapped downstream of the RPZ serving 12 pop-up sprinkler heads with a fertilizer injection system, a boiler fill line with chemical treatment, and a mop sink with a threaded hose bibb on the loading dock. The building engineer reports that the RPZ relief port discharges a steady stream every night at 2 a.m., about the time the irrigation controller starts. The engineer wants to turn off the irrigation and plug the relief port until the sprinklers are needed. Last year's test tag on the RPZ is dated 13 months ago.

1. Identify the required backflow protection for each connection and explain why the service RPZ alone is not enough.

Read the worked answer

The service RPZ is containment protection; it protects the public main from backflow out of the building. It does not protect building occupants from cross-connections inside the building, so each high-hazard connection needs isolation protection.

The irrigation system with fertilizer injection is a high hazard and requires an RPZ, not a pressure vacuum breaker, because the injection can create a health hazard and backpressure. The carbonated beverage dispenser with a CO2 tank and booster pump also requires an air gap or an RPZ; a simple dual check is not adequate for CO2 backpressure. The boiler fill line with chemical treatment requires an RPZ or an air gap. The threaded hose bibb requires a hose-connection vacuum breaker or an air gap; a plain threaded outlet without protection is a cross-connection. The mop sink itself should have an air gap or a properly installed vacuum breaker if a hose is attached.

The service RPZ and the fixture/appliance protection serve different purposes and both are required for a code-compliant installation.

2. Diagnose the nightly RPZ discharge. What should be done, and why is plugging the relief port unacceptable?

Read the worked answer

The RPZ relief port opens when the pressure differential across the first check changes beyond the assembly's design, often because the first check is fouled, damaged, or held open by debris. The timing with irrigation startup suggests a pressure fluctuation or a check that is not seating. The correct procedure is to isolate the assembly, disassemble and inspect the first and second checks and the relief valve, clean or replace parts with manufacturer-approved components, and retest with a calibrated differential-pressure test kit. Do not adjust the relief spring to stop the drip.

Plugging the relief port defeats the assembly's protection and can allow contaminated water to backflow into the potable system. It is also a violation of the cross-connection requirements and can create a health hazard for the building and the public main. If the assembly cannot be repaired promptly, keep it isolated and provide an approved temporary air gap or other approved protection; do not leave the building without backflow protection.

3. What are the testing and reporting requirements, and what does the 13-month-old tag tell you?

Read the worked answer

The tag shows the assembly has not been tested within the required annual interval. Reduced-pressure zone assemblies must be tested at least annually by a certified backflow assembly tester, and the test report must be submitted to the water utility or the authority that administers the cross-connection program. The test is not a visual check; it verifies the first-check differential, the second-check differential, and the relief-valve opening point.

After the repair, the assembly must be retested and a new report filed before it is returned to service. The building owner should also correct the irrigation, carbonator, boiler, and hose-bibb protection and maintain records for each assembly. Because the RPZ is at the service, the utility may treat a failure to test or a plugged relief port as a serious violation and may require correction or termination of service.