MN Plumber study materials
MN Plumber study resources

MN Plumber cheat sheet

MN Plumber · Keep the key ideas within reach.

Quick reference

General Regulations, Licensing, and Administration

  • Plumbing work must be performed by a licensed master or journeyman plumber, or by an apprentice under direct supervision; permits are required before installing, altering, or replacing a plumbing system.

  • A permit is generally not required for minor repairs such as clearing stoppages, replacing a faucet washer, or replacing a toilet tank flapper; replacing a water heater or repiping requires a permit.

  • Inspections occur in stages: rough-in (before concealment), water and drainage testing, and final inspection after fixtures are set and trim is complete.

  • Concealed work must be tested and approved before covering; the code official may require removal of covering installed before inspection at the installer's expense.

  • Licenses are issued by the state or local authority, carry an expiration date, and require continuing education hours for renewal; unlicensed contracting is a misdemeanor with fines.

  • A contractor must carry a bond and liability insurance; bonding protects the public against incomplete or defective work and code violations.

  • Code editions are adopted by reference with local amendments; the stricter provision governs when local amendments conflict with the model code.

  • Plans and specifications for commercial projects must be submitted for plan review by a licensed engineer or architect before a permit is issued.

  • Stop-work orders may be issued for work without a permit, unsafe conditions, or deviations from approved plans; work resumes only after the order is lifted.

Quick reference

Definitions, General Requirements, and Plumbing System Design

  • Potable water is water free from impurities in amounts sufficient to cause disease or harmful physiological effects, meeting the primary and secondary drinking water standards.

  • A fixture unit (f.u.) is a measure of the probable discharge load of a fixture; 1 f.u. equals 1 cubic foot per minute (7.5 gpm) of flow or 1 gallon per minute of drainage load, depending on the table used.

  • A stack is a vertical drainage pipe carrying waste; a vent stack serves the drainage stack, and a stack vent is the extension of a drainage stack above the highest fixture branch.

  • A branch is a pipe between a fixture and a stack, main, or branch; a main is the primary pipe carrying water or drainage to the sewer or from the water main.

  • Building drain receives discharge inside the building and connects to the building sewer at a point 2 feet outside the building wall.

  • A plumbing system includes water supply, fixtures, drainage, venting, traps, and the building sewer; all must be designed for gravity flow and adequate venting.

  • Minimum slope for horizontal drainage: 1/4 inch per foot for pipe 2-1/2 inches and smaller, 1/8 inch per foot for 3 inches and larger (or per local amendment).

  • Water supply design uses demand load from fixture units converted to gallons per minute; the system must maintain minimum residual pressure at the highest fixture, typically 8 psi for flush tanks and 15 psi for flushometers.

  • The plumbing code requires protection against freezing, structural damage, and contamination; piping must be supported, sleeved through masonry, and isolated from corrosive soils.

Quick reference

Fixtures, Fixture Fittings, and Water Heaters

  • Water closets are rated in gallons per flush (gpf): 1.6 gpf maximum for standard tanks, 1.28 gpf for high-efficiency models; urinals are 1.0 gpf or less.

  • Fixture clearances: water closets require 15 inches from centerline to side wall and 30 inches of clear width; 21 inches of clearance from the front of the fixture to an obstruction.

  • Shower compartments require a minimum of 900 square inches of interior area and 30 inches minimum dimension; shower valves must be pressure-balancing or thermostatic anti-scald type.

  • A water heater's temperature and pressure relief (T&P) valve must be rated for the heater's input and discharge to a safe location, terminating 6 to 24 inches above the floor or outside.

  • Water heaters must be installed with seismic strapping (two straps, upper and lower third) where required, and a drip pan when leakage could cause damage.

  • Expansion tanks are required on closed systems to absorb thermal expansion; the tank is sized to the system volume and temperature rise.

  • Fixture fittings must be listed and labeled; backflow protection is required at hose bibs, sill cocks, and any connection that could allow contamination.

  • Water heater flue connections must maintain proper draft; the vent connector rises toward the chimney and the heater needs combustion air from the space or outside.

Quick reference

Water Supply and Distribution

  • Minimum water service size is typically 3/4 inch for a single dwelling; size depends on fixture-unit demand and developed length of pipe.

  • Pressure-reducing valves are required when street pressure exceeds 80 psi; 50 to 60 psi is the typical target for a residence.

  • Water supply pipe sizing uses fixture-unit tables converted to gpm; velocity should not exceed 8 fps in cold water and 5 fps in hot water to limit noise and erosion.

  • Thermal expansion of hot water lines requires allowance for movement; plastic pipe expands about 1 inch per 100 feet per 10 degrees F temperature change.

  • PEX and CPVC require protection from UV and freeze; copper requires dielectric unions at steel connections to prevent galvanic corrosion.

  • Water distribution systems must be tested at working pressure for at least one hour; hydrostatic test pressure is typically 100 psi or system working pressure.

  • A water main must be at least 10 feet horizontally from a building sewer or 18 inches below it when crossing, per typical separation requirements.

  • Hot water distribution should minimize dead legs; recirculation lines or point-of-use heaters reduce wait time and waste.

  • Backflow preventers are required at the service entrance when a private well, irrigation system, or boiler is connected.

Quick reference

Sanitary Drainage and Venting

  • Drainage pipes must be sized by fixture units and slope; a 3-inch building drain at 1/8 inch per foot carries about 40 fixture units, while 4-inch carries about 180.

  • Vent stacks must extend at least 6 inches above the roof and be sized per drainage stack size; a 1-1/2 inch vent stack is minimum for most dwellings.

  • Each trap requires a vent; a fixture may be wet-vented only where the code allows and within specified distance limits.

  • Horizontal drainage branch length from trap to vent is limited (typically 5 feet for 1-1/2 inch, 6 feet for 2 inch, 8 feet for 3 inch).

  • A cleanout is required at the base of each stack, at the building drain near the sewer, and at changes of direction greater than 45 degrees.

  • Drainage fittings must be directional (sweep fittings); sanitary tees are used on vertical-to-horizontal changes, wyes on horizontal-to-horizontal.

  • The building drain must be tested with water or air before concealment; a 10-foot head of water or 5 psi air is typical.

  • Vent terminals must be at least 10 feet from windows or air intakes and 3 feet above roof penetrations within 10 feet.

  • A combination waste and vent system is permitted only for specific fixtures and must be sized with the drain serving as the vent.

Quick reference

Storm Drainage

  • Storm drainage must be separate from sanitary drainage; combined systems are allowed only where the public sewer is combined and the authority approves.

  • Roof drains are sized by roof area and rainfall intensity (inches per hour); the design storm is specified by local code.

  • A 4-inch roof drain leader at 1/8 inch per foot carries roughly 180 fixture units or about 4,000 square feet of roof at 1 inch per hour.

  • Secondary (overflow) roof drainage is required where the primary system could be blocked; scuppers or secondary drains must discharge to a visible location.

  • Storm drainage may not discharge into the sanitary sewer unless approved; it must go to a storm sewer, dry well, or approved dispersal area.

  • Leader and storm drain pipe must be supported and protected from freezing; cleanouts are required at the base of leaders and at changes of direction.

  • Sizing tables use the roof area and rainfall rate to determine leader and horizontal storm drain diameter; steeper slopes increase capacity.

  • Sump pumps and area drains must discharge to an approved location and cannot connect to the sanitary sewer without approval.

  • Storm drainage systems require testing similar to sanitary systems; water test or smoke test may be used.

Quick reference

Traps, Interceptors, and Special Wastes

  • Each fixture must have a trap with a liquid seal of 2 to 4 inches; trap arms must be protected from siphonage by venting.

  • A trap may serve one fixture only; except for a set of fixtures with a continuous waste, or a floor drain and its trap primer.

  • Grease interceptors are required for commercial kitchens; sizing is by fixture units or by the formula: capacity = gallons per minute of flow times retention time.

  • An interceptor must be installed with a vent, cleanout, and accessible cover; the flow-through rate and grease retention capacity are listed on the interceptor.

  • Sand and oil interceptors are required for garages, service stations, and car washes; they must be cleaned and maintained by the owner.

  • A trap primer is required for floor drains that could lose their seal; a trap seal must be maintained to prevent sewer gas entry.

  • Special wastes such as chemicals, acids, and photographic wastes require neutralization or dilution before discharge, per local pretreatment rules.

  • A backwater valve is required on fixtures below the sewer grade where backflow could occur; it must be accessible for maintenance.

  • Trap arms must be level or have a grade, must not exceed the developed length allowed, and must be vented within the allowed distance.

Quick reference

Fuel Gas Piping and Appliance Connections

  • Fuel gas piping must be sized by the longest length method or the branch length method using the gas code tables; the sizing depends on gas type, pressure, and total load.

  • Natural gas is supplied at about 1,000 Btu per cubic foot; propane is about 2,500 Btu per cubic foot, so pipe sizes differ for the same appliance load.

  • A shutoff valve is required within 6 feet of each appliance and must be accessible; a union or flanged connection is required at the appliance.

  • A sediment trap (drip leg) is required at the appliance connection for gas-fired appliances to catch debris before it enters the controls.

  • Combustion air must be provided by the appliance manufacturer's instructions and the gas code; two permanent openings to an interior space are typical.

  • Gas piping must be tested at 1.5 times the working pressure, but not less than 3 psi for a 10-minute test on low-pressure systems (or as the code specifies).

  • Gas vents must terminate above the roof, with clearances to windows, doors, and air intakes; a vent must not terminate in a crawl space or attic.

  • Flexible appliance connectors must be listed, not concealed in walls, and not exceed 6 feet in length unless the manufacturer allows otherwise.

  • Gas piping cannot be installed in a concealed location without protection, and it must be supported at intervals specified by the code.

Quick reference

Health, Safety, Backflow Prevention, and Water Conditioning

  • Backflow is the reversal of flow in a water system; it can be caused by backpressure or backsiphonage.

  • An air gap is the only absolute backflow protection; an RPZ (reduced pressure zone) assembly is required for high-hazard connections.

  • A double check valve assembly is used for low-hazard connections; a pressure vacuum breaker is used for irrigation systems.

  • Backflow assemblies must be tested annually by a certified tester; test reports are submitted to the water authority.

  • Water conditioning includes softening, filtration, and disinfection; softeners use ion exchange and must be installed with a bypass and drain to an approved location.

  • Cross-connections must be eliminated or protected; a hose bib is a common cross-connection and requires a vacuum breaker.

  • Potable water systems must be protected from contamination by chemicals, sewage, and process water; separation distances between water and sewer lines must be maintained.

  • Lead and copper concerns require corrosion control; water treatment must not create a health hazard or exceed contaminant levels.

  • A backflow prevention device must be accessible for testing and maintenance and installed in the orientation required by the manufacturer.

Quick reference

Plan Reading, Isometric Drawings, and Material Calculations

  • A floor plan shows fixture locations and pipe routing in plan view; a riser diagram shows vertical relationships and stack connections.

  • An isometric drawing shows three dimensions (width, height, depth) on a 30-degree angle grid; pipe lengths must be calculated from the true lengths of runs.

  • Developed length is the total length of pipe plus fittings measured along the centerline; fitting allowances are added for each 90-degree or 45-degree turn.

  • A 45-degree offset length equals the offset times 1.414; a 22-1/2 degree offset uses a multiplier of 2.613.

  • Fixture-unit calculations sum each fixture's f.u. value; convert to gpm using the demand curve for sizing water supply.

  • Material takeoff: count fittings, pipe lengths, and valves from the isometric, then add a waste factor (typically 5 to 10 percent).

  • Pipe grade is expressed as inches per foot; total fall equals slope times run length (e.g., 1/4 inch per foot over 20 feet equals 5 inches).

  • A plumbing plan must show the building drain, building sewer, vents, water service, and fixture locations; dimensions and elevations are taken from the plan.

  • Scale is read from the drawing title block; measure with a scale and convert to actual dimensions before ordering material.