Sensible heat formula
Qs = 1.08 × CFM × ΔT. It calculates the sensible heat load in BTU/h for standard air, where 1.08 combines air density and specific heat at sea level.
Latent heat formula
QL = 0.68 × CFM × ΔW, where ΔW is the moisture difference in grains per pound. It estimates the BTU/h needed to remove or add moisture from the air.
One ton of refrigeration
Equal to 12,000 BTU/h, 200 BTU/min, or 3.517 kW. It represents the heat absorption rate of melting one ton of ice in 24 hours.
Superheat definition
The difference between the actual suction line temperature and the saturation temperature at the suction pressure. It confirms the refrigerant is fully vapor before the compressor.
Subcooling definition
The difference between the saturation temperature at the liquid line pressure and the actual liquid line temperature. It confirms the refrigerant is fully liquid before the metering device.
Pressure unit conversion
1 psi equals 2.31 feet of water column or 27.7 inches of water column. 1 inch of water column is about 0.036 psi or 249 pascals.
Sensible heat factor
SHF equals sensible load divided by total load. A value near 1.0 means the space load is mostly sensible with little latent moisture removal.
Refrigeration cycle order
Compressor, condenser, metering device, evaporator, then back to the compressor. Heat is rejected in the condenser and absorbed in the evaporator.
TXV function
The thermostatic expansion valve meters refrigerant into the evaporator and controls superheat, typically holding 8 to 12 degrees Fahrenheit at the evaporator outlet.
Low superheat diagnosis
Low superheat with a cold, sweating suction line suggests overcharge or a stuck-open TXV. Liquid refrigerant may reach the compressor and cause damage.
High discharge pressure causes
Dirty condenser, non-condensable air, overcharge, low condenser airflow, or high ambient temperature. Each raises condensing pressure and compressor load.
Filter-drier purpose
Liquid line filter-driers remove moisture and acid from the refrigerant. Suction line filter-driers are temporary and removed after a burnout cleanup.
Evacuation standard
Evacuate to 500 microns and perform a standing vacuum test. This confirms moisture and non-condensables are removed before charging the system.
Scroll compressor caution
Scroll compressors are unidirectional. Running one backward from reversed three-phase power damages the scroll set, so verify phase rotation before startup.
Ohm's law and power
E = I × R and P = E × I. For single-phase AC, include power factor: P = E × I × PF when the load is not purely resistive.
Run capacitor test
A good run capacitor reads within its rated microfarad tolerance. A bulging, leaking, or open capacitor prevents compressor or fan motor start.
Thermostat wiring letters
R is 24V power, W is heat, Y is cooling compressor, G is indoor fan, O/B is reversing valve, and C is common. These follow standard color conventions.
LRA versus RLA
LRA is locked rotor amps, the inrush current at startup. RLA is running load amps, the normal operating current. Drawing near LRA while running indicates a fault.
Blown low-voltage fuse
A blown 24V control fuse usually means a shorted control wire or failed component. Locate the short before replacing the fuse to avoid repeat failure.
Contactor coil versus contacts
The coil is in the low-voltage control circuit and the contacts switch the high-voltage load. Pitted contacts cause voltage drop and compressor overheating.
Equal friction duct method
Duct sizing that holds a constant pressure drop per 100 feet, typically 0.1 inch water column. It simplifies design for supply and return trunk lines.
CFM from velocity
CFM equals velocity in feet per minute times free area in square feet. A duct traverse with a pitot tube or anemometer gives average velocity.
High static pressure meaning
Static pressure above about 0.5 inch water column at the blower outlet suggests restricted ductwork, a dirty filter, or an undersized return.
MERV filter ratings
MERV 8 to 13 filters capture particulate matter for general IAQ. Higher MERV means finer capture but more airflow resistance and fan energy.
Coil icing cause
A dirty evaporator coil or filter reduces airflow, lowers suction pressure, and can cause coil icing. Restored airflow usually clears the ice.
Furnace ignition sequence
Inducer starts, pressure switch proves draft, igniter heats, gas valve opens, flame sensor proves flame, then the blower starts after a delay.
AFUE meaning
Annual fuel utilization efficiency rates furnace efficiency. Units at 90 percent or higher condense flue gas and require a condensate drain.
Heat pump balance point
The outdoor temperature where heat pump capacity equals building load. Below it, auxiliary or emergency heat supplements the heat pump.
Defrost cycle purpose
The heat pump reverses refrigerant flow to melt frost on the outdoor coil. Auxiliary heat runs during defrost to temper the supply air.
Furnace temperature rise
The difference between supply and return air temperatures across the furnace, typically 35 to 65 degrees Fahrenheit. It confirms proper airflow and firing rate.
Combustion CO safety
A flue gas CO reading above 100 ppm or any measurable ambient CO indicates a problem. Cracks in the heat exchanger can leak CO into the space.
SEER2 and HSPF2
Efficiency ratings for cooling and heating. Higher values mean lower operating cost, and SEER2 and HSPF2 replace the older SEER and HSPF metrics.