NSSCO Building Studies 6186 · Put your knowledge to work in context.

All case studies

Cracked Boundary Wall on Expansive Clay

A 230 mm concrete block boundary wall 3.0 m high and 9.0 m long is built on a plot in Rundu. The wall has no piers and no movement joints. Its strip footing is 600 mm wide and 200 mm thick with two Y10 bars, founded at 0.6 m depth on dark cracking clay. Blocks are laid in stretcher bond with 1:6 cement-sand mortar. The blocks were delivered dry and laid without wetting. The plot slopes gently and surface water drains toward the wall. Three weeks after construction, a vertical crack about 4 mm wide appears 3.5 m from one end, and the top two courses bow inward. The client wants the wall rendered immediately to hide the crack before a family event. The rainy season is two weeks away.

1. Identify the likely causes of the crack and bowing, explaining how each cause fits the evidence.

Read the worked answer

The crack and bowing point to movement rather than simple shrinkage. A 9 m wall with no movement joints is long enough for thermal and moisture movement to open a vertical crack; the crack at 3.5 m is roughly where a joint should have been. The footing is only 600 mm wide and 200 mm thick with two Y10 bars, founded at 0.6 m on dark cracking clay. Expansive clay can heave in the wet season and shrink in the dry season, producing differential movement and lifting the wall. The absence of piers leaves a 3.0 m high wall laterally weak, which fits the inward bowing of the top courses. Dry blocks laid without wetting can absorb water from the mortar, causing poor bond and shrinkage cracking. The 1:6 mortar is not inherently wrong, but it cannot compensate for movement. Rendering now would hide the symptom, not the cause.

2. Evaluate the client's proposal to render the wall immediately. What would you recommend instead?

Read the worked answer

I would advise the client not to render yet. Rendering over a live crack will crack again, often within weeks, and it traps moisture. The first step is to monitor the crack with tell-tales or a glass strip for at least a month, and to record widths at top, middle and bottom. I would also check ground levels and drainage, and inspect the footing by a trial pit. If the cause is clay heave, the footing may need to be deepened or widened, or the wall rebuilt with a movement joint. If the cause is thermal movement, joints and piers are needed. Only after the movement has been stabilized should the wall be repaired, and the render should include reinforcement or a control joint over the repair. The client's event is understandable, but a cosmetic fix would be poor value and could damage my reputation. I would explain the risk in writing.

3. Specify a repair and improvement scheme for the wall, including sequence and key dimensions where reasonable.

Read the worked answer

Repair sequence: prop the bowing section, remove the top two courses and the cracked panel, and cut a full-height movement joint at the crack. Add at least two movement joints so no panel exceeds about 4.5–6.0 m, and build 300 × 300 mm piers at the ends and at mid-length. Widen the strip footing to about 700–800 mm and deepen it to at least 0.8–1.0 m into firm ground, with two Y12 bars and links; alternatively use a reinforced trench-fill footing. Damp-proof the top of the footing. Rebuild with dampened blocks, a 1:5 or 1:6 mortar, and reinforcement in the bed joints if specified. Finish with a flexible sealant in the movement joints, not mortar. Render only after monitoring shows no further movement, using a mesh-reinforced mix. The sequence matters because rebuilding before stabilizing the foundation would repeat the failure.