Responding to Plan Review Comments on a Value-Engineered Design

NABCEP PVDS · Put your knowledge to work in context.

All case studies

Responding to Plan Review Comments on a Value-Engineered Design

An 11.4 kW residential rooftop system returns from plan review with three comments. The design is 36 × 400 W modules (Voc 45.2 V) in four strings of nine, feeding an 11.4 kW string inverter rated 47.5 A at 240 V. The single line shows 8 AWG copper in 3/4 in. EMT from the inverter to a 60 A two-pole backfed breaker at the bottom of a 200 A panel with a 200 A busbar and a 200 A main breaker at the top. No rapid shutdown equipment appears on the drawings; there is a lockable DC disconnect at the inverter, 35 ft from the array, with DC conductors run in EMT through the attic. Attachment spacing is 48 in. with no engineer's letter, and the builder's truss drawing shows top chords at 24 in. on center. The permit was originally submitted as a 7.6 kW system, and the utility interconnection application still lists 7.6 kW. The contractor swapped to the larger inverter after the application was filed and told the crew the plans would be updated at closeout.

1. Identify which of the three comments reflect actual code violations and specify the corrections for the AC conductor, the overcurrent protection, and the interconnection method.

Read the worked answer

AC conductor and OCPD. 11,400 W ÷ 240 V = 47.5 A; × 1.25 continuous factor = 59.4 A → 60 A OCPD is correct. But the conductor must have at least 60 A of ampacity, and 8 AWG copper is 50 A at 75 °C. 8 AWG is a violation on two counts: it is undersized for the load and it cannot be protected by a 60 A breaker. Correction: 6 AWG copper (65 A at 75 °C), then verify the ambient and rooftop temperature correction and conduit fill still leave ≥ 60 A. If correction pulls 6 AWG below 60 A, go to 4 AWG.

Busbar. 200 A main + 60 A backfeed = 260 A against a 240 A limit (120% of 200 A). Violation. Options: downsize the main to 175 A (240 − 175 = 65 A allowance, which covers the 60 A breaker), or convert to a supply-side connection. For a 200 A service, downsizing the main risks nuisance trips on the existing load calculation, so run that calc before choosing.

Interconnection method. The backfed breaker must stay at the end of the bus opposite the main, and the panel must be listed and labeled for backfeed. Any change to the main breaker size requires new service-equipment labeling.

Structural. 48 in. attachment spacing on 24 in. trusses needs the engineer's letter the AHJ asked for - that comment is a documentation gap, not a field defect, but it stops the permit.

2. Address the rapid shutdown comment: what is required, and what labels must be added to the drawing set?

Read the worked answer

Under 690.12, PV system circuits on or in a building must be controlled by a rapid shutdown system. Conductors within the array boundary (1 ft of the array in all directions) are permitted to remain energized; conductors outside that boundary must be reduced to 30 V and 240 VA within 30 seconds of initiation. The 35 ft of DC conductors in EMT through the attic is exactly the condition the rule targets.

A lockable DC disconnect at the inverter is not a rapid shutdown system unless it is the initiating device and listed equipment performs the shutdown. The design needs one of: module-level electronics with a listed initiator, a listed combiner/transmitter arrangement at the array, or another listed RSD solution.

Labels and drawings:

  • The initiating device must be at a readily accessible location - normally adjacent to the service equipment - and labeled as the rapid shutdown initiator.
  • A permanent placard at the service equipment showing the rapid shutdown system and its initiation point (690.56(C) in the editions most AHJs enforce).
  • The DC disconnect labeled with maximum system voltage and maximum current per 690.53, plus the standard dual-power-source warning at the service.
  • The single line must show the RSD equipment, the initiator location, and the array boundary dimension.

One practical note: module-level electronics do not fix the string's cold-temperature Voc, so the DC design still needs the 600 V check on four strings of nine.

3. The contractor wants to note all three changes on the as-built and skip a resubmittal. Explain the correct process and the risks of that shortcut.

Read the worked answer

The changes are not field adjustments; they alter the approved permit documents in ways the plan reviewer specifically flagged. The correct sequence:

  1. Revise the drawings with a revision cloud, delta number, date, and a revision block entry, and update the load calculation, single line, and label schedule together so they stay consistent.
  2. Re-run the busbar and conductor calculations against the final inverter rather than the value-engineered one.
  3. Resubmit to the AHJ as a revision and obtain approval before the rough-in inspection, not at final.
  4. Re-file the utility interconnection application with the correct 11.4 kW nameplate, updated AC output current, and a new single line. Utilities often process this as a new or amended application, which can reset the queue position.
  5. Confirm the structural letter covers the drawn attachment spacing.

Risks of the shortcut: the inspector compares the roof and panel to the approved set, so mismatches now become correction notices and re-inspection fees; the utility may refuse to energize based on a nameplate that does not match the interconnection agreement; the interconnection approval may be void; and the as-built record misstates the service capacity for the next owner or electrician. The 7.6 kW filing also understates AC output current, which can invalidate the utility's protection settings - a safety issue, not paperwork.