NABCEP SH Associate: Balance of System Components and Materials

NABCEP SH Associate · Work through your exam, one topic at a time.

All guide sections

Balance of System Components and Materials

The hydronic balance of system

An array is only as good as the parts around it. Typical components and their jobs:

  • Expansion tank - absorbs volume change; size it for stagnation, not just normal operation.
  • Pressure relief valve - the only safe over-pressure path; never valve it off.
  • Air elimination or air vent - air pockets stop circulation and corrode loops.
  • Check valve - prevents night-time reverse thermosiphon that cools the tank.
  • Isolation and drain valves - service without draining everything.
  • Strainer and flow meter - protect the pump and let you balance flow.
  • Circulator and differential controller with collector and tank sensors - pump on at the set ΔT, off when gain disappears.
  • Heat exchanger - separates glycol from potable water.
  • Tempering/mixing valve - limits delivery temperature at fixtures.
  • Vacuum breaker and drainback tank where the design requires them.

Sizing rules of thumb

Storage of roughly 1.5–2 gallons per square foot of collector for DHW; glycol expands a few percent between cold fill and operating temperature; cold loop pressure is commonly set between 20 and 40 psi per manufacturer instruction.

Worked example

A 40-gallon glycol loop expands about 4 % to operating temperature - roughly 1.6 gallons - but full stagnation vaporizes far more. If the expansion tank's acceptance volume is only 1 gallon, the relief valve will lift every sunny summer afternoon. Resize for stagnation volume, not normal operation.

Traps

Omitting the check valve and wondering why the tank cools at night; placing the tempering valve on the solar loop instead of the potable outlet; wiring a pump with no disconnect; using automotive hose or non-rated insulation that fails at stagnation temperature.