NASCLA Journeyman Electrician study materials
NASCLA Journeyman Electrician study resources

NASCLA Journeyman Electrician cheat sheet

NASCLA Journeyman Electrician · Keep the key ideas within reach.

Quick reference

Electrical Principles, Theory and Code Fundamentals

  • Ohm's law: E = I × R; power P = E × I = I²R = E²/R for resistive circuits.

  • Series circuit: same current, voltages add, R_T = R1 + R2 + ...; parallel circuit: same voltage, currents add, 1/R_T = Σ(1/R).

  • Balanced three-phase power: P = √3 × V_L × I_L × power factor.

  • Voltage drop: single-phase 2KID/CM; three-phase √3KID/CM, where K is the conductor constant.

  • Continuous load: expected to operate 3 hours or more; branch-circuit OCPD and conductors are sized at 125% of continuous current plus noncontinuous load.

  • NEC Article 100 contains definitions; Article 110 contains general requirements; Article 90 covers scope and enforcement.

  • Ampacity adjustment: apply ambient-temperature correction and conductor-count adjustment from NEC 310.15; use the lower adjusted ampacity.

  • RMS sine wave: V_RMS = 0.707 × V_peak; V_peak = 1.414 × V_RMS.

Quick reference

Services, Feeders and Branch Circuits

  • Service disconnecting means must be grouped, marked, and have no more than six switches or breakers to disconnect all service conductors.

  • Service-entrance conductors are sized per Article 230 and the ampacity tables; the service load is calculated per Article 220.

  • Dwelling receptacle spacing: wall space must be arranged so no point is more than 6 ft from a receptacle; receptacles are generally no more than 12 ft apart.

  • Dwelling small-appliance branch circuits: at least two 20A circuits for kitchen countertop; laundry and bathroom require dedicated 20A circuits.

  • GFCI protection is required in dwelling bathrooms, garages, outdoors, kitchens, laundry, crawl spaces, and unfinished basements per 210.8.

  • Branch-circuit OCPD for continuous loads: 125% continuous plus 100% noncontinuous load, then select a standard rating.

  • Feeder and branch-circuit conductors must have ampacity at least equal to the load; the OCPD protects conductors per 240.4.

Quick reference

Conductors, Raceways and Wiring Methods

  • Raceway fill: 53% for one conductor, 31% for two, 40% for three or more; a nipple may be filled to 60% of cross-sectional area.

  • EMT must be secured within 3 ft of boxes and supported at intervals not exceeding 10 ft.

  • Paralleled conductors: minimum 1/0 AWG, same material, size, insulation, length, and terminations.

  • NM cable is prohibited in wet locations and where subject to physical damage; use raceway or approved cable where required.

  • Equipment grounding conductor is sized from Table 250.122 based on the rating of the overcurrent device.

  • Conductors in wet locations require moisture-resistant insulation and approved fittings; splices in wet locations require listed connectors.

  • Conductor ampacity comes from Table 310.16; derate for ambient temperature and number of current-carrying conductors.

  • Copper branch-circuit conductors: 14 AWG for 15A, 12 AWG for 20A, and 10 AWG for 30A are common minimum sizes per Table 310.16.

Quick reference

Boxes, Fittings, Switches and Receptacles

  • Box fill volume: 14 AWG = 2.00 in³, 12 AWG = 2.25 in³, 10 AWG = 2.50 in³ per conductor; add clamps, devices, and EGC as specified.

  • All equipment grounding conductors in a box count as one conductor for box fill.

  • Each yoke or device counts as two conductors of the largest conductor connected to it for box fill.

  • Boxes must be accessible without removing building finish; boxes may not be buried.

  • Receptacles in wet or damp locations require weather-resistant types and GFCI protection where required.

  • A 15A receptacle is permitted on a 20A circuit only where the circuit supplies two or more receptacles per 210.21(B)(3).

  • Switches and receptacles must be installed in boxes; faceplates are required, and device grounding terminals are bonded to the EGC.

  • Cable clamps count as one conductor for box fill.

Quick reference

Grounding, Bonding and Overcurrent Protection

  • Grounding electrode system: rod, pipe, plate, concrete-encased electrode, or ground ring; if one rod has more than 25 ohms, add a second electrode per 250.53.

  • GEC is sized per Table 250.66; EGC is sized per Table 250.122; the main bonding jumper bonds the grounded service conductor to the EGC bus.

  • Separately derived system: bond X0 to the transformer enclosure and grounding electrode; install the system bonding jumper.

  • NEC 240.4(B) permits the next higher standard OCPD for certain circuits ≤800A when conductor ampacity does not match a standard rating and the load is not a multioutlet receptacle circuit.

  • GFCI protects people from ground-fault current; AFCI detects arcing faults; neither replaces overcurrent protection.

  • Bonding connects metal parts to ensure a fault-current path; grounding connects the electrical system to earth.

  • An overcurrent device interrupts overloads and short circuits and must be rated for voltage and available fault current.

  • The grounding electrode conductor must be continuous and installed without splices except as permitted by Article 250.

Quick reference

Motors, Motor Controls and HVAC Equipment

  • Motor branch-circuit conductors: at least 125% of motor full-load current from Tables 430.248–430.250 for continuous-duty motors.

  • Motor overload protection: typically 115% to 125% of nameplate FLA, depending on service factor and temperature rise.

  • Short-circuit and ground-fault protection for motors is sized per Table 430.52; it may be increased if starting current trips the device.

  • Motor disconnecting means must be within sight of the motor and controller, readily accessible, and lockable where required.

  • Motor controller must have a horsepower rating not less than the motor horsepower.

  • HVAC hermetic compressor branch circuits use nameplate rated-load amps and Article 440 rules.

  • Thermal overload relays protect motor windings from sustained overload; they do not protect the branch circuit from short circuits.

  • Motor full-load current for conductor sizing comes from NEC tables, not the motor nameplate current.

Quick reference

Transformers and Power Distribution Equipment

  • Single-phase transformer kVA = V × I / 1000; three-phase kVA = √3 × V_L × I_L / 1000.

  • Transformer overcurrent protection is per Table 450.3(B); primary and secondary OCPD ratings depend on transformer voltage and current.

  • Separately derived transformer: bond secondary X0 to the enclosure, install the system bonding jumper, and connect to the grounding electrode.

  • Transformer secondary conductors are protected by OCPD; tap rules in 240.21(C) allow limited lengths without secondary OCPD.

  • Dry-type transformers require listed clearances and ventilation; access and working space follow Article 110.

  • Transformer nameplate primary and secondary currents are used to size conductors and overcurrent protection; conductors must have ampacity at least equal to the load.

  • A delta-wye transformer provides a grounded neutral on the secondary; a delta-delta transformer may be ungrounded.

  • Available fault current at a transformer secondary depends on kVA and impedance; equipment must have adequate SCCR.

Quick reference

Special Occupancies, Special Locations and Special Equipment

  • Hazardous location classes: Class I flammable gases or vapors; Class II combustible dust; Class III ignitable fibers or flyings.

  • Division 1 means the hazard is present under normal conditions; Division 2 means the hazard is present only under abnormal conditions.

  • Hazardous-location equipment must be marked with class, division, and group; use listed fittings and seals as required.

  • Dwelling bathroom receptacles require GFCI protection; at least one receptacle must be within 3 ft of each basin.

  • Swimming pool areas require equipotential bonding of metal parts and specified clearances for receptacles; GFCI protection is required.

  • Wet locations require weather-resistant receptacles and enclosures; all openings must be closed.

  • Special equipment such as signs, welders, and elevators has additional requirements in Articles 600, 630, and 620.

  • Temporary wiring on construction sites is subject to Article 590 and GFCI requirements.

Quick reference

Jobsite Safety, Tools and OSHA Requirements

  • Lockout/tagout: isolate all energy sources, apply locks and tags, release stored energy, and verify zero energy before work.

  • OSHA 29 CFR 1926 Subpart K covers construction electrical safety; GFCI protection is required for 15A and 20A, 120V receptacles on construction sites.

  • Arc-flash PPE and approach boundaries are based on incident energy and voltage; only qualified persons may enter the restricted approach boundary.

  • Test before touch: verify the circuit is de-energized with a meter rated for the category and voltage.

  • Extension cords must be three-wire with grounding, not daisy-chained, and free of damage; use GFCI where required.

  • Ladders: extend 3 ft above the landing, set at a 4:1 slope, and maintain three-point contact.

  • Voltage-rated gloves require inspection and testing per class; leather protectors are used over rubber gloves.

Quick reference

Code Calculations and Reading Electrical Plans

  • Dwelling general lighting load: 3 VA per square foot; small-appliance circuits add 1500 VA each; laundry adds 1500 VA.

  • Dwelling demand factor: first 3000 VA at 100%; remaining general lighting and appliance load at 35% per 220.42.

  • Service load calculation sums general lighting, small-appliance, laundry, appliance, HVAC, and motor loads, then applies demand factors.

  • Voltage drop formula: single-phase 2KID/CM; three-phase √3KID/CM, where K is the resistivity constant.

  • Plan scale: 1/4 inch = 1 foot means 1/4 inch on the drawing represents 12 inches actual.

  • Panel schedule shows circuit numbers, breaker ratings, loads, and phase balance; verify neutral and grounding bars.

  • Box fill calculation: count conductors and fittings, multiply by Table 314.16(B) volume, and compare with box volume.

  • Feeder and service conductor size is selected from ampacity tables after load calculation and adjustment factors.