NASCLA Journeyman Electrician flashcards
NASCLA Journeyman Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- For a resistive circuit, voltage equals current times resistance; power equals voltage times current and also equals current squared times resistance.
- Balanced three-phase power
- For a balanced three-phase load, real power equals the square root of three times line voltage times line current times power factor.
- Continuous load definition
- A continuous load is one expected to operate at maximum current for three hours or more; its branch-circuit conductors and overcurrent device are sized at 125 percent.
- RMS sine voltage
- For a sine wave, root-mean-square voltage equals 0.707 times peak voltage; peak voltage equals 1.414 times RMS voltage.
- Service disconnect six throws
- Service disconnecting means must be grouped and marked, and no more than six switches or breakers may be used to disconnect all service conductors.
- Dwelling receptacle spacing
- In dwelling units, wall space must be arranged so no point is more than six feet from a receptacle; receptacles are generally spaced no more than twelve feet apart.
- GFCI dwelling locations
- GFCI protection is required for dwelling bathroom, garage, outdoor, kitchen, laundry, crawl-space, and unfinished-basement receptacles under NEC 210.8.
- Raceway fill percentages
- A raceway may be filled to 53 percent for one conductor, 31 percent for two, and 40 percent for three or more conductors; a nipple may be filled to 60 percent.
- Paralleled conductor requirements
- Paralleled conductors must be at least 1/0 AWG and have the same material, size, insulation, length, and termination arrangement to share current equally.
- EMT support intervals
- Electrical metallic tubing must be secured within three feet of boxes and supported at intervals not exceeding ten feet.
- Box fill conductor volumes
- For box fill, each 14 AWG conductor counts 2.00 cubic inches, each 12 AWG counts 2.25, and each 10 AWG counts 2.50; fittings and devices add volume.
- Equipment grounding box count
- All equipment grounding conductors entering a box are counted as one conductor when calculating box fill volume.
- Device yoke box fill
- Each yoke or device with a strap counts as two conductors of the largest conductor connected to it for box fill calculations.
- Grounding electrode 25 ohms
- A single grounding electrode such as a rod must have resistance of 25 ohms or less; if not, a second electrode must be added.
- GEC versus EGC
- The grounding electrode conductor connects the system to earth; the equipment grounding conductor provides a fault-current path between equipment and the grounding system.
- Separately derived system bonding
- At a separately derived transformer, bond the secondary neutral X0 to the enclosure and grounding electrode and install the system bonding jumper.
- GFCI versus AFCI
- GFCI devices protect people from ground-fault current; AFCI devices detect dangerous arcing faults in branch-circuit wiring.
- Motor conductor 125 percent
- Motor branch-circuit conductors for continuous-duty motors must have ampacity at least 125 percent of the motor full-load current from NEC tables.
- Motor overload protection range
- Motor overload protection is typically set at 115 to 125 percent of nameplate full-load amps, depending on service factor and temperature rise.
- Motor disconnect location
- A motor disconnecting means must be within sight of the motor and controller, readily accessible, and lockable where required by the installation.
- Transformer kVA formula
- Single-phase transformer capacity in kVA equals voltage times current divided by 1000; three-phase capacity uses the square root of three times line voltage times line current divided by 1000.
- Transformer secondary tap rule
- NEC 240.21(C) permits limited lengths of transformer secondary conductors without overcurrent protection at the transformer, subject to length and ampacity rules.
- Delta-wye secondary neutral
- A delta-wye transformer provides a grounded neutral on its secondary, allowing line-to-neutral loads and a separately derived grounding connection.
- Hazardous location classes
- Class I locations contain flammable gases or vapors; Class II contains combustible dust; Class III contains ignitable fibers or flyings.
- Division 1 versus 2
- Division 1 means the hazardous condition is present under normal operation; Division 2 means it is present only under abnormal conditions.
- Bathroom receptacle GFCI
- Dwelling bathroom receptacles require GFCI protection, and at least one receptacle must be located within three feet of the basin.
- Lockout tagout steps
- Lockout/tagout requires isolating all energy sources, applying locks and tags, releasing stored energy, and verifying zero energy before work begins.
- OSHA construction GFCI
- OSHA construction standards require GFCI protection for 15- and 20-ampere, 120-volt receptacle outlets on construction sites.
- Test before touch
- Before contacting conductors, verify the circuit is de-energized using a meter rated for the voltage and installation category.
- Dwelling lighting load
- Dwelling general lighting load is calculated at three volt-amperes per square foot; small-appliance and laundry circuits each add 1500 volt-amperes.
- Dwelling demand factor
- For dwelling general lighting and appliance loads, the first 3000 volt-amperes is at 100 percent and the remainder at 35 percent.
- Plan scale reading
- A plan scale of one-quarter inch equals one foot means one-quarter inch on the drawing represents twelve inches in the actual building.