NASCLA Journeyman Electrician: Code Calculations and Reading Electrical Plans

NASCLA Journeyman Electrician · Work through your exam, one topic at a time.

All guide sections

Code Calculations and Reading Electrical Plans

What the exam targets

Article 220 calculations, conductor and OCPD selection from tables, box and conduit fill, voltage drop, and the ability to read a plan set: legend, one-line diagram, panel schedule, and load calculations.

Concepts to own

  • Standard method for a dwelling: general lighting at 3 VA/ft²; demand factors in Table 220.42 (first 3000 VA at 100%, remainder at 35%); 1500 VA per small-appliance circuit and 1500 VA for laundry; appliances at 75% (220.53); ranges per Table 220.55; optional method in 220.82.
  • Commercial: lighting VA/ft² by occupancy (Table 220.12), receptacles at 180 VA each, continuous versus noncontinuous loading.
  • Conductor and OCPD selection from Table 310.16 and 240.6; voltage drop = 2 × K × I × L ÷ circular mils (K = 12.9 copper, 21.2 aluminum).
  • Plan reading: match the symbol legend to the panel schedule; the one-line diagram gives service size, main device, and feeder sizes; check the revision block and the "issued for construction" stamp before pricing.
  • Never scale from a photocopy; use the stated scale and a scale rule on the original or digital file.

Traps

Using only the lighting load and forgetting small-appliance and laundry circuits; applying demand factors line by line instead of to the combined total; using 180 VA per receptacle in a dwelling; reading a dimension that is a "nominal" or existing condition rather than new work.

Worked example

A 2,000 ft² dwelling: lighting 2,000 × 3 = 6,000 VA; two small-appliance circuits = 3,000 VA; laundry = 1,500 VA. Total 10,500 VA. Demand: first 3,000 at 100% = 3,000; remaining 7,500 at 35% = 2,625; total 5,625 VA. Add fixed appliances under 220.53 before converting to amps at 240 V.