NASCLA Journeyman Electrician: Transformers and Power Distribution Equipment

NASCLA Journeyman Electrician · Work through your exam, one topic at a time.

All guide sections

Transformers and Power Distribution Equipment

What the exam targets

Article 450 transformer protection, 250.30 separately derived systems, 240.21(C) secondary conductor rules, plus transformer math and working clearances.

Concepts to own

  • Full-load current: single phase I = kVA × 1000 ÷ E; three phase I = kVA × 1000 ÷ (1.732 × E).
  • 450.3(B): with primary-only protection, the primary device may be up to 125% of rated primary current (167% where primary current is under 9 A). With both primary and secondary protection, 125% primary and 125% secondary.
  • Secondary conductors must be protected by a secondary overcurrent device, a 240.21(C) tap rule (10 ft or 25 ft), or approved transformer thermal protection.
  • Separately derived systems (250.30): system bonding jumper at the transformer, grounding electrode conductor to the building electrode system, equipment grounding conductor run with the secondary conductors.
  • Working space (110.26) and ventilation (450.9) apply to transformer installations.

Traps

Sizing the primary device at 100% instead of 125%; forgetting the 167% allowance for small primary currents; treating a transformer secondary as a service and bonding neutral to ground at the first panel in addition to the transformer; ignoring that the secondary of a 480-to-208Y/120 transformer is a separately derived system.

Worked example