NATE AC Service flashcards
NATE AC Service · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Superheat
- Suction line temperature minus evaporator saturation temperature. It verifies the evaporator is fully fed with liquid refrigerant and is the primary charging method for fixed-orifice systems.
- Subcooling
- Condensing saturation temperature minus liquid line temperature. It confirms the condenser has enough liquid seal and is the primary charging method for TXV systems.
- Target superheat
- The superheat value a fixed-orifice system needs at the current indoor wet-bulb and outdoor dry-bulb conditions, read from the manufacturer's charging chart rather than a fixed number.
- Evaporator saturation temperature
- The boiling temperature of refrigerant inside the evaporator, found by reading suction pressure on the refrigerant's pressure-temperature chart. It is the baseline for superheat calculation.
- Condensing saturation temperature
- The temperature at which refrigerant condenses in the condenser, found from the high-side pressure on the pressure-temperature chart. The baseline for subcooling calculation.
- 400 CFM per ton
- The standard design airflow for residential comfort cooling. One nominal ton equals 12,000 Btu/h, so a 2-ton system is designed for about 800 CFM of supply air.
- External static pressure
- The resistance to airflow measured in inches of water column across the blower assembly, combining supply and return duct, coil, and filter pressure drops. High readings indicate restriction.
- Evaporator delta-T
- The dry-bulb temperature difference between return air entering and supply air leaving the evaporator coil. Normal is roughly 16-22°F when charge and airflow are correct.
- Wet-bulb temperature
- The temperature of air measured with a wetted thermometer, reflecting moisture content and evaporative potential. Indoor wet-bulb is required input for target superheat charts.
- Dry-bulb temperature
- The ordinary air temperature measured by a standard thermometer, with no regard to humidity. Used for return and supply temperature split and condenser entering air checks.
- Low charge symptoms
- High superheat, low subcooling, low suction pressure, low head pressure, and reduced amp draw. A fixed-orifice system also shows a starved, partially frosted evaporator.
- Overcharge symptoms
- High subcooling, low superheat, elevated head pressure, and high compressor amp draw. Liquid may flood back to the compressor, causing frost on the suction line at the service valve.
- Restricted liquid line
- A blockage or kinked line between condenser and metering device. It produces high subcooling at the condenser outlet, low suction pressure, and a temperature drop across the restriction.
- Restricted suction line
- A blockage or kink between evaporator and compressor. It causes low suction pressure at the compressor, high superheat at the compressor, and a frosted line at the restriction point.
- TXV operation
- A thermostatic expansion valve modulates refrigerant flow to hold a set superheat at the evaporator outlet, responding to bulb pressure, evaporator pressure, and spring force.
- TXV hunting
- Repeated over-correction by the expansion valve, causing suction pressure and superheat to swing cyclically. Causes include oversized valves, poor bulb contact, or a weak bulb charge.
- Fixed orifice metering
- A piston with a drilled bore that meters refrigerant at a rate set by pressure difference. Charge must be set by superheat because the device cannot self-adjust.
- Dirty condenser coil
- Restricted heat rejection raises condensing temperature and head pressure, increases subcooling and compressor amps, and reduces system capacity. Cleaning the coil restores normal readings.
- Dirty evaporator coil
- Reduced heat absorption lowers suction pressure and evaporator temperature, raises superheat, and can frost or ice the coil. Airflow drops and delta-T may appear high.
- Low airflow effects
- Below-design CFM lowers suction pressure, raises superheat, and can ice the evaporator. Causes include restrictive filters, closed dampers, undersized ducts, and low blower speed.
- High airflow effects
- Above-design CFM raises evaporator temperature and suction pressure, lowers superheat, and reduces the temperature split. It also lessens latent removal and leaves the space humid.
- Compressor RLA
- Rated load amps stamped on the compressor nameplate. Measured running amps are compared to RLA to judge loading; readings near or above RLA suggest high head pressure or mechanical wear.
- Liquid line sight glass
- A viewing port in the liquid line. Bubbles indicate flash gas from a low charge or restriction, while a clear glass with proper subcooling indicates a solid liquid seal.
- Flash gas
- Refrigerant vaporizing before reaching the metering device because of insufficient subcooling. It reduces capacity and appears as bubbles in the sight glass.
- Non-condensables
- Air or nitrogen trapped in the system. They raise head pressure and condensing temperature beyond what outdoor ambient predicts and cause high subcooling with normal suction readings.
- Superheat charging method
- For fixed-orifice systems, adjust charge until measured superheat matches the target from the chart using indoor wet-bulb and outdoor dry-bulb. Verify airflow first.
- Subcooling charging method
- For TXV systems, adjust charge until liquid line subcooling matches the manufacturer's target, typically 8-12°F, after confirming the valve is operating and airflow is correct.
- Weigh-in charging
- Charging by weight using the nameplate factory charge plus adjustments for line-set length and added components. Required for systems with critically charged or unknown-charge conditions.
- Recovery machine operation
- Refrigerant is pulled from the system into a recovery cylinder, never vented. The cylinder must be rated for the refrigerant, not overfilled, and weighed during the process.
- Evacuation and micron gauge
- Pulling a vacuum with a pump to remove moisture and air, verified with a micron gauge isolated from the pump. A decay test confirms no leaks or trapped moisture remain.
- Leak detection methods
- Electronic leak detector, soap bubbles, UV dye, and pressure testing with nitrogen. Nitrogen is preferred for standing pressure tests because it adds no moisture or refrigerant.
- Temperature split measurement
- Return air dry-bulb minus supply air dry-bulb after 15 minutes of steady operation. It is a quick performance check, not a substitute for superheat or subcooling verification.