NATE AC Service study materials
NATE AC Service study resources

NATE AC Service key terms

NATE AC Service · Get comfortable with the vocabulary.

superheat

The number of degrees a refrigerant vapor is above its saturation temperature at a given pressure. Measured as suction line temperature minus the saturation temperature corresponding to suction pressure.

Related: subcooling, saturation temperature, TXV
subcooling

The number of degrees a liquid refrigerant is below its saturation temperature at a given pressure. Measured as saturation temperature at the liquid line pressure minus the liquid line temperature.

Related: superheat, saturation temperature, condenser
saturation temperature

The temperature at which a refrigerant changes phase at a given pressure. In a condenser it is the condensing temperature; in an evaporator it is the boiling temperature.

Related: superheat, subcooling, pressure-temperature chart
pressure-temperature chart

A reference table or graph listing the saturation pressure of a refrigerant at each temperature. Technicians use it to convert gauge readings into saturation temperatures for superheat and subcooling calculations.

Related: saturation temperature, superheat, subcooling
thermostatic expansion valve

A metering device that regulates refrigerant flow into the evaporator by maintaining a set superheat at the evaporator outlet, using a sensing bulb and modulating the valve opening.

Related: superheat, evaporator, metering device
metering device

The component that drops refrigerant pressure between the liquid line and the evaporator, controlling flow and creating the low-side pressure that drives boiling and heat absorption.

Related: thermostatic expansion valve, evaporator, liquid line
evaporator

The indoor coil where low-pressure liquid refrigerant boils and absorbs heat from the airstream, cooling and dehumidifying the air delivered to the conditioned space.

Related: superheat, condensate, airflow
condenser

The outdoor coil where high-pressure refrigerant vapor rejects heat to outdoor air and condenses into liquid, dropping from a hot gas to a subcooled liquid.

Related: subcooling, compressor, head pressure
compressor

The pump that raises refrigerant pressure and temperature, moving vapor from the low side to the high side of the system and driving the entire refrigeration cycle.

Related: condenser, suction line, discharge line
suction line

The insulated line carrying low-pressure refrigerant vapor from the evaporator back to the compressor inlet. Its temperature and pressure are used to measure superheat.

Related: superheat, compressor, liquid line
liquid line

The line carrying high-pressure liquid refrigerant from the condenser outlet to the metering device. Its temperature and pressure are used to measure subcooling.

Related: subcooling, condenser, metering device
discharge line

The line carrying hot, high-pressure refrigerant vapor from the compressor outlet to the condenser inlet. It is the hottest line in the system.

Related: compressor, condenser, head pressure
head pressure

The high-side pressure read at the compressor discharge or condenser. It reflects condensing conditions and rises with high outdoor temperature or restricted condenser airflow.

Related: condenser, subcooling, discharge line
suction pressure

The low-side pressure read at the compressor inlet. It corresponds to the evaporator boiling temperature and indicates load, airflow, and charge conditions.

Related: superheat, evaporator, manifold gauge set
manifold gauge set

A service tool with high-side and low-side gauges plus hoses used to read system pressures, evacuate the system, and add refrigerant during service.

Related: suction pressure, head pressure, vacuum pump
refrigerant charge

The amount of refrigerant contained in a sealed system. Correct charge is verified by superheat, subcooling, or weigh-in methods depending on the metering device type.

Related: superheat, subcooling, refrigerant recovery
refrigerant recovery

The process of removing refrigerant from a system and storing it in a recovery cylinder for reuse, recycling, or reclaim, as required by environmental regulations before opening the circuit.

Related: refrigerant charge, vacuum pump, EPA Section 608
EPA Section 608

The federal regulation governing handling, recovery, and disposal of ozone-depleting and substitute refrigerants. Certification is required to purchase refrigerant and service sealed systems.

Related: refrigerant recovery, refrigerant charge, leak detection
vacuum pump

A pump used to evacuate a refrigeration system, removing air and moisture so the circuit can be opened, repaired, and recharged without contaminants.

Related: micron gauge, refrigerant recovery, manifold gauge set
micron gauge

An electronic instrument that measures deep vacuum in microns of mercury. It verifies that a system has been evacuated to a level that removes moisture before charging.

Related: vacuum pump, refrigerant charge, leak detection
leak detection

The process of locating refrigerant leaks using electronic detectors, UV dye, soap bubbles, or pressure testing, so the system can be repaired before recharging.

Related: refrigerant recovery, EPA Section 608, micron gauge
airflow

The volume of air moved across the evaporator or condenser, usually stated in cubic feet per minute. Low airflow causes low superheat, icing, and high head pressure.

Related: evaporator, static pressure, blower
static pressure

The resistance to airflow in a duct system, measured in inches of water column. High static pressure reduces airflow and can indicate undersized ducts or a dirty filter.

Related: airflow, blower, filter
blower

The indoor fan that moves conditioned air through the duct system. Its speed settings and cleanliness directly affect airflow across the evaporator coil.

Related: airflow, static pressure, evaporator
filter

A device that traps dust and particles from return air before it reaches the evaporator. A loaded filter raises static pressure and reduces airflow.

Related: static pressure, airflow, evaporator
condensate

Water that condenses on the evaporator coil as air is cooled below its dew point. It must drain away through a trap and drain line to prevent water damage.

Related: evaporator, relative humidity, drain pan
drain pan

A pan under the evaporator coil that collects condensate and routes it to the drain line. A clogged pan or line can cause overflow and water damage.

Related: condensate, float switch, evaporator
float switch

A safety device installed in the drain pan or line that shuts off the unit when condensate rises to a set level, preventing overflow and water damage.

Related: drain pan, condensate, safety controls
relative humidity

The amount of moisture in air expressed as a percentage of the maximum it can hold at that temperature. Cooling coils reduce it by condensing water out of the airstream.

Related: condensate, evaporator, dew point
dew point

The temperature at which air becomes saturated and moisture begins to condense. An evaporator coil below dew point removes moisture from the airstream.

Related: relative humidity, condensate, evaporator
sensible heat

Heat that changes the temperature of air or a substance without changing its phase. It is measured by dry-bulb temperature change across a coil.

Related: latent heat, dry-bulb temperature, enthalpy
latent heat

Heat absorbed or released during a phase change without a temperature change, such as refrigerant boiling or water vapor condensing on a coil.

Related: sensible heat, condensate, enthalpy
dry-bulb temperature

The temperature of air measured by an ordinary thermometer, unaffected by moisture content. It is used with wet-bulb to find enthalpy and coil performance.

Related: wet-bulb temperature, sensible heat, enthalpy
wet-bulb temperature

The temperature of air measured with a wetted thermometer bulb, reflecting evaporative cooling and moisture content. It indicates how much latent heat the air carries.

Related: dry-bulb temperature, relative humidity, enthalpy
enthalpy

The total heat content of air, combining sensible and latent energy per pound of dry air. Psychrometric charts use it to calculate coil capacity and airflow.

Related: sensible heat, latent heat, psychrometric chart
psychrometric chart

A graph relating dry-bulb, wet-bulb, humidity ratio, and enthalpy of air. Technicians use it to analyze cooling, heating, and dehumidification performance.

Related: enthalpy, dry-bulb temperature, wet-bulb temperature
temperature split

The difference between return-air and supply-air temperatures across the evaporator. It is a quick check of cooling performance, typically 15 to 22 degrees Fahrenheit in normal conditions.

Related: airflow, evaporator, dry-bulb temperature
contactor

An electrically operated switch that closes to energize the compressor and condenser fan on a call for cooling. Pitted contacts cause intermittent operation.

Related: relay, capacitor, control board
capacitor

A component that stores electrical energy and helps start or run motors. A failed run capacitor causes the compressor or fan to hum and overheat without starting.

Related: contactor, blower, compressor
control board

The electronic circuit board that sequences the blower, compressor, and safety circuits in response to thermostat signals and sensor inputs.

Related: thermostat, contactor, safety controls
thermostat

The temperature-sensing control that calls for cooling or heating by closing low-voltage circuits to the equipment. It also sets fan mode and setpoint.

Related: control board, low-voltage circuit, contactor