NATE Air Distribution Service study materials
NATE Air Distribution Service study resources

NATE Air Distribution Service flashcards

NATE Air Distribution Service · Build recall with a focused review session.

31 cards. Read the term and the definition here. The deck at the top of this page is optional.

Diffuser
A supply air outlet that spreads and mixes conditioned air into the space, typically at the ceiling, using fixed or adjustable vanes to control throw and drop.
Return grille
A louvered opening that admits room air into the return duct system without a damper; it protects the duct and distributes return airflow across the face.
Volume damper
An adjustable blade inside a duct that throttles airflow to balance branches; opposed-blade types maintain straighter flow while single-blade types are cheaper.
Fire damper
A listed closure installed at rated wall or floor penetrations that closes on heat to preserve the fire-resistance rating of the assembly and limit smoke spread.
Turning vane
Curved blades inside a square elbow that guide airflow around the corner, reducing turbulence and pressure loss compared with an unvaned elbow.
Plenum
A box or duct section that distributes air to several outlets or collects return air; an extended plenum serves multiple branch takeoffs from one trunk.
Total external static pressure
The sum of supply and return static pressures measured at the air handler, representing the resistance the blower must overcome across the entire duct system.
VAV terminal box
A variable-air-volume terminal with a damper and airflow sensor that modulates primary airflow to a zone; reheat or fan-powered versions add heating capability.
Equal-friction method
A duct sizing approach that assigns the same friction rate to every section, commonly 0.08 to 0.10 in. w.c. per 100 ft for residential supply trunks.
Available static pressure
Total external static pressure minus losses from filters, coils, and accessories; the remaining pressure drives duct sizing and airflow through the distribution system.
Friction rate formula
Friction rate in inches of water per 100 ft equals available static pressure multiplied by 100 and divided by the total effective length of the longest run.
Total effective length
The straight-run duct length plus the equivalent lengths of all elbows, tees, and takeoffs on the longest path from fan to outlet.
Equivalent length
A published value in feet that converts a fitting's pressure loss into an equivalent straight-duct length, allowing fittings to be added to measured duct length.
Velocity method sizing
A sizing method that assigns target velocities: roughly 700 to 900 fpm for supply trunks, 500 to 700 fpm for branches, and 600 to 900 fpm for returns.
Duct area formula
Cross-sectional duct area in square feet equals airflow in cfm divided by velocity in fpm; equivalent round diameter derives from area equal to pi times radius squared.
Velocity-friction relationship
Friction loss per unit length rises approximately with the square of velocity, so doubling duct velocity roughly quadruples friction loss and noise.
Duct traverse
A measurement averaging velocity readings across a duct cross-section with a pitot tube or anemometer to calculate total airflow in cfm.
Flow hood
A calibrated balometer placed over a diffuser or grille that directly reads delivered airflow in cfm during balancing and diagnostic checks.
Temperature-rise method
Estimating airflow by dividing sensible heat in Btu/h by 1.08 times the temperature difference in degrees Fahrenheit across the equipment.
Balancing sequence
Set the air handler to design airflow, balance the branch farthest from the fan first, then adjust progressively toward the trunk.
Static pressure profile
A series of static readings taken along the air path; a large drop across a filter or coil reveals a restriction, while low readings suggest leakage.
Duct leakage test
A calibrated fan and pressure gauge test with all registers sealed that measures leakage cfm at a specified test pressure against a leakage class limit.
Evaporator delta T
The temperature difference between return and supply air across the coil; values outside roughly 16 to 22 degrees Fahrenheit suggest charge, airflow, or duct problems.
UL 181A sealant
A listed sealant for rigid fibrous glass duct board and closures; flexible duct and its connections require UL 181B listed tape or mastic.
Flex duct bend radius
Flexible duct should bend with a centerline radius of at least one duct diameter and be supported every 4 ft to prevent crushing and airflow loss.
Vapor retarder orientation
Duct insulation vapor barriers face the warm side of the assembly to keep the cold duct surface above dew point and prevent condensation and mold growth.
Duct leakage class
A SMACNA rating expressing allowable leakage in cfm per 100 square feet of duct area at 1 in. w.c., ranging from class 3 to class 30.
MERV rating
Minimum Efficiency Reporting Value from 1 to 16; MERV 8 captures about 20 percent of 3 to 10 micron particles, while MERV 13 captures roughly 85 percent.
ASHRAE 62.2
The residential ventilation standard requiring whole-house ventilation of about 0.03 cfm per square foot plus 7.5 cfm per occupant, with local exhaust in kitchens and baths.
Energy recovery ventilator
A ventilation device that transfers both sensible heat and latent moisture between exhaust and incoming outdoor air, reducing heating and cooling loads.
Filter pressure drop
The resistance a filter adds to the air path; it rises as the filter loads, so higher-MERV filters must fit within the equipment's rated external static pressure.