NATE GS Installation key terms
NATE GS Installation · Get comfortable with the vocabulary.
- superheat
- Related: subcooling, saturation temperature, thermostatic expansion valve
The temperature rise of refrigerant vapor above its saturation temperature at a given pressure, measured at the evaporator outlet to confirm the expansion valve is feeding the coil correctly.
- subcooling
- Related: superheat, saturation temperature, condenser
The temperature drop of liquid refrigerant below its saturation temperature at a given pressure, measured at the condenser outlet to confirm the coil is fully condensing and liquid reaches the metering device.
- saturation temperature
- Related: superheat, subcooling, pressure-temperature chart
The temperature at which a refrigerant changes phase at a given pressure; on a gauge manifold it is read as the boiling or condensing point corresponding to the measured pressure.
- pressure-temperature chart
- Related: saturation temperature, superheat, subcooling
A table or graph listing saturation pressures and temperatures for a specific refrigerant, used to convert gauge readings into the temperatures needed for superheat and subcooling calculations.
- thermostatic expansion valve
- Related: superheat, evaporator, metering device
A metering device that regulates refrigerant flow into the evaporator by sensing suction line temperature and evaporator pressure, maintaining a set superheat across the coil.
- metering device
- Related: thermostatic expansion valve, evaporator, liquid line
Any restriction that drops refrigerant pressure between the liquid line and evaporator, controlling flow and creating the low-side pressure that drives boiling in the coil.
- condenser
- Related: evaporator, subcooling, compressor
The outdoor coil where high-pressure refrigerant vapor rejects heat to ambient air and condenses into liquid, rejecting both sensible heat and the heat absorbed by the evaporator.
- evaporator
- Related: condenser, superheat, latent heat
The indoor coil where low-pressure refrigerant boils and absorbs heat from air moving across it, producing the cooling and dehumidification delivered to the conditioned space.
- compressor
- Related: condenser, evaporator, refrigerant
The pump that raises refrigerant vapor from low-side to high-side pressure, creating the pressure difference that circulates refrigerant and drives the entire refrigeration cycle.
- refrigerant
- Related: compressor, saturation temperature, ozone depletion potential
The fluid that circulates through the sealed system, absorbing heat as it boils at low pressure and releasing heat as it condenses at high pressure.
- static pressure
- Related: external static pressure, velocity pressure, duct sizing
The outward force per unit area exerted by air against duct walls, expressed in inches of water column and used to size blowers and evaluate duct and filter resistance.
- external static pressure
- Related: static pressure, airflow, blower
The total resistance to airflow measured across the air handler, including supply and return ducts, coils, filters, and grilles, used to verify blower performance against its rating table.
- velocity pressure
- Related: static pressure, airflow, balancing damper
The pressure created by air in motion, equal to total pressure minus static pressure, used with a pitot tube or flow hood to determine air speed in a duct.
- airflow
- Related: static pressure, duct sizing, blower
The volume of air moved per unit time, typically stated in cubic feet per minute, which must match equipment capacity and duct sizing for proper system performance.
- duct sizing
- Related: static pressure, airflow, plenum
Selecting duct dimensions so that airflow is delivered within acceptable friction loss and velocity limits, commonly done with friction-rate or velocity-based sizing methods.
- plenum
- Related: duct sizing, trunk and branch, return air
A boxed chamber connected to the air handler that distributes supply air to branch ducts or collects return air before the unit; it must be sealed and sized to avoid turbulence.
- trunk and branch
- Related: plenum, duct sizing, balancing damper
A duct layout in which a large main trunk carries air from the air handler and smaller branches deliver it to individual outlets or rooms.
- balancing damper
- Related: airflow, velocity pressure, return air
An adjustable plate inside a duct that is set during air balancing to restrict flow in one branch so that all outlets receive their design airflow.
- return air
- Related: plenum, static pressure, airflow
Air drawn back from conditioned spaces to the air handler for reconditioning; undersized or restricted returns raise static pressure and reduce total system airflow.
- latent heat
- Related: sensible heat, evaporator, relative humidity
Heat energy absorbed or released during a phase change without a temperature change, such as water vapor condensing on a cooling coil; it drives the dehumidification portion of the load.
- sensible heat
- Related: latent heat, dry bulb temperature, wet bulb temperature
Heat that changes the dry-bulb temperature of air or a substance without changing its phase, making up the portion of the load that a thermostat can directly sense.
- dry bulb temperature
- Related: wet bulb temperature, relative humidity, sensible heat
The temperature of air measured by an ordinary thermometer, unaffected by moisture content, and the value most thermostats use to control space temperature.
- wet bulb temperature
- Related: dry bulb temperature, relative humidity, latent heat
The temperature reached by air when water evaporates into it until saturated, indicating the evaporative cooling limit and used with dry bulb to determine humidity and enthalpy.
- relative humidity
- Related: wet bulb temperature, dry bulb temperature, latent heat
The amount of water vapor in air expressed as a percentage of the maximum the air could hold at that temperature; it falls as air is heated and rises as it is cooled.
- dew point
- Related: relative humidity, condensate drain, latent heat
The temperature at which air becomes saturated and water vapor begins to condense; surfaces colder than the dew point will sweat or collect condensate.
- condensate drain
- Related: dew point, evaporator, primary-secondary drain
The pipe and trap assembly that carries water removed from the cooling coil to a drain, requiring a trap to overcome cabinet pressure and a slope to prevent standing water.
- filtration
- Related: MERV rating, static pressure, ventilation
Removing airborne particles by passing air through a filter media, rated by MERV, which also adds static pressure that must be accounted for in blower selection.
- MERV rating
- Related: filtration, static pressure, ventilation
Minimum Efficiency Reporting Value, a 1-to-16 scale describing how well a filter captures particles of given sizes; higher ratings capture finer particles but add more resistance.
- ventilation
- Related: filtration, relative humidity, carbon monoxide
Deliberately introducing outdoor air into a building to dilute pollutants and control humidity, required by code for occupied spaces and often provided by an economizer or dedicated outdoor-air unit.
- carbon monoxide
- Related: combustion air, ventilation, flue
A colorless, odorless gas produced by incomplete combustion that can cause illness or death; combustion appliances must be vented and tested to keep levels within safe limits.
- combustion air
- Related: carbon monoxide, flue, backdrafting
The air supplied to a fuel-burning appliance for burning fuel, required by code in adequate volume and often drawn from outdoors to avoid depressurizing the building.
- backdrafting
- Related: carbon monoxide, combustion air, flue
Reversal of normal vent flow that spills combustion products into a building, typically caused by depressurization or a blocked flue; a serious carbon monoxide hazard.
- flue
- Related: combustion air, backdrafting, carbon monoxide
The passage that carries combustion gases from an appliance to the outdoors, which must be properly sized, sloped, and terminated to prevent spillage and condensation damage.
- lockout/tagout
- Related: disconnect, grounding, personal protective equipment
A safety procedure that de-energizes equipment and places a personal lock and tag on the disconnect so it cannot be re-energized while someone is working on it.
- grounding
- Related: bonding, overcurrent protection, disconnect
The intentional connection of electrical equipment to earth, providing a low-resistance path that lets overcurrent devices clear faults and protects people from shock.
- bonding
- Related: grounding, overcurrent protection, disconnect
Connecting metal parts together so they remain at the same electrical potential, preventing dangerous voltage differences and ensuring fault current has a reliable return path.
- overcurrent protection
- Related: disconnect, grounding, bonding
A fuse or circuit breaker that interrupts current above its rating, protecting conductors and equipment from overheating caused by shorts or overloads.
- disconnect
- Related: lockout/tagout, overcurrent protection, grounding
A switch or breaker that removes all power from a unit for service, required within sight of the equipment and sized to the circuit's ampacity.
- blower
- Related: airflow, external static pressure, duct sizing
The motor-driven fan in an air handler that moves air through the duct system; its speed taps or ECM settings are selected to deliver design airflow against the system's static pressure.