- Sensible capacity formula
- Qs = 1.08 × CFM × ΔT for standard air at sea level. At altitude, multiply by the density ratio so thin air does not inflate the calculated capacity.
- Total capacity formula
- Qt = 4.5 × CFM × Δh, where Δh is the entering-to-leaving enthalpy difference. This captures both sensible and latent capacity removed by the coil.
- Sensible heat ratio
- SHR = sensible capacity ÷ total capacity. A measured SHR far from the rated value usually points to airflow or charge problems rather than a failed compressor.
- EER versus SEER2
- EER is a single-point Btu/h per watt rating at 95 °F outdoor. SEER2 is a seasonal rating with different test conditions and static allowances, so the two numbers are not interchangeable.
- Oversizing symptoms
- Short runtimes, high cycling rate, poor latent removal, and a low coil ΔT indicate an oversized system. Runtime fraction below about 0.5 supports the diagnosis.
- Steady-state combustion efficiency
- Efficiency = (CO2 max − CO2 measured) ÷ CO2 max. Alternatively use flue O2 and stack temperature; condensing appliances gain roughly one point per 2 °F stack reduction.
- Heat pump COP from HSPF2
- COP ≈ HSPF2 ÷ 3.412 applies only at the rating point. Seasonal COP varies with outdoor bin temperature, so do not use the ratio for annual energy estimates.
- Fan laws
- CFM varies with RPM, static pressure with RPM squared, and brake horsepower with RPM cubed. A 10% speed increase raises power about 33%.
- External static pressure
- ESP is measured across the air handler between the return and supply plenum taps. Whether filter and coil drops are included depends on the manufacturer's table.
- Available static pressure
- Available static = blower rated ESP minus the drops of coil, filter, and grilles. It is the budget that the duct system's total equivalent length must consume.
- Equivalent length method
- Each fitting is converted to an equivalent length of straight duct. Total effective length = straight runs plus fitting equivalents; friction rate = available static ÷ total effective length.
- Duct leakage fraction
- Measured with a duct blaster at 25 Pa. Leakage fraction = CFM25 ÷ system CFM; about 10% is a common threshold for existing residential systems.
- Airflow from temperature rise
- CFM = output Btu/h ÷ (1.08 × ΔT). Use the electric heat kit's rated output or the furnace's temperature rise table to solve for airflow.
- Pitot traverse velocity
- V (fpm) = 4005 × √VP, where VP is velocity pressure in inches of water column. Residential branch velocities above roughly 900 fpm raise noise and static.
- Superheat definition
- Superheat = suction line temperature − saturated suction temperature at the measured suction pressure. It confirms the evaporator is fully boiling refrigerant before the compressor.
- Subcooling definition
- Subcooling = saturated condensing temperature − liquid line temperature. TXV systems are charged to the manufacturer's target, commonly 8 to 12 °F.
- Target superheat chart inputs
- Fixed-orifice charging charts take indoor wet-bulb and outdoor dry-bulb. The system is correct when measured superheat matches the chart at those conditions.
- TXV overcharge pattern
- Low superheat with high subcooling suggests overcharge or a restricted, overfeeding valve. High superheat with low subcooling suggests undercharge or a starved evaporator.
- Glide and PT columns
- Zeotropic blends have separate bubble and dew points. Use the dew point for superheat and the bubble point for subcooling; R-407C glides about 10 °F.
- Non-condensable symptoms
- High discharge pressure and high subcooling with normal superheat indicate air or nitrogen in the system. Compare condensing temperature to outdoor ambient plus design TD.
- Compression ratio
- Ratio = absolute discharge pressure ÷ absolute suction pressure. Above roughly 4:1 on a single-stage system suggests a restriction, low load, or high condensing temperature.
- Condensing temperature split
- Subtract outdoor ambient from saturated condensing temperature. A split well above the design 10 to 20 °F points to dirty coils, low airflow, or overcharge.
- Blower door leakage ratio
- CFM50 ÷ conditioned floor area gives the leakage ratio. Natural infiltration is roughly CFM50 ÷ 20 for a typical two-story house using the LBL factor.
- kWh savings calculation
- kWh saved = (baseline watts − post watts) × annual operating hours ÷ 1000. Document the source of the hours: bin data, runtime log, or manufacturer data.
- Degree-day normalization
- Compare pre- and post-retrofit energy use against heating or cooling degree-days. Without normalization, weather variation can look like savings or a regression.
- Simple payback
- Payback in years = installed cost ÷ annual dollar savings. State the assumed equipment life and discount rate when presenting life-cycle cost instead.
- Meter accuracy statement
- Record the instrument model, calibration date, and stated accuracy as ±% of reading plus digits. A clamp reading without true-RMS and accuracy is not defensible.
- Tariff-based cost savings
- Cost savings = kWh saved × the customer's actual tariff, including demand charges where applicable. An average national rate understates or overstates the real bill impact.
- Efficiency report contents
- Include measured static pressures, airflow, superheat and subcooling, combustion readings, blower door CFM50, and the before/after calculation method with its assumptions.
- Report evidence chain
- State the measurement method and instruments, compare measured values to manufacturer or code references, then present calculated savings with every assumption disclosed.
- Runtime fraction
- Runtime fraction = actual compressor runtime ÷ total elapsed time. Values well below about 0.5 support an oversizing diagnosis when paired with short cycling.