Class 2 circuit
A power-limited circuit per NEC Article 725 that operates at 30 V or less and 100 VA or less, or as listed in Table 725.121, used for signaling and control.
Plenum-rated cable
Cable listed for installation in ducts, plenums, and air-handling spaces. Examples include CMP, CL2P, FPLP, and CATVP. It has low smoke and flame spread characteristics.
Cable support interval
Horizontal communications cable must be supported at intervals not exceeding 4.5 ft and within 12 in of boxes, per NEC Article 800 installation requirements.
Abandoned cable rule
NEC requires removal of accessible abandoned communications, Class 2/3, and optical fiber cables unless they are tagged for future use.
Ohm's law
The relationship E = I x R, where E is voltage in volts, I is current in amperes, and R is resistance in ohms. The basis for all circuit calculations.
Power formula
P = E x I, where P is power in watts, E is voltage, and I is current. Equivalent forms are P = I²R and P = E²/R.
Voltage drop formula
For single-phase circuits, VD = 2 x K x I x L / CM, where K is 12.9 for copper, L is length in feet, and CM is circular mils.
Circular mils
A unit of conductor area equal to the square of the diameter in mils (thousandths of an inch). 12 AWG copper has 6,530 circular mils.
Article 725
The NEC article covering Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits, including wiring methods and cable listings.
Article 760
The NEC article covering fire alarm systems, including non-power-limited (NPLFA) and power-limited (PLFA) fire alarm circuits and cable types FPL, FPLR, and FPLP.
Article 800
The NEC article covering communications circuits, including cable types CMP, CMR, CM, CMG, and CMX, and their permitted substitutions in buildings.
Article 820
The NEC article covering community antenna television and radio distribution systems, including coaxial cable types CATVP, CATVR, CATV, and CATVX.
NC low voltage license
A special restricted electrical license issued by the NC State Board of Examiners of Electrical Contractors, authorizing low voltage work up to 50 volts.
Communications bonding conductor
A conductor of at least 14 AWG copper, listed, and run as short and straight as practicable, bonding communications cable shields to the building grounding electrode system.
Grounding electrode system
The set of electrodes required by NEC 250.50, including metal water pipe, building frame, concrete-encased electrode, ground rod, and plate electrodes.
Equipment grounding conductor
A conductor sized per Table 250.122 that provides a low-impedance path from equipment enclosures back to the source, enabling overcurrent devices to clear faults.
System bonding jumper
The connection between the grounded conductor and the equipment grounding conductor at a separately derived system, installed at the source or first disconnecting means.
Class A circuit
A fire alarm signaling circuit that survives a single open or ground fault by providing a return path to the panel, maintaining operation of all devices.
Class B circuit
A fire alarm signaling circuit that does not survive an open; a break disables devices beyond the break, so it is used where reduced reliability is acceptable.
Smoke detector spacing
On a smooth ceiling, spot-type smoke detectors are spaced no more than 30 ft apart and within 15 ft of walls, and at least 3 ft from air diffusers.
NAC voltage drop
Notification appliance circuit calculation ensuring that the appliance at the end of the circuit receives at least its rated minimum operating voltage under alarm conditions.
Fire alarm battery sizing
Secondary supply must power the system for 24 hours of standby plus 5 minutes of alarm for commercial systems, or 24 hours plus 15 minutes for voice evacuation.
TIA-568 channel length
The maximum horizontal channel is 100 m, consisting of up to 90 m of permanent link plus 10 m of patch cords at the work area and cross-connect.
Cat 6A cable
Balanced twisted-pair cable rated to 500 MHz, supporting 10GBASE-T to 100 m. It typically requires larger conductors and more careful installation than Cat 6.
OM3 fiber
A laser-optimized 50/125 µm multimode fiber with 2000 MHz·km bandwidth at 850 nm, supporting 10GBASE-SR to about 300 m and 40GBASE-SR4 to 100 m.
T568A versus T568B
Two pinout standards for RJ-45 connectors that differ in the assignment of pairs 2 and 3 (green and orange). Either is acceptable if used consistently throughout a project.
NC license classes
Limited (up to 600 V), Intermediate (up to 600 V, unlimited), Unlimited (any voltage), and Special Restricted Low Voltage (up to 50 V) issued by the NC Board.
Notice to Lien Agent
A NC-required notice filed on projects over $30,000 by subcontractors and suppliers to preserve mechanics' lien rights on improved real property.
Continuing education requirement
NC electrical licensees must complete annual continuing education hours to renew their license; verify the current hour requirement with the NC State Board.
Multimeter CAT rating
A safety category rating for test instruments: CAT II for portable equipment, CAT III for distribution circuits, and CAT IV for service entrance measurements.
Lockout/tagout
A procedure requiring verification of de-energization, application of a lock and tag, and confirmation of zero energy before servicing equipment, per OSHA 1910.147.
Ladder 4-to-1 rule
For every 4 ft of working height, the ladder base is set 1 ft from the wall. Maintain three points of contact and do not stand on the top two rungs.