NCCER Electrical · Keep the key ideas within reach.

Quick reference

Electrical Safety

  • Treat all conductors as energized until tested with a voltage tester rated for the circuit; test the tester before and after the check.

  • Lockout/tagout sequence: notify, shut down, isolate, lock and tag, release stored energy, and verify absence of voltage at the point of work.

  • A Class A GFCI trips at 4–6 mA of current imbalance and is used for personnel protection in locations specified by NEC 210.8.

  • Arc-rated PPE must meet or exceed the calculated incident energy; 1.2 cal/cm² is commonly used as the second-degree-burn threshold.

  • Rubber insulating glove classes: Class 00 ≤500 V, Class 0 ≤1,000 V, Class 1 ≤7,500 V, Class 2 ≤17,000 V.

  • Body current effects: about 1 mA perception, 10–15 mA let-go threshold, 30 mA respiratory tetany, and 50–100 mA ventricular fibrillation.

  • Only qualified persons may cross the restricted approach boundary, and doing so requires an energized work permit and appropriate PPE.

  • Temporary receptacles on construction sites require GFCI protection.

Quick reference

Electrical Theory and Circuits

  • Ohm's law: V = I × R; rearrange to I = V/R or R = V/I for resistive circuit calculations.

  • Power formulas: P = V × I = I²R = V²/R for DC and resistive AC loads.

  • Series circuit: current is constant, resistances add, and voltage divides in proportion to resistance.

  • Parallel circuit: voltage is constant across branches, branch currents add, and total resistance is less than the smallest branch resistance.

  • Capacitive current leads voltage by 90°, while inductive current lags voltage by 90° in a pure AC circuit.

  • Power factor = real power / apparent power = cos θ for sinusoidal waveforms.

  • Balanced three-phase real power: P = √3 × line voltage × line current × power factor.

  • RMS value of a sine wave = 0.707 × peak value; peak value = 1.414 × RMS.

  • Kirchhoff's current law: current entering a junction equals current leaving; Kirchhoff's voltage law: voltages around a closed loop sum to zero.

Quick reference

National Electrical Code and Code Calculations

  • Continuous loads require branch-circuit conductors and overcurrent devices sized at not less than 125% of the continuous load before adjustments.

  • A standard overcurrent device may carry only 80% of its rating continuously unless it is listed for 100% operation.

  • Ampacity adjustment for bundled current-carrying conductors: 80% for 4–6, 70% for 7–9, and 50% for 10–20 conductors.

  • Ambient temperature correction factors are based on a 30°C (86°F) ambient; higher ambient reduces conductor ampacity.

  • Informational notes recommend no more than 3% voltage drop on a branch circuit and 5% total from the service to the farthest outlet.

  • Box fill is calculated by summing conductor, device, fitting, and equipment-grounding volumes and comparing the total with the box volume from NEC 314.16.

  • Working space for energized equipment: at least 30 in wide, 36 in deep for 0–150 V to ground, and 6.5 ft high.

  • Dwelling-unit receptacle spacing: no point along the floor line may be more than 6 ft from an outlet, and wall spaces 2 ft or wider require an outlet.

  • GFCI protection requirements are in NEC 210.8; AFCI protection requirements are in NEC 210.12.

Quick reference

Raceways, Boxes, and Fittings

  • No more than 360° of total bends is permitted between pull points in a raceway run.

  • EMT must be supported within 3 ft of each box or fitting and at intervals not exceeding 10 ft.

  • Rigid metal conduit and intermediate metal conduit must be supported within 3 ft of each box and at intervals not exceeding 10 ft.

  • Maximum raceway fill: 53% for one conductor, 31% for two conductors, and 40% for three or more conductors.

  • Liquidtight flexible metal conduit must be supported within 12 in of each box and at intervals not exceeding 4.5 ft.

  • Bushings are required where conductors 4 AWG and larger enter a box or enclosure through a raceway.

  • Expansion fittings are required where raceway runs are subject to expansion or contraction, such as long PVC runs.

  • Raceway bends must not damage conductors; the minimum bend radius depends on raceway type and size.

  • Where a raceway terminates at a box, the raceway and box must be securely fastened and mechanically connected.

Quick reference

Conductors, Cables, and Wiring Devices

  • Copper conductor overcurrent protection: 14 AWG is generally limited to 15 A, 12 AWG to 20 A, and 10 AWG to 30 A.

  • Ampacity tables have 60°C, 75°C, and 90°C columns; the usable ampacity is limited by the lowest temperature rating of the conductor and its terminations.

  • Grounded conductors are identified by white or gray, or by three continuous white stripes on other than green insulation.

  • Equipment grounding conductors are identified by green, green with yellow stripes, or bare metal.

  • The neutral counts as a current-carrying conductor where it carries unbalanced current, but not in a balanced three-phase wye feeder.

  • THHN is a 90°C dry-location insulation with a nylon jacket; in wet locations its ampacity is limited to the 75°C column.

  • Splices must be made in accessible enclosures such as boxes or conduit bodies, not buried in walls or raceways.

  • Voltage drop approximates: VD = 2 × K × I × L / CM for single-phase, using conductor constant K and circular mils.

  • NM cable must be supported at intervals not exceeding 4.5 ft and within 12 in of each box.

Quick reference

Grounding, Bonding, Motors, and Controls

  • The grounding electrode conductor is sized from NEC Table 250.66 based on the largest ungrounded service conductor.

  • The equipment grounding conductor is sized from NEC Table 250.122 based on the rating of the circuit overcurrent device.

  • A single rod, pipe, or plate electrode must have 25 ohms or less resistance to earth, or a second electrode must be installed.

  • The main bonding jumper connects the grounded service conductor to the service equipment enclosure and the equipment grounding conductor at the service.

  • Motor branch-circuit conductors must have an ampacity of at least 125% of the motor full-load current from the Article 430 tables.

  • Motor overload protection is generally set at 125% of nameplate current for a service factor of 1.15 or higher, and 115% otherwise.

  • Motor short-circuit and ground-fault protection generally follows NEC 430.52: 250% for an inverse-time breaker, 175% for a dual-element fuse, and 300% for a non-time-delay fuse.

  • A motor disconnecting means must be within sight of the motor and controller or capable of being locked open.

  • Two-wire control uses a maintained-contact switch; three-wire control uses momentary start/stop pushbuttons with a holding contact and undervoltage release.