Lockout/tagout verification
After isolating and locking the disconnect, release stored energy and use a voltage tester rated for the circuit to confirm zero voltage at the point of work.
Class A GFCI threshold
A Class A ground-fault circuit interrupter trips when it senses 4 to 6 milliamperes of current imbalance between the ungrounded and grounded conductors.
Arc flash burn threshold
1.2 calories per square centimeter is the incident-energy level commonly used as the threshold for a second-degree burn on bare skin.
Rubber glove Class 00
Class 00 rubber insulating gloves are rated for use up to 500 volts AC and must be air-tested and electrically retested on the required schedule.
Let-go current threshold
The let-go threshold is about 10 to 15 milliamperes for most adults; at higher currents, a person may be unable to release an energized conductor.
Ohm's law
Voltage equals current times resistance (V = I × R); it applies to resistive portions of DC and AC circuits and can be rearranged to find current or resistance.
Series circuit rules
In a series circuit, current is the same through every component, resistances add, and source voltage divides in proportion to the individual resistance values.
Parallel circuit rules
In a parallel circuit, voltage is the same across every branch, branch currents add, and total resistance is found from the reciprocal of the sum of reciprocals.
Three-phase power formula
For a balanced three-phase load, real power equals the square root of three times line voltage times line current times power factor.
Power factor
Power factor is real power divided by apparent power, equal to the cosine of the angle between voltage and current for sinusoidal waveforms.
Continuous load 125 percent
Branch-circuit conductors and overcurrent devices supplying a continuous load must be sized at not less than 125 percent of the continuous load before other adjustments.
Conductor bundling derating
When four to six current-carrying conductors share a raceway or cable, the NEC adjustment table requires ampacity to be reduced to 80 percent of the table value.
Box fill calculation
Box fill is the sum of conductor volumes plus fittings, devices, and equipment-grounding allowances; compare the total to the box volume from NEC Table 314.16(A).
Voltage drop recommendation
NEC informational notes recommend no more than 3 percent voltage drop on a branch circuit and 5 percent total from the service to the farthest outlet.
Working space 110.26
Energized equipment requires a clear working space at least 30 inches wide, 36 inches deep for 0–150 volts to ground, and 6.5 feet high.
Dwelling receptacle spacing
In dwelling units, no point along the floor line may be more than 6 feet from a receptacle outlet, and wall spaces 2 feet or wider require an outlet.
360-degree bend rule
No more than 360 degrees of total bends, including offsets, is permitted between pull points in a raceway run.
EMT support intervals
Electrical metallic tubing must be supported within 3 feet of each box or fitting and at intervals not exceeding 10 feet.
Conduit fill percentages
NEC Chapter 9 limits raceway fill to 53 percent for one conductor, 31 percent for two, and 40 percent for three or more conductors.
LFMC support
Liquidtight flexible metal conduit must be supported within 12 inches of each box and at intervals not exceeding 4.5 feet.
RMC support intervals
Rigid metal conduit and intermediate metal conduit must be supported within 3 feet of each box and at intervals not exceeding 10 feet.
12 AWG copper ampacity
A 12 AWG copper conductor with 60°C terminations is generally limited to 20 amperes; the 75°C column permits 25 amperes where terminations are rated for it.
Grounded conductor color
The grounded circuit conductor must be identified by white or gray, or by three continuous white stripes on other than green insulation.
THHN insulation rating
THHN is a 90°C dry-location thermoplastic insulation with a nylon jacket; in wet locations its ampacity is limited to the 75°C column.
Neutral as current-carrying
The neutral counts as a current-carrying conductor when it carries the unbalanced current of a wye circuit, but not for a balanced three-phase wye feeder.
Splice location rule
Conductors must be spliced only in enclosures such as boxes or conduit bodies that are accessible without removing building finish.
Grounding electrode conductor sizing
The grounding electrode conductor is sized from NEC Table 250.66 based on the largest ungrounded service conductor; it connects the service neutral to the grounding electrode system.
Equipment grounding conductor sizing
The equipment grounding conductor is sized from NEC Table 250.122 based on the rating of the overcurrent device protecting the circuit.
25-ohm ground rule
A single rod, pipe, or plate electrode must have a resistance to earth of 25 ohms or less, or a second electrode must be installed.
Main bonding jumper
The main bonding jumper connects the grounded service conductor to the service equipment enclosure and the equipment grounding conductor at the service.
Motor branch conductor sizing
Motor branch-circuit conductors must have an ampacity of at least 125 percent of the motor full-load current from the appropriate Article 430 table.
Motor overload protection
Overload relays protect a motor from sustained overcurrent; they are generally set at 125 percent of nameplate full-load current when the service factor is at least 1.15, and 115 percent otherwise.