Domain 4 tests hands-on execution: how arrays are attached, flashed, bonded, torqued, and protected on roofs, ground mounts, and other structures.

Roof attachment and weatherproofing

  • Locate rafters with a stud finder and confirm by pilot hole; lag screws need the manufacturer's minimum embedment (commonly 2.5–3 in) into structural members.
  • Every penetration needs flashing integrated with the roofing - a flashed standoff or pitch pad plus roofing-compatible sealant. Sealant alone is not flashing.
  • Keep modules 3–6 in above the roof for airflow and cell cooling, following the rack manufacturer's standoff height.

Mechanical rules

  • Mid-clamps go between modules and end-clamps at array edges; they are not interchangeable.
  • Torque to the rack manufacturer's specification with a calibrated wrench. Over-torque crushes frames and voids warranties.
  • Bonding: rail splices, module frames, and rack parts need listed bonding hardware or a continuous equipment grounding conductor sized per 250.122.
  • Conduit: support within 3 ft of boxes and every 10 ft; add expansion fittings on long runs and at roof transitions; use UV-rated, wet-location raceway outdoors.

Worked example

For a 6:12 roof pitch, rise ÷ run = 6 ÷ 12 = 0.5, so the roof angle is tan⁻¹(0.5) = 26.6°. Instead of eyeballing the tilt legs, set them from the rack manufacturer's table for 26.6°; rails then run parallel to the roof plane and clamps land inside the marked clamp zones on the module frame.

Traps

  • Torquing by feel rather than a calibrated specification.
  • Swapping mid-clamps and end-clamps.
  • Skipping bonding jumpers across rail splices.
  • Standing or kneeling on module glass; carry modules vertically by the frame.