- Fall protection height, construction
- OSHA requires fall protection when employees work 6 feet or more above a lower level in construction; general industry triggers at 4 feet.
- Confined space oxygen range
- Entry is permitted only while oxygen is between 19.5 and 23.5 percent by volume; readings outside that range require ventilation, respiratory protection, and permit controls.
- Hot work fire watch
- A fire watch stays at the location during brazing, cutting, or grinding and continues after work stops until all slag and ignition sources are cooled.
- NPT thread taper
- Standard pipe threads are tapered 1 in 16, which is 3/4 inch per foot of length, so overtightening can split fittings and thin-wall pipe.
- Back-up wrench purpose
- A second pipe wrench is placed on the fitting or valve so turning force is not transferred into the piping, hangers, or equipment connection.
- Sling capacity at angle
- A sling's capacity decreases as its legs move away from vertical; the working load limit applies to the actual leg angle and must never be exceeded.
- Roll versus cut grooving
- Roll grooving forms a groove without removing wall material; cut grooving removes metal and is limited to Schedule 40 and heavier pipe.
- Dielectric union function
- A dielectric union or listed transition fitting separates steel from copper to stop galvanic corrosion driven by dissimilar-metal contact in the presence of water.
- Brazed copper joint filler
- Copper sprinkler tube is brazed with BCuP filler at roughly 1,100 to 1,500 degrees Fahrenheit, producing a joint stronger than the tube itself when properly made.
- Threaded joint size limit
- Threaded pipe joints in sprinkler systems are generally limited to 2 inch and smaller; larger pipe is joined by grooving, welding, or flanging.
- Hanger spacing for 2 inch pipe
- NFPA 13 allows a maximum hanger spacing of 25 feet for 2 inch Schedule 40 steel pipe, and 12 feet for 1 inch pipe.
- Lateral sway brace spacing
- Lateral braces are placed at intervals not exceeding 40 feet and within 20 feet of the end of the pipe run, resisting motion perpendicular to the pipe.
- Longitudinal brace spacing
- Longitudinal sway braces resist motion along the pipe axis and are spaced at intervals not exceeding 80 feet in NFPA 13 systems.
- Minimum hanger rod size
- The smallest rod permitted for sprinkler hangers is 3/8 inch; rod size and hanger type are selected from listings for the calculated load.
- Feet of head to psi
- One foot of water column equals 0.433 psi, so a 10 foot rise adds 4.33 psi of pressure and a 10 foot drop subtracts the same.
- Sprinkler K-factor formula
- Discharge from a sprinkler is Q equals K times the square root of P, where Q is gpm, K is the listed K-factor, and P is pressure in psi.
- Hazen-Williams C factor
- The Hazen-Williams roughness coefficient is about 120 for unlined steel pipe and about 150 for cement-lined or plastic pipe; a higher C means less friction loss.
- Dry pipe system capacity limit
- A single dry pipe system is limited to 750 gallons of capacity, which controls how much water must enter before the farthest sprinkler flows.
- Standard spray maximum spacing
- Standard spray sprinklers are spaced no more than 15 feet apart and protect no more than 225 square feet each in light hazard and 130 in ordinary hazard.
- Pendent deflector distance
- A pendent sprinkler deflector is positioned 1 to 12 inches below the ceiling, while an upright deflector sits 1 to 12 inches above the pipe.
- Sprinkler temperature color code
- NFPA 13 color code: 135 to 170 degrees Fahrenheit uncolored or black, 175 to 225 white, 250 to 300 blue, 325 to 375 red, and 400 to 650 green.
- Standpipe class definitions
- Class I provides 2-1/2 inch outlets for fire department hose, Class II provides 1-1/2 inch hose stations for occupants, and Class III provides both.
- Standpipe hydrostatic test
- Standpipe systems are hydrostatically tested at 200 psi for 2 hours, or at 50 psi above the maximum working pressure when that value is higher.
- Standpipe flow requirement
- The most remote standpipe must supply 500 gpm at 100 psi residual at the topmost outlet, with 250 gpm added for each additional standpipe up to 1,250 gpm.
- Fire pump 150 percent point
- A fire pump must deliver 150 percent of rated flow while holding at least 65 percent of rated pressure, and its shutoff cannot exceed 140 percent of rated.
- Jockey pump setting
- The jockey pump starts about 10 psi below normal system pressure, and the fire pump starts about 5 to 10 psi below the jockey pump setting.
- Light hazard water duration
- NFPA 13 requires a 30 minute water supply duration for light hazard, 60 to 90 minutes for ordinary hazard, and 90 to 120 minutes for extra hazard.
- NFPA 13 scope
- NFPA 13 governs the design and installation of automatic sprinkler systems, covering hazard classification, density, spacing, hangers, and acceptance testing.
- Working plan approval
- Sprinkler working plans and hydraulic calculations must be approved by the authority having jurisdiction before any pipe is installed on the project.
- Hydrostatic test pressure
- New sprinkler piping is hydrostatically tested at 200 psi for 2 hours, or 50 psi above working pressure if that is greater, with no leakage allowed.
- Main drain test purpose
- The main drain test compares static and residual pressure at the riser to a baseline, revealing a closed valve, obstruction, or degraded water supply.
- Inspector's test alarm time
- The inspector's test connection simulates one sprinkler; on a wet system the waterflow alarm must operate within 90 seconds of opening the valve.