NEBB Testing, Adjusting and Balancing Certified Technician (CT) flashcards
NEBB Testing, Adjusting and Balancing Certified Technician (CT) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Fan law for airflow
- Airflow varies directly with fan speed: CFM2 equals CFM1 multiplied by RPM2 divided by RPM1, at constant air density and system geometry.
- Velocity pressure formula
- At standard air density, velocity in feet per minute equals 4005 times the square root of velocity pressure in inches of water column.
- Pitot tube traverse
- A grid of velocity-pressure readings across a duct; the average velocity pressure is converted to average velocity and multiplied by duct area to obtain airflow.
- Terminal K factor
- A manufacturer-supplied multiplier that converts the square root of measured velocity pressure to airflow: CFM equals K times the square root of VP.
- Proportional air balancing
- Adjusting dampers so each branch carries the same percentage of its design airflow; the branch with the lowest percentage is used as the reference.
- Outdoor air measurement
- Measure intake airflow at the outdoor-air louver or flow station to confirm the minimum ventilation rate required by design and ASHRAE Standard 62.1.
- Hydronic flow equation
- Gallons per minute equal 2.448 times the inside diameter squared in inches times velocity in feet per second.
- Water horsepower
- Water horsepower equals gallons per minute times head in feet times specific gravity, divided by 3960; brake horsepower equals water horsepower divided by pump efficiency.
- Hydronic sensible heat
- For water near 60°F, Btu per hour equals 500 times gallons per minute times the temperature drop; glycol solutions require a lower constant.
- Balance valve Cv
- A valve's flow coefficient relates flow to pressure drop: flow equals Cv times the square root of differential pressure; use the manufacturer curve to set design flow.
- Reverse-return piping
- A piping arrangement that gives each terminal a nearly equal path length, reducing the need for balance valves compared with direct-return systems.
- Pitot tube alignment
- The impact port must face directly into airflow and the static ports must be perpendicular; misalignment beyond about ten degrees causes significant velocity error.
- Flow hood backpressure
- A balometer restricts grille airflow; apply the manufacturer's correction factor for hood size and airflow to avoid reading lower than actual.
- Instrument calibration record
- Record model, serial number, calibration date, and correction factors for every instrument; calibration must be traceable to a national standard such as NIST.
- Sling psychrometer use
- Wet-bulb and dry-bulb temperatures are read after slinging at proper velocity; the pair gives relative humidity and dew point on a psychrometric chart.
- Infrared thermometer limits
- Infrared meters infer temperature from emitted radiation; emissivity errors on shiny metal and distance-to-spot ratio can produce large errors, so contact sensors are preferred.
- Anemometer traverse
- Take multiple velocity readings across a duct or grille face, keep the probe perpendicular to flow, and average the readings to represent the area.
- NEBB airflow tolerance
- NEBB procedural standards typically require air quantities to be within plus or minus ten percent of design, with all terminals and branches measured and recorded.
- TAB final report
- The final report presents design versus actual airflow, water flow, pressures, temperatures, instrument calibration records, and a log of unresolved deficiencies.
- Pre-balance checklist
- Before balancing, verify fan rotation, belt tension, filter condition, damper and valve positions, and control sequence; corrections are documented and the system is rechecked.
- Specification precedence
- Contract documents state which document governs conflicts; addenda and RFIs modify the specifications, and the more stringent requirement usually governs.
- NEBB certification
- A NEBB-certified firm employs a certified professional, supervisor, and technicians, maintains instrument calibration, and undergoes quality assurance audits to keep certification.
- Fan operating point
- The intersection of the fan performance curve and the system curve; system pressure rises with the square of airflow, so the point moves as dampers change.
- Pump best efficiency point
- The flow and head at which a pump operates at maximum efficiency; operating far from this point causes vibration, cavitation, and bearing wear.
- Parallel pump operation
- Pumps in parallel add their flows at the same head; the combined operating point is found where the combined curve meets the system curve.
- Opposed-blade damper
- Blades rotate in opposite directions, producing a nearly linear airflow characteristic; parallel-blade dampers are used more for shutoff than modulation.
- Coil sensible heat
- At sea level, sensible Btu per hour equals 1.08 times airflow in CFM times the dry-bulb temperature difference across the coil.
- Lockout tagout
- Isolate and lock electrical, pneumatic, and hydraulic energy sources before service; verify zero energy and wait for rotating equipment to stop.
- VFD capacitor hazard
- Variable-frequency drives store dangerous voltage in capacitors; wait the manufacturer's specified discharge time before opening the enclosure.
- Confined space entry
- Test oxygen, flammable gas, and toxic gas before entry; use a permit, attendant, and rescue plan; never enter a confined space alone.
- Ladder setup angle
- Set an extension ladder at about a four-to-one ratio of working length to distance from the wall and maintain three points of contact while climbing.
- Jobsite TAB coordination
- Schedule balancing after duct cleaning and before ceiling closure, and coordinate with controls, electrical, and commissioning so systems are complete and operable.