NETA ETT Level 4 flashcards
NETA ETT Level 4 · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Arc flash boundary
- The distance at which incident energy equals 1.2 cal/cm² (5 J/cm²), marking the boundary where PPE is required for arc flash protection.
- Limited approach boundary
- The shock protection boundary for unqualified persons; for systems below 750 V, it is 1 foot (0.3 m) from exposed energized parts.
- Lockout/tagout verification
- After locking out, verify absence of voltage with a tester rated for the system, testing on a known live source before and after.
- Step potential
- Voltage difference between two points on the ground separated by about 0.8 m (one step), caused by fault current flowing through soil.
- Thevenin equivalent
- A linear circuit reduced to a single voltage source (open-circuit voltage) in series with a resistance (looking back with sources deactivated).
- Three-phase power formula
- Real power P = √3 × V_L × I_L × cosθ, where V_L is line voltage, I_L is line current, and θ is the power factor angle.
- Series resonance
- Occurs at f_r = 1/(2π√(LC)) where inductive and capacitive reactances cancel, leaving only resistance and minimum impedance.
- Per-unit impedance conversion
- Z_new = Z_old × (S_new/S_old) × (V_old/V_new)² converts per-unit impedance from one base to another for power system analysis.
- Symmetrical components
- A method decomposing unbalanced three-phase currents or voltages into positive, negative, and zero sequence components for fault analysis.
- Surge impedance loading
- SIL = V² / Z_c, where Z_c = √(L/C) is the surge impedance; it is the power level at which a line produces no reactive power.
- Polarization index
- Ratio of insulation resistance at 10 minutes to that at 1 minute; a value ≥2.0 is generally acceptable for Class B/F insulation.
- Guard terminal
- A terminal on an insulation tester that shunts surface leakage current away from the measurement, improving accuracy on contaminated insulation.
- Tan delta test
- Measures dielectric dissipation factor; increases with moisture, aging, and contamination; typical limit <0.5% for new high-voltage insulation.
- Turns ratio test
- Verifies transformer voltage ratio against nameplate; deviation >0.5% indicates shorted turns or tap changer problems.
- Sweep frequency response analysis
- Compares a transformer's impedance fingerprint over frequency to detect winding deformation, displacement, or core issues.
- Dissolved gas analysis
- Oil test interpreting gases like acetylene (arcing), ethylene (overheating), and hydrogen (partial discharge) to diagnose transformer faults.
- Contact resistance test
- Micro-ohm measurement across closed breaker contacts; values above manufacturer's limit (e.g., 50 µΩ) indicate pitting or misalignment.
- Vacuum bottle integrity test
- AC hipot applied across open vacuum interrupter contacts; breakdown or leakage indicates loss of vacuum and need for replacement.
- SF6 moisture test
- Measures water content in SF6 gas; should be below 500 ppmv for new gas; higher levels reduce dielectric strength and form acids.
- CT polarity
- Subtractive polarity means current into H1 produces current out of X1; verified by DC kick test to ensure correct relay operation.
- Differential protection setting
- Pickup set above maximum unbalanced current (e.g., 0.2–0.4 pu) to avoid false trips while detecting internal faults.
- Distance relay zones
- Zone 1 covers 80% of line, Zone 2 covers 120–150%, Zone 3 provides remote backup; reach settings depend on line impedance.
- VLF cable test
- Very low frequency (0.1 Hz) AC hipot test for aged cables; test voltage typically 2–3 × U0 for 15–60 minutes, reducing space charge effects.
- Time domain reflectometry
- Locates cable faults by measuring reflection time; distance = (velocity factor × c × time)/2, where c is speed of light.
- Partial discharge test
- Detects voids and defects in cable insulation; PD magnitude above 100 pC may require action; inception voltage indicates severity.
- Surge comparison test
- Applies a surge to each motor phase and compares waveforms; differences indicate turn-to-turn or phase-to-phase insulation faults.
- Motor current signature analysis
- Analyzes current spectrum to detect broken rotor bars, eccentricity, and load issues in rotating machinery.
- Core loss test
- Loop test measuring core losses in motors; high losses indicate lamination shorting or core damage.
- Fall-of-potential method
- Ground resistance measurement using three electrodes; spacing ≥5× electrode depth; typical target <5 Ω for industrial systems.
- Touch voltage limit
- Per IEEE 80, E_touch = (1000 + 1.5C_s ρ_s) × 0.116/√t, limiting voltage across the body from hand to feet during a fault.
- Total harmonic distortion
- THD = √(Σ V_h²)/V_1 × 100%; IEEE 519 limits THDv to 5% at the point of common coupling for systems below 69 kV.
- Voltage unbalance derating
- NEMA MG-1 requires motor derating if voltage unbalance exceeds 1%; unbalance = maximum deviation from average / average × 100%.