NETA ETT Level 4 · Give each week a clear focus.

8 weeks · About 7 hours per week

Week 1

Electrical Safety and Hazard Control & Power System Fundamentals and Equipment

  • Define the shock-hazard envelope for AC and DC systems by stating the body-current thresholds for perception, let-go, and ventricular fibrillation and the corresponding touch-voltage limits for dry, wet, and immersed skin.

  • Apply the NFPA 70E approach-boundary model by computing limited, restricted, and arc-flash boundaries for at least three sample tasks using incident-energy and shock tables you build yourself.

  • Explain the difference between a shock risk assessment and an arc-flash risk assessment, and list the PPE category selection inputs for each.

  • Trace how a phase-to-ground fault on a solidly grounded 480 V system differs in hazard profile from the same fault on a high-resistance-grounded system.

  • Sketch the single-line diagram of a typical industrial distribution system from utility service through main breaker, bus, and feeder breakers, labeling voltage levels and grounding type at each point.

Your checkpoint

A one-page hazard-and-single-line reference sheet with computed approach boundaries for three tasks and your labeled distribution sketch.

Week 2

Power System Fundamentals and Equipment & AC and DC Circuit Theory and Analysis

  • Solve phasor problems for series and parallel RLC circuits at 60 Hz, computing impedance, current, phase angle, and power factor without a calculator shortcut sheet.

  • Convert among real, reactive, and apparent power for a three-phase load and verify the result using both line-to-line and line-to-neutral formulations.

  • Describe the construction and operating principle of the core power system equipment: power transformers, instrument transformers, breakers, and surge arresters, noting one failure mode for each.

  • Explain per-unit normalization and compute per-unit impedances for a two-transformer radial system on a common base.

  • Interpret a nameplate for a distribution transformer and a generator, extracting kVA, voltage ratio, impedance, temperature rise, and connection type.

Your checkpoint

A worked problem set of ten circuit and per-unit calculations with answers checked against an independent method.

Week 3

Insulation Resistance and Dielectric Testing & Transformer Testing and Inspection

  • Select the correct test voltage and duration for insulation resistance testing of transformers, cables, and motors per the applicable field-test standard, and justify each choice.

  • Explain how temperature, humidity, and surface contamination bias insulation resistance readings, and describe the guard-terminal technique that removes surface leakage.

  • Interpret polarization index and dielectric absorption ratio results, including when the test is invalid and must be repeated.

  • Sequence a transformer commissioning test program covering winding resistance, ratio, insulation resistance, power factor or capacitance, and excitation current, stating what each test detects.

  • Diagnose three fault signatures from transformer test data: turn-to-turn shorts, moisture ingress, and core grounding problems.

Your checkpoint

A transformer test report template with pass/fail criteria and three completed case interpretations from data you generate or source.

Week 4

Circuit Breaker and Switchgear Testing & Protective Relays and Instrument Transformers

  • Describe the operating mechanism and arc-quenching method for air, vacuum, SF6, and oil breakers, and match each to its typical voltage class and application.

  • Interpret timing-test results, including contact bounce, pole discrepancy, and mechanism travel curves, and state the tolerance for each.

  • Explain CT ratio, burden, saturation, and accuracy class, and compute the secondary voltage required to saturate a given CT at a fault current.

  • Trace a protection scheme from CT through relay to trip coil, identifying where a wiring error would cause a false trip or a failure to trip.

  • Compare overcurrent, differential, and distance protection philosophies and state the application each serves best.

Your checkpoint

A protection-and-switchgear troubleshooting flowchart that maps five symptom patterns to their likely causes and confirming tests.

Week 5

Cable Testing and Diagnostics & Rotating Machinery Testing

  • Select the correct field test for a cable based on insulation type and age, comparing insulation resistance, DC hi-potential, very-low-frequency, and partial-discharge testing.

  • Explain why DC testing is discouraged or prohibited for aged XLPE cable and what diagnostic alternative applies.

  • Interpret time-domain reflectometry traces to locate a cable fault and distinguish an open from a short.

  • Plan a rotating-machinery test sequence covering insulation resistance, winding resistance, surge comparison, and vibration, and state the acceptance criteria for each.

  • Diagnose bearing failure, rotor bar problems, and winding insulation degradation from test and signature data.

Your checkpoint

A cable and motor diagnostic decision table that maps observed test results to a recommended next test and probable fault.

Week 6

Grounding, Ground Fault Protection, and Power Quality & Electrical Safety and Hazard Control

  • Compute ground electrode resistance for rod, grid, and plate configurations and explain how soil resistivity and seasonal moisture change the result.

  • Compare solidly grounded, low-resistance, and high-resistance grounding for continuity of service, fault detection, and personnel safety.

  • Explain the operation of a ground-fault circuit interrupter and a ground-fault protection relay, and state the trip thresholds and time delays typical for each.

  • Diagnose power-quality problems from waveform evidence: harmonics, voltage sags, transients, and neutral overload from triplen harmonics.

  • Revisit your week-one hazard sheet and revise any boundary or PPE conclusion that grounding practice changes.

Your checkpoint

A grounding and power-quality case file with three waveform or measurement scenarios analyzed to root cause and a corrective recommendation for each.

Week 7

Electrical Safety and Hazard Control & Power System Fundamentals and Equipment & Insulation Resistance and Dielectric Testing & Transformer Testing and Inspection & Circuit Breaker and Switchgear Testing & Protective Relays and Instrument Transformers & Cable Testing and Diagnostics & Rotating Machinery Testing & Grounding, Ground Fault Protection, and Power Quality

  • Build a 60-question mixed practice exam weighted to the published domain percentages and take it under timed conditions.

  • Score the practice exam by domain and rank your three weakest areas by percentage, not by count.

  • Re-study each weak area using your own week notes and rework every missed question to a correct final answer with a written justification.

  • List the formulas, thresholds, and standard clause numbers you still cannot recall from memory and drill them.

Your checkpoint

A scored practice exam with a per-domain breakdown and a written remediation log for every miss.

Week 8

Electrical Safety and Hazard Control & Power System Fundamentals and Equipment & Circuit Breaker and Switchgear Testing & Protective Relays and Instrument Transformers & Grounding, Ground Fault Protection, and Power Quality

  • Re-take a fresh 60-question mixed exam and compare domain scores against week seven to confirm improvement in every weak area.

  • Deliver a five-minute verbal walkthrough of a substation commissioning sequence, from safety planning through relay verification to energization.

  • Review every formula and threshold on your drill list and confirm recall without notes.

  • Practice the exam interface and question pacing so that no item is left unanswered for time reasons.

Your checkpoint

A final readiness scorecard showing both practice exam results side by side, with every domain at or above 70 percent.

Milestones

Week 2: You can compute per-unit impedances and three-phase power for a two-transformer system without notes and get the same answer two ways.

Week 4: You can explain, from memory, why a saturated CT causes misoperation and name the test that confirms it.

Week 6: You can select the correct grounding scheme and cable test method for three described field scenarios and defend each choice.

Week 7: Your timed practice exam score is recorded by domain and you have a written remediation log covering every missed item.

Week 8: Both practice exams are complete, every domain is at or above 70 percent, and your formula drill list is fully recalled without notes.