NICET FAS-III · Keep the key ideas within reach.

Quick reference

Codes, Standards, and References

  • NFPA 72 is the National Fire Alarm and Signaling Code; it establishes minimum design, installation, inspection, testing, and maintenance requirements.

  • NFPA 70 (NEC) Article 760 governs fire alarm wiring and classifies circuits as power-limited fire alarm (PLFA) or non-power-limited fire alarm (NPLFA).

  • NFPA 101 (Life Safety Code) and IBC Chapter 9 establish when detection, alarm, and notification are required by occupancy.

  • NFPA 72 Chapter 7 addresses documentation, including the Record of Completion; Chapter 14 addresses inspection, testing, and maintenance in current editions.

  • Cable ratings: FPL for general use, FPLR for riser, FPLP for plenum; the marking must match the installation environment.

  • All fire alarm equipment must be listed for the purpose by a nationally recognized testing laboratory.

  • The adopted code edition and local amendments are enforced by the AHJ; where documents conflict, the more restrictive requirement typically governs.

  • Manufacturer's published installation instructions must be followed for spacing, wiring, and device compatibility.

  • System design begins with approved drawings, specifications, and a documented sequence of operations.

Quick reference

Fire Alarm System Fundamentals and Design

  • Smoke detector nominal spacing on smooth ceilings is 30 ft (9.1 m), with a detector within 15 ft (4.6 m) of any wall, partition, or ceiling end.

  • Standard heat detector nominal spacing is 50 ft (15.2 m), with a detector within 25 ft (7.6 m) of walls or partitions.

  • Manual fire alarm boxes are mounted 42-48 in (1.1-1.2 m) above finished floor and within 5 ft (1.5 m) of an exit doorway.

  • Public mode audible notification: at least 15 dBA above average ambient or 5 dBA above maximum ambient of at least 60 seconds, whichever is greater, and at least 65 dBA.

  • Sleeping areas require at least 75 dBA at the pillow or 15 dBA above ambient, whichever is greater.

  • Voltage drop for a two-wire circuit: Vd = 2 x R x I x L; end-device voltage must remain at or above the listed minimum.

  • Battery sizing: standby current x 24 h plus alarm current x 5 min (15 min for voice), then apply manufacturer derating.

  • Class A pathways provide redundant return; Class B pathways use an end-of-line device and may lose part of the circuit on a single fault.

  • Duct smoke detectors supervise airflow but do not replace area smoke detection; elevator lobby, machine room, and hoistway detectors initiate Phase I recall per ASME A17.1.

Quick reference

Installation and Wiring

  • NEC Article 760 sets conductor types, installation methods, and separation requirements for fire alarm circuits.

  • PLFA conductors must be separated from electric light, power, Class 1, and NPLFA conductors by at least 2 in (50 mm) or a listed barrier unless otherwise permitted.

  • Fire alarm cable must be supported and secured per NEC and manufacturer requirements; do not exceed cable fill or bend radius.

  • Class B initiating and notification circuits require a supervised end-of-line device at the last device.

  • Class A circuits require a return conductor to the control unit; a single open fault must not prevent operation of all devices.

  • The fire alarm control unit requires a dedicated AC branch circuit marked FIRE ALARM; the disconnecting means must be accessible only to authorized personnel.

  • Ground faults on supervised circuits must annunciate a trouble condition; do not use earth ground as a circuit conductor.

  • Use listed plenum-rated cable, raceway, and splices in environmental air spaces.

  • Maintain battery polarity and use the manufacturer's listed charging and backup configuration.

Quick reference

Inspection, Testing, and Maintenance

  • NFPA 72 Table 14.4.3.2 establishes minimum inspection and testing frequencies; the complete system is functionally tested at least annually.

  • Smoke detector sensitivity is checked within 1 year of installation and at least every alternate year thereafter, or per manufacturer instructions.

  • Duct smoke detectors are tested annually; verify sampling tube airflow and alarm initiation.

  • Batteries are inspected quarterly and load-tested annually or per manufacturer instructions.

  • Before any test or impairment, notify the owner, supervising station, and fire department as required; tag the system and restore promptly.

  • Test records must document devices tested, results, deficiencies, and corrective actions; make records available to the AHJ.

  • Notification appliances are functionally tested annually for audibility and visual output.

  • After testing, confirm that all supervisory and alarm signals were received and that the system is returned to normal.

  • Use listed test methods and manufacturer-approved smoke or heat test equipment; do not alter detector sensitivity without authorization.

Quick reference

Project Management, Documentation, and Records

  • The Record of Completion documents the installed system, tested functions, and signatures of contractor and owner.

  • As-built drawings show actual device locations, wiring routes, and panel details and are delivered at closeout.

  • Submittals include shop drawings, product data, calculations, and sequence of operations; work proceeds only after approval.

  • RFIs clarify design intent; change orders authorize scope, cost, or schedule changes before work is performed.

  • Acceptance testing is witnessed by the AHJ or owner's representative and verifies code and design compliance.

  • Preliminary testing identifies and corrects deficiencies before the formal acceptance test.

  • O&M manuals, training, and spare parts are provided to the owner at turnover.

  • Maintain site-specific software, backups, and passwords; document software changes.

  • A punch list tracks incomplete or deficient items through final closeout.