NICET FAS-III study materials
NICET FAS-III study resources

NICET FAS-III flashcards

NICET FAS-III · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

NFPA 72
National Fire Alarm and Signaling Code; sets design, installation, testing, and maintenance requirements for fire detection and notification systems.
NEC Article 760
Covers fire alarm system wiring, including power-limited and non-power-limited circuits, conductor types, separation, and installation requirements.
FPLR cable
Fire alarm cable rated for riser installation; suitable for vertical shafts where plenum rating is not required.
FPLP cable
Plenum-rated fire alarm cable; required in environmental air spaces and return air plenums unless enclosed in a raceway.
AHJ
Authority Having Jurisdiction; official who reviews, permits, inspects, and approves fire alarm installations and enforces the adopted code edition.
NFPA 101
Life Safety Code; addresses means of egress, occupancy protection, and when detection, alarm, and notification systems are required.
Listed fire alarm equipment
Equipment evaluated by a nationally recognized testing laboratory for fire alarm use and marked accordingly; required by NFPA 72.
Smoke detector spacing
On smooth ceilings, nominal spacing is 30 ft (9.1 m), with detectors within 15 ft of walls, partitions, or ceiling ends.
Heat detector spacing
Nominal spacing for standard heat detectors is 50 ft (15.2 m) on smooth ceilings, with detectors within 25 ft of walls or partitions.
Manual pull station height
Operating handle must be between 42 in and 48 in above finished floor and located within 5 ft of an exit doorway.
Public mode audibility
Alarm sound must be at least 15 dBA above average ambient or 5 dBA above maximum ambient, whichever is greater, with minimum 65 dBA.
Sleeping area audibility
Fire alarm sound must reach at least 75 dBA at the pillow or 15 dBA above ambient, whichever is greater.
NAC voltage drop
Use Vd = 2 x R x I x L for a two-wire loop; verify end-of-line voltage remains above the appliance minimum operating voltage.
Battery standby capacity
Secondary supply sized for 24 hours standby plus 5 minutes alarm; voice systems require 15 minutes alarm, with derating per manufacturer.
Class B circuit
Supervised circuit with an end-of-line resistor; a single open or ground fault may disable part of the circuit but the fault is annunciated.
Class A circuit
Supervised circuit with a redundant return path; remains operational after a single open fault and annunciates the trouble condition.
Power-limited separation
PLFA conductors must be separated from power conductors by at least 2 in or a listed barrier unless code permits otherwise.
Dedicated AC circuit
Fire alarm control unit requires a dedicated branch circuit, marked FIRE ALARM, with disconnect controlled by authorized personnel.
Ground fault detection
Fire alarm circuits must be monitored for unintentional ground connections; a ground fault should annunciate a trouble condition.
Surge protection
Listed transient protection installed on circuits leaving the building or exposed to lightning, per manufacturer and NFPA 72.
Annual fire alarm test
NFPA 72 requires at least annual functional testing of the complete fire alarm system, including initiating devices, notification appliances, and control functions.
Smoke detector sensitivity
Sensitivity checked within one year of installation and at least every alternate year thereafter, or per manufacturer's published instructions.
Duct detector test
Duct smoke detectors are tested annually using manufacturer method; airflow and sampling tube operation are verified and alarm signal confirmed.
Impairment procedure
Before testing or repair, notify owner, supervising station, and fire department as required; tag system and restore promptly after work.
Record of inspection
Written record documenting tests, results, deficiencies, and corrective actions; retained and made available to the authority having jurisdiction.
Battery inspection
Batteries inspected quarterly for corrosion, terminal tightness, and charging; load tested annually or per manufacturer instructions.
Record of Completion
NFPA 72 document signed by contractor and owner confirming system installation, tested functions, and compliance with approved plans.
As-built drawings
Updated drawings showing actual installed device locations, wiring routes, and panel details; provided to owner at project closeout.
Submittal process
Contractor submits shop drawings, product data, and calculations for approval before installation; approved submittals guide construction.
RFI
Request for Information; formal document asking designer to clarify plans or specifications before work proceeds.
Change order
Written authorization modifying contract scope, cost, or schedule after original agreement; required before extra work.
Acceptance test
Functional test of installed system witnessed by AHJ or owner's representative to verify code and design compliance before acceptance.