NFPA 25
Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems; establishes frequencies and procedures for sprinklers, standpipes, pumps, and water supplies.
Impediment
A condition that prevents a system from performing as designed, such as a closed control valve or failed pump; requires immediate correction and notification to the AHJ.
Deficiency
A condition that could impair system performance but does not immediately prevent operation; it is documented and scheduled for correction per NFPA 25.
AHJ
Authority Having Jurisdiction; the organization or individual responsible for enforcing code requirements and approving installations, tests, and impairments.
Record retention
NFPA 25 generally requires inspection and test records to be kept on site for at least one year and made available to the AHJ upon request.
Fire pump churn test
A no-flow run of the fire pump to verify it starts and operates; churn pressure should not exceed 140% of rated pressure per NFPA 20.
150% flow test
Annual fire pump test requiring the pump to deliver 150% of rated flow at not less than 65% of rated pressure, verifying the pump curve.
Diesel pump weekly run
Diesel fire pumps must run weekly for at least 30 minutes; record oil pressure, coolant temperature, battery voltage, and fuel level.
Suction pressure
The pressure at the pump suction inlet; must remain positive and adequate to prevent cavitation and meet the system demand during flow tests.
Main drain test
A test of the water supply by fully opening the main drain; static and residual pressures are recorded and compared to baseline values to detect obstructions.
Spare sprinkler stock
NFPA 13 requires at least 6 spare heads for systems up to 300 heads, 12 for 300-1000, and 24 for over 1000 heads.
Dry pipe trip test
Annual test of a dry pipe valve by opening the test valve to verify the valve trips and water flows within the required time.
Control valve supervision
Control valves must be locked open or electrically supervised; a closed valve is an impairment requiring immediate correction and AHJ notification.
Gauge replacement
NFPA 25 requires replacement of pressure gauges every 5 years, or when they are damaged or fail calibration checks.
Class I standpipe
A standpipe system with 2.5-inch outlets intended for fire department use; requires 100 psi residual pressure at the topmost outlet per NFPA 14.
Class II standpipe
A standpipe system with 1.5-inch hose stations intended for occupant use; typically found in older or specific occupancy types.
Fire department connection
An exterior connection allowing the fire department to supplement the system water supply; caps, clappers, and access must be maintained clear.
Pressure-reducing valve
A valve that reduces downstream pressure to a safe level; requires annual testing and 5-year full flow testing per NFPA 25.
Smoke detector sensitivity
Sensitivity testing is required within one year of installation and every two years thereafter, or per manufacturer instructions, to verify alarm response.
Notification appliance test
Annual test of horns, strobes, and speakers to verify audibility at 15 dBA above ambient or 75 dBA minimum, and visibility per design.
Battery load test
Annual test of emergency power batteries to verify voltage, charging current, and capacity; batteries are replaced per manufacturer intervals.
Manual pull station test
Annual functional test of manual fire alarm pull stations to verify alarm transmission, annunciation, and proper reset.
Extinguisher hydrostatic test
Pressure testing of extinguisher shells at 5 or 12 year intervals depending on type; CO2 and water every 5 years, dry chemical every 12 years.
Class K extinguisher
A portable extinguisher for cooking oils and fats in commercial kitchens; uses wet chemical agent and requires semiannual system inspection.
Clean agent system
A gaseous suppression system using agents such as FM-200 or Novec 1230; requires annual inspection of agent quantity, pressure, and nozzles.
Wet chemical system
A kitchen hood suppression system using wet chemical agent; requires semiannual inspection and test of fusible links and manual pull stations.
Smoke control system
A system of fans, dampers, and barriers designed to control smoke movement; requires annual testing of fan operation and pressure differentials.
Stairwell pressurization
A smoke control method maintaining positive pressure in stairwells; verify pressure differential and door opening force during annual testing.
Emergency generator test
Level 1 emergency power systems require monthly exercise under load for at least 30 minutes and annual full load testing per NFPA 110.
Transfer switch test
Verification that the automatic transfer switch transfers load to the emergency source upon loss of normal power and returns properly.
Deficiency report
A written report identifying the system, component, condition, and recommended corrective action; classified as impediment or deficiency per NFPA 25.
Impairment procedure
Notification of the AHJ, owner, and occupants when a system is out of service; interim measures such as a fire watch may be required.