NICET Special Hazards Level I study materials
NICET Special Hazards Level I study resources

NICET Special Hazards Level I flashcards

NICET Special Hazards Level I · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Design area reduction quick-response
NFPA 13 permits a 25% reduction of the remote-area size for wet systems with quick-response sprinklers under flat ceilings of 10 ft or less, with a 1,500 sq ft minimum.
Sloped ceiling design area
Design area increases 30% for ceiling slopes over 2/12 up to 4/12, and an additional 30% per 2 in of slope beyond 4/12, per NFPA 13.
NFPA 13R scope
Covers automatic sprinkler systems in residential occupancies up to and including four stories, allowing reduced densities and omission of sprinklers in certain closets and bathrooms.
NFPA 13D scope
Applies to one- and two-family dwellings and manufactured homes, with a design goal of allowing occupants time to escape rather than protecting the structure.
NFPA 15 water spray
Covers fixed water spray systems using nozzles that produce specific spray patterns to protect hazards such as transformers, tanks, and flammable gas cylinders.
NFPA 16 foam-water systems
Covers the installation of foam-water sprinkler and foam-water spray systems, including discharge devices, piping, and foam concentrate supply.
NFPA 17A wet chemical
Standard for wet chemical extinguishing systems protecting commercial cooking appliances, hoods, and ducts; requires fuel and appliance shutdown upon actuation.
NFPA 2001 clean agent
Covers total flooding and local application clean agent systems using halocarbon or inert gases; design concentration includes safety factors over extinguishment values.
NFPA 11 foam systems
Standard for low-, medium-, and high-expansion foam systems; low-expansion foam is typical for hydrocarbon storage tanks and dike areas.
NFPA 750 water mist
Covers water mist systems, categorized by operating pressure: low below 175 psi, intermediate 175 to 500 psi, and high above 500 psi.
NFPA 12 CO2 systems
Covers carbon dioxide extinguishing systems for total flooding and local application; CO2 displaces oxygen, so occupied-area discharge requires pre-discharge alarm and delay.
NFPA 12A halon systems
Covers halon 1301 total flooding systems; halon production is phased out, so existing systems are maintained and replacements are considered at retrofit.
NFPA 17 dry chemical
Covers dry chemical extinguishing systems for total flooding and local application, commonly used for flammable liquid and gas hazards.
Remote area definition
The hydraulically most demanding area of sprinkler operation, whose size depends on occupancy classification and construction type under NFPA 13.
Density-area method
Sprinkler design method in which a discharge density in gpm per sq ft is applied over a specified remote area, determined from the occupancy hazard curve.
Hydraulic calculation purpose
Determines required pipe sizes and water supply by summing friction loss, elevation change, and discharge pressure to confirm adequate supply at the base of riser.
Safety factor in clean agent
Design concentration is set above the agent's extinguishment value by a factor to account for leakage and mixing uncertainty in the protected enclosure.
Hold time in clean agent
The period the design concentration must be maintained in the enclosure, typically 10 minutes, to allow occupant egress and prevent re-ignition.
Agent concentration calculation
Uses the enclosure volume, agent weight, and agent specific volume at the design temperature to confirm the required concentration is achieved.
Pre-discharge alarm requirement
Clean agent and CO2 total flooding systems in occupied spaces require audible and visual alarms before discharge, with a time delay for egress.
Foam expansion ratio
Ratio of finished foam volume to foam solution volume; low expansion is under 20:1, medium is 20:1 to 200:1, and high exceeds 200:1.
Foam concentrate proportioning
Mixing of foam concentrate with water at a specified percentage, commonly 3% or 6%, achieved by bladder tanks, pumps, or eductor systems.
Water mist droplet size
Water mist is defined by droplets with a Dv0.99 of 1,000 microns or less, distinguishing it from conventional sprinkler spray.
Wet chemical saponification
Chemical reaction between alkaline wet chemical agent and hot cooking oils that forms a soap-like foam, cooling the surface and sealing vapors.
Hood plenum protection
NFPA 17A requires protection of the cooking appliance, hood, and exhaust duct, with nozzles positioned per the manufacturer's listed design.
Manual pull station location
Required at a means of egress from the protected area, mounted at a listed height, and clearly identified for the cooking equipment system.
Dry chemical agent
Typically sodium bicarbonate or potassium bicarbonate based; extinguishes by interrupting the combustion chain reaction, not by cooling alone.
Total flooding application
Discharge of agent into an enclosed space to achieve a specified concentration throughout the volume, used for clean agent, CO2, and foam systems.
Local application
Agent is discharged directly onto the hazard rather than the entire enclosure, used for dip tanks, quench baths, and similar localized hazards.
Plan review submittal
Requires hydraulic calculations, agent quantity calculations, manufacturer data sheets, and nozzle layout drawings for approval before installation.
Acceptance test
Verifies system installation, including flow test, alarm operation, agent discharge test where permitted, and documentation of results for the authority having jurisdiction.
Inspection and maintenance
Periodic checks per NFPA 25 and system-specific standards, including agent weight verification, container pressure checks, and nozzle inspection.