NICET Special Hazards Level I key terms
NICET Special Hazards Level I · Get comfortable with the vocabulary.
- Clean agent
- Related: Halocarbon agent, Inert gas agent, Design concentration
An electrically nonconductive extinguishing agent that evaporates cleanly and leaves no residue, used to protect occupied spaces and sensitive equipment. It works mainly by absorbing heat and interrupting the combustion chemistry.
- Halocarbon agent
- Related: Clean agent, Design concentration, No-observed-effect level
A clean extinguishing agent built from carbon and halogen atoms, such as an HFC or FK-5-1-12. It extinguishes mainly by absorbing heat and disrupting the flame chemistry, and it is stored as a liquid.
- Inert gas agent
- Related: Clean agent, Design concentration, Discharge nozzle
A clean agent made from naturally occurring gases, usually nitrogen, argon, or a blend, that extinguishes by lowering the oxygen concentration below the level that supports combustion. It is stored as a compressed gas.
- Design concentration
- Related: Minimum design concentration, No-observed-effect level, Clean agent
The agent concentration selected for a hazard, set above the minimum extinguishing concentration with a safety margin and kept below the limit safe for people. It is the basis for calculating the agent quantity.
- Minimum design concentration
- Related: Cup burner value, Design concentration, Class B fuel
The lowest agent concentration accepted for a specific fuel, found by adding a required safety factor to the cup burner extinguishing value. Calculations must not fall below it for the hazard being protected.
- Cup burner value
- Related: Minimum design concentration, Class B fuel, Design concentration
The agent concentration, measured in a standardized small-scale test, that just extinguishes a liquid fuel flame. It is the reference point from which minimum design concentrations are derived for clean agents.
- No-observed-effect level
- Related: Design concentration, Egress time, Halocarbon agent
The highest agent concentration at which testing showed no adverse physiological effect on people. It sets the ceiling for designs in normally occupied spaces and is reported with a corresponding exposure time.
- Class B fuel
- Related: Cup burner value, Polar solvent, Design concentration
A flammable or combustible liquid or gas hazard, such as a solvent bath or fuel spill. Clean agent and foam designs for these fuels depend on the specific material and its flash point.
- Class C hazard
- Related: Clean agent, Class B fuel, Discharge nozzle
An electrical or electronic fire risk, such as energized equipment or a control cabinet. The classification matters because the extinguishing agent must be electrically nonconductive and leave no conductive residue.
- Total flooding system
- Related: Enclosure integrity test, Hold time, Discharge nozzle
A system that discharges agent into an enclosed volume to build and hold an extinguishing concentration throughout the space. The enclosure must be able to retain the agent for the required holding time.
- Local application system
- Related: Total flooding system, Discharge nozzle, Agent quantity
A system that applies agent directly onto a specific hazard rather than filling the whole room. It suits open or unenclosable equipment and is designed around the hazard's footprint and discharge rate.
- Enclosure integrity test
- Related: Hold time, Total flooding system, Design concentration
A door fan or pressurization test that measures leakage of the protected room to confirm it can hold the agent concentration for the required time. Failed results require sealing before acceptance.
- Hold time
- Related: Enclosure integrity test, Egress time, Total flooding system
The period during which a total flooding system must maintain the design concentration after discharge, allowing occupants to evacuate and responders to act. It is verified by the enclosure integrity test.
- Egress time
- Related: No-observed-effect level, Hold time, Predischarge alarm
The time allowed for occupants to leave a space before or during agent discharge, set by the design and by alarm and door hardware arrangements. It is tied to the physiological limits of the agent used.
- Predischarge alarm
- Related: Egress time, Discharge delay, Manual release station
An alarm that sounds before agent is released, warning occupants to evacuate and giving them time to leave. Its duration and audibility are set by the design and by the occupancy of the space.
- Discharge delay
- Related: Predischarge alarm, Manual release station, Abort switch
A programmed pause between the alarm or detection signal and the actual agent release. It provides time for evacuation and for personnel to abort a discharge when the hazard is minor.
- Abort switch
- Related: Discharge delay, Manual release station, Predischarge alarm
A manually operated device that stops or postpones the automatic discharge sequence, usually during the delay period. It is intended for trained personnel who can confirm the alarm is unwanted.
- Manual release station
- Related: Abort switch, Discharge delay, Detection circuit
A pull station or button that lets a person start agent discharge by hand, independent of automatic detection. It is located at the exit and marked for the hazard it controls.
- Detection circuit
- Related: Cross-zoning, Control panel, Manual release station
The wiring and devices, such as smoke or heat detectors, that sense a fire condition and signal the control panel. Cross-zoning or two-detector logic is often used to reduce false discharges.
- Cross-zoning
- Related: Detection circuit, Control panel, Discharge delay
A detection arrangement requiring signals from two independent zones before discharge, reducing the chance of a false release. One zone alone may sound an alarm but will not trip the agent.
- Control panel
- Related: Detection circuit, Release circuit, Cross-zoning
The unit that monitors detection circuits, manages alarms, delays, and abort signals, and energizes the release circuit. It also supervises the system for trouble conditions and records events.
- Release circuit
- Related: Control panel, Actuation device, Discharge nozzle
The supervised wiring and output that fires the actuation device, such as a solenoid or gas cartridge, to open the agent container valve. It is energized only when the discharge sequence is confirmed.
- Actuation device
- Related: Release circuit, Container valve, Control panel
The electrically or mechanically operated component that opens the container valve on command, such as a solenoid, squib, or gas cartridge. It is the final link between the control panel and the agent supply.
- Container valve
- Related: Actuation device, Discharge piping, Agent quantity
The valve on the agent cylinder that retains the charge and opens to release agent when actuated. It includes safety features such as a rupture disc and a pressure gauge connection.
- Discharge piping
- Related: Discharge nozzle, Container valve, Flow calculation
The pipe network that carries agent from the container to the nozzles in the protected space. Its size and layout are engineered to deliver the agent within the required time and pattern.
- Discharge nozzle
- Related: Discharge piping, Total flooding system, Flow calculation
A device that distributes agent into the protected space at a designed rate and pattern. Nozzle type, spacing, and elevation are chosen to achieve uniform concentration and avoid obstructions.
- Flow calculation
- Related: Discharge piping, Discharge nozzle, Agent quantity
The hydraulic analysis that predicts agent flow, pressure, and discharge time through the piping and nozzles. It confirms the design will deliver the required concentration within the specified time.
- Agent quantity
- Related: Design concentration, Total flooding system, Flow calculation
The mass or volume of extinguishing agent required for the hazard, calculated from the protected volume, design concentration, and expected leakage. It accounts for temperature and altitude corrections.
- Foam concentrate
- Related: Proportioning, AFFF, Foam expansion ratio
A concentrated liquid that, when mixed with water and air, produces foam for suppressing flammable liquid fires. Its type and percentage determine the proportioning and application rates used.
- AFFF
- Related: Foam concentrate, Polar solvent, Proportioning
Aqueous film-forming foam, a synthetic concentrate that spreads a thin film over liquid fuel surfaces to seal in vapors and cool the fuel. It is used for hydrocarbon spill and tank hazards.
- Polar solvent
- Related: AFFF, Foam concentrate, Foam expansion ratio
A fuel such as alcohol or ketone that breaks down ordinary foam, requiring an alcohol-resistant concentrate. Designers must match the foam type to the fuel to prevent rapid foam breakdown.
- Proportioning
- Related: Foam concentrate, Foam expansion ratio, Discharge device
The process of mixing foam concentrate with water at the correct percentage before it reaches the discharge device. It can be done with an eductor, a balanced pressure pump, or a bladder tank.
- Foam expansion ratio
- Related: Foam concentrate, Proportioning, Discharge device
The ratio of finished foam volume to the volume of the foam solution used to make it. It distinguishes low, medium, and high expansion foams and guides which application method is suitable.
- Discharge device
- Related: Foam expansion ratio, Proportioning, Foam concentrate
The foam maker, nozzle, or monitor that turns the foam solution into finished foam and directs it onto the hazard. Its type and placement control the reach and coverage of the foam blanket.
- Water mist system
- Related: Discharge nozzle, Total flooding system, Class C hazard
A special hazard system that discharges fine water droplets to cool the fire, displace oxygen near the flame, and wet surfaces. Small droplet size reduces water damage and electrical conductivity concerns.
- Kitchen hood suppression system
- Related: Fuel shutoff, Pre-engineered system, Detection circuit
A pre-engineered system that protects cooking appliances, hoods, and ducts with wet chemical or other listed agent. It interlocks with fuel shutoff and often with the building fire alarm.
- Fuel shutoff
- Related: Kitchen hood suppression system, Control panel, Pre-engineered system
A valve or control that stops the supply of gas or liquid fuel to protected cooking or process equipment when the suppression system actuates. It prevents continued fuel feed to the fire.
- Pre-engineered system
- Related: Kitchen hood suppression system, Flow calculation, Listing
A packaged suppression system whose design, pipe sizes, and nozzle placement are fixed by the manufacturer's listing and cannot be field-modified outside those limits. It requires limited site-specific calculation.
- Listing
- Related: Pre-engineered system, Approval, Actuation device
Formal recognition by a nationally recognized testing laboratory that a product meets a published standard. Listed components must be installed within the limits of their listing to remain acceptable.
- Approval
- Related: Listing, Authority having jurisdiction, Acceptance test
Acceptance of equipment or a design by the authority having jurisdiction, often after review of listings and plans. It is the formal permission to install or occupy the protected space.
- Authority having jurisdiction
- Related: Approval, Acceptance test, Listing
The official or agency responsible for enforcing the code and approving installations, plans, and tests. Their interpretations can set local requirements beyond the published standard.
- Acceptance test
- Related: Authority having jurisdiction, Approval, Enclosure integrity test
The documented test performed after installation to confirm the system operates as designed, including alarms, delays, and release logic. It is witnessed and recorded before the system is placed in service.