32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Hazen-Williams formula
Empirical friction-loss equation: p = 4.52 Q^1.85 / (C^1.85 d^4.87), giving psi loss per foot of pipe for flow Q in gpm, inside diameter d in inches, and roughness coefficient C.
C factor meaning
The Hazen-Williams roughness coefficient representing internal pipe condition; smoother linings have higher values (about 130–150), while older unlined cast iron drops toward 100, increasing calculated friction loss.
Velocity formula
Flow velocity in feet per second equals 0.4085 times gpm divided by the square of inside diameter in inches; used to screen layouts for excessive velocity and surge risk.
Equivalent length of fittings
The length of straight pipe that produces the same friction loss as a given fitting; added to actual pipe length to obtain total equivalent length for hydraulic calculations.
Total equivalent length
Actual pipe run length plus the sum of equivalent lengths of all fittings, valves, and devices in the path; the input to per-foot friction loss when using the equivalent-length method.
Elevation pressure change
Static pressure changes by 0.433 psi per foot of vertical rise, because a one-square-inch column one foot tall weighs about 0.433 pounds; subtracted when calculating available pressure at higher elevations.
Node pressure equality
At any junction where pipes meet, all connected branches share the same pressure; this single constraint drives flow splitting and is the starting condition for balancing looped networks.
Loop closure requirement
In a gridded system, the sum of friction losses around any closed loop must equal zero; layouts are solved iteratively until this condition holds for every loop.
Pipe schedule method limits
A tabular sizing method permitted only within the standard's stated size, pressure, and occupancy limits; it assumes specific schedule wall thicknesses and cannot be extrapolated to other schedules.
Remote area location
The hydraulically most demanding area of sprinkler operation, determined by calculation rather than by distance alone; it sets the minimum demand that the water supply must satisfy.
Density-area design approach
Design method selecting a discharge density in gpm per square foot applied over a defined remote area; the product gives the sprinkler flow demand before hose and inside/outside allowances.
Hose stream allowance
Additional flow, in gpm, added to the sprinkler demand to account for manual hose lines; duration and amount depend on occupancy hazard classification and the adopted standard.
Safety margin
The buffer between available supply pressure and calculated system demand, often 10–20 psi, retained so that supply fluctuations, pipe aging, or minor changes do not defeat the design.
Supply curve analysis
Plotting available pressure versus flow from a flow test, then comparing it to the system demand curve; the intersection shows the residual margin at the design point.
Static versus residual pressure
Static pressure is measured with no flow and reflects elevation and supply head; residual pressure is measured while flowing and reveals friction and supply capacity losses.
Backflow preventer loss
Devices such as reduced-pressure zone assemblies impose significant friction loss, often 5–15 psi, that must be included in the supply-to-riser pressure budget.
Standpipe Class I demand
Class I standpipe systems are hydraulically sized for the most remote 2½ inch outlet at 100 psi residual pressure and 250 gpm flow, unless the standard specifies otherwise.
Standpipe Class III demand
Class III systems combine 2½ inch and 1½ inch outlets; sizing must satisfy 100 psi at 250 gpm for the large outlet and 100 psi at 100 gpm for the small outlet.
Combined system sizing
Where sprinkler and standpipe share a supply main, the layout must satisfy whichever demand is greater at the point of connection, including simultaneous operation requirements.
Pump churn pressure
The shutoff pressure a fire pump produces at zero flow, typically 100–140 percent of rated pressure; the system and components downstream must be rated for this maximum.
Pump rated point
The flow and pressure at which a fire pump is rated, commonly at 100 percent flow; the curve must still deliver at least 65 percent of rated pressure at 150 percent flow.
Gridded system advantage
Looped piping provides multiple paths to each sprinkler, reducing friction loss and improving pressure at remote heads, but requires iterative hydraulic balancing to solve.
Tree system limitation
In a tree (branch-line) layout, all flow to a point travels one path, so downstream friction accumulates; larger mains or fewer heads per branch are typical remedies.
Sprinkler K-factor
Discharge coefficient relating pressure to flow: Q = K times the square root of pressure; K values around 5.6 are standard, while larger K heads deliver more flow at the same pressure.
Minimum operating pressure
The lowest pressure at which a sprinkler is listed to perform its design density; typically 7 psi for standard spray heads, with higher minimums for some special types.
Balancing valve function
A valve with a measured position indicator used to set and hold design flow to a zone or standpipe; its pressure loss must be included in the hydraulic calculation.
Pressure reducing valve
Device limiting downstream pressure to protect components and occupants; its friction loss at design flow, not just its set pressure, must be entered into the calculation.
Water supply duration
The time, in minutes, that the supply must sustain the design demand; it depends on hazard classification and is a required input when evaluating storage or connection capacity.
Inside and outside hose
Separate allowances for manual firefighting from within and outside the building; both may apply depending on occupancy and must be added to sprinkler flow demand.
Flow test correction
Measured static and residual pressures with a known pitot flow are adjusted to the design flow using the supply curve relationship, yielding expected residual pressure at demand.
N1.85 supply curve
Available pressure at a given flow follows a curve proportional to flow raised to about the 1.85 power, consistent with Hazen-Williams; this allows extrapolating flow-test data.
Hydraulic reference points
The base of riser, the highest sprinkler, and the remote area are the standard reference elevations; pressure budgets are computed between these points for clarity and checking.