- Hazen-Williams formula
- Empirical friction-loss equation: p = 4.52 Q^1.85 / (C^1.85 d^4.87), giving psi loss per foot of pipe for flow Q in gpm, inside diameter d in inches, and roughness coefficient C.
- C factor meaning
- The Hazen-Williams roughness coefficient representing internal pipe condition; smoother linings have higher values (about 130–150), while older unlined cast iron drops toward 100, increasing calculated friction loss.
- Velocity formula
- Flow velocity in feet per second equals 0.4085 times gpm divided by the square of inside diameter in inches; used to screen layouts for excessive velocity and surge risk.
- Equivalent length of fittings
- The length of straight pipe that produces the same friction loss as a given fitting; added to actual pipe length to obtain total equivalent length for hydraulic calculations.
- Total equivalent length
- Actual pipe run length plus the sum of equivalent lengths of all fittings, valves, and devices in the path; the input to per-foot friction loss when using the equivalent-length method.
- Elevation pressure change
- Static pressure changes by 0.433 psi per foot of vertical rise, because a one-square-inch column one foot tall weighs about 0.433 pounds; subtracted when calculating available pressure at higher elevations.
- Node pressure equality
- At any junction where pipes meet, all connected branches share the same pressure; this single constraint drives flow splitting and is the starting condition for balancing looped networks.
- Loop closure requirement
- In a gridded system, the sum of friction losses around any closed loop must equal zero; layouts are solved iteratively until this condition holds for every loop.
- Pipe schedule method limits
- A tabular sizing method permitted only within the standard's stated size, pressure, and occupancy limits; it assumes specific schedule wall thicknesses and cannot be extrapolated to other schedules.
- Remote area location
- The hydraulically most demanding area of sprinkler operation, determined by calculation rather than by distance alone; it sets the minimum demand that the water supply must satisfy.
- Density-area design approach
- Design method selecting a discharge density in gpm per square foot applied over a defined remote area; the product gives the sprinkler flow demand before hose and inside/outside allowances.
- Hose stream allowance
- Additional flow, in gpm, added to the sprinkler demand to account for manual hose lines; duration and amount depend on occupancy hazard classification and the adopted standard.
- Safety margin
- The buffer between available supply pressure and calculated system demand, often 10–20 psi, retained so that supply fluctuations, pipe aging, or minor changes do not defeat the design.
- Supply curve analysis
- Plotting available pressure versus flow from a flow test, then comparing it to the system demand curve; the intersection shows the residual margin at the design point.
- Static versus residual pressure
- Static pressure is measured with no flow and reflects elevation and supply head; residual pressure is measured while flowing and reveals friction and supply capacity losses.
- Backflow preventer loss
- Devices such as reduced-pressure zone assemblies impose significant friction loss, often 5–15 psi, that must be included in the supply-to-riser pressure budget.
- Standpipe Class I demand
- Class I standpipe systems are hydraulically sized for the most remote 2½ inch outlet at 100 psi residual pressure and 250 gpm flow, unless the standard specifies otherwise.
- Standpipe Class III demand
- Class III systems combine 2½ inch and 1½ inch outlets; sizing must satisfy 100 psi at 250 gpm for the large outlet and 100 psi at 100 gpm for the small outlet.
- Combined system sizing
- Where sprinkler and standpipe share a supply main, the layout must satisfy whichever demand is greater at the point of connection, including simultaneous operation requirements.
- Pump churn pressure
- The shutoff pressure a fire pump produces at zero flow, typically 100–140 percent of rated pressure; the system and components downstream must be rated for this maximum.
- Pump rated point
- The flow and pressure at which a fire pump is rated, commonly at 100 percent flow; the curve must still deliver at least 65 percent of rated pressure at 150 percent flow.
- Gridded system advantage
- Looped piping provides multiple paths to each sprinkler, reducing friction loss and improving pressure at remote heads, but requires iterative hydraulic balancing to solve.
- Tree system limitation
- In a tree (branch-line) layout, all flow to a point travels one path, so downstream friction accumulates; larger mains or fewer heads per branch are typical remedies.
- Sprinkler K-factor
- Discharge coefficient relating pressure to flow: Q = K times the square root of pressure; K values around 5.6 are standard, while larger K heads deliver more flow at the same pressure.
- Minimum operating pressure
- The lowest pressure at which a sprinkler is listed to perform its design density; typically 7 psi for standard spray heads, with higher minimums for some special types.
- Balancing valve function
- A valve with a measured position indicator used to set and hold design flow to a zone or standpipe; its pressure loss must be included in the hydraulic calculation.
- Pressure reducing valve
- Device limiting downstream pressure to protect components and occupants; its friction loss at design flow, not just its set pressure, must be entered into the calculation.
- Water supply duration
- The time, in minutes, that the supply must sustain the design demand; it depends on hazard classification and is a required input when evaluating storage or connection capacity.
- Inside and outside hose
- Separate allowances for manual firefighting from within and outside the building; both may apply depending on occupancy and must be added to sprinkler flow demand.
- Flow test correction
- Measured static and residual pressures with a known pitot flow are adjusted to the design flow using the supply curve relationship, yielding expected residual pressure at demand.
- N1.85 supply curve
- Available pressure at a given flow follows a curve proportional to flow raised to about the 1.85 power, consistent with Hazen-Williams; this allows extrapolating flow-test data.
- Hydraulic reference points
- The base of riser, the highest sprinkler, and the remote area are the standard reference elevations; pressure budgets are computed between these points for clarity and checking.