- Hydraulic Junction
- Related: Node, Loop, Hydraulic Grade Line
A point in a piping network where three or more pipe segments meet, causing flow to split or combine. Layout calculations must balance pressure and flow at every junction.
- Node
- Related: Hydraulic Junction, Path
A defined point in a hydraulic model, such as a junction, sprinkler, or water supply connection, where pressure and flow are calculated during layout analysis.
- Loop
- Related: Hydraulic Junction, Hardy Cross Method
A closed circuit of pipe in a gridded or looped system where water can reach a point by more than one route, making flow direction dependent on pressure loss.
- Hardy Cross Method
- Related: Loop, Hydraulic Junction
An iterative balancing technique that adjusts assumed flows around pipe loops until the head loss around each closed loop sums to zero, used for gridded system layout.
- Hazen-Williams Formula
- Related: C Factor, Friction Loss, Equivalent Pipe Length
An empirical equation relating friction loss in pipe to flow rate, internal diameter, pipe length, and a roughness coefficient C. It is the standard friction method in sprinkler layout.
- C Factor
- Related: Hazen-Williams Formula, Friction Loss
The Hazen-Williams roughness coefficient representing internal pipe condition. Higher values mean smoother pipe and less friction; unlined cast iron is low and cement-lined steel is high.
- Friction Loss
- Related: Hazen-Williams Formula, Equivalent Pipe Length, Remote Area
Pressure lost to resistance as water moves through pipe, fittings, and devices. It increases with flow and pipe length and must be summed along the most demanding path.
- Equivalent Pipe Length
- Related: Friction Loss, Fitting Loss
The length of straight pipe that produces the same friction loss as a fitting or valve. Adding it to actual pipe length converts fittings into a single computable length.
- Fitting Loss
- Related: Equivalent Pipe Length, Friction Loss
Pressure loss caused by turbulence through elbows, tees, reducers, and valves, often expressed as equivalent length or a loss coefficient applied at the fitting.
- Elevation Loss
- Related: Residual Pressure, Hydraulic Grade Line
Pressure change caused by height difference, equal to about 0.433 psi per foot of rise for water. Downward runs recover pressure; upward runs consume it.
- Hydraulic Grade Line
- Related: Elevation Loss, Friction Loss, Node
A plotted line showing available pressure head at each point along a piping route. Its slope reflects friction loss and its elevation reflects changes in height.
- Remote Area
- Related: Most Remote Sprinkler, Design Area, Friction Loss
The hydraulically most demanding area of sprinklers, where pressure is lowest and pipe runs and elevation are least favorable. Design flow is proven at this area.
- Most Remote Sprinkler
- Related: Remote Area, Minimum Operating Pressure
The single sprinkler requiring the highest pressure to deliver its design flow, typically the farthest and highest head in the remote area. Calculation starts here.
- Design Area
- Related: Remote Area, Density
The assumed number of sprinklers, or floor area, expected to operate simultaneously for a design fire. It sets the flow demand used in hydraulic calculations.
- Density
- Related: Design Area, Discharge Coefficient
The design discharge rate applied over a protected area, usually expressed in gallons per minute per square foot. It varies with hazard classification and storage configuration.
- Discharge Coefficient
- Related: Minimum Operating Pressure, Density
The K-factor relating sprinkler flow to pressure, where flow equals K times the square root of pressure. It defines how much water a head delivers at a given pressure.
- Minimum Operating Pressure
- Related: Most Remote Sprinkler, Discharge Coefficient
The lowest pressure at which a sprinkler must operate to produce its design discharge. Calculations must show this pressure at the most remote head.
- Residual Pressure
- Related: Static Pressure, Supply Curve, Elevation Loss
The pressure remaining in a water supply main while water is flowing at a measured rate. It is the basis for determining available supply during a fire.
- Static Pressure
- Related: Residual Pressure, Supply Curve
The pressure in a water system when no water is flowing. Comparing it with residual pressure reveals how much the supply drops under demand.
- Supply Curve
- Related: Residual Pressure, Static Pressure, Safety Margin
A graph of available pressure versus flow for a water supply, derived from flow test data and adjusted to the base of the riser. It defines the usable demand range.
- Safety Margin
- Related: Supply Curve, Residual Pressure
An allowance added to calculated demand so the supply exceeds system needs by a set amount, accounting for uncertainty in flow test data and pipe condition.
- Fire Pump
- Related: Churn Pressure, Supply Curve
A pump that boosts water supply pressure for a sprinkler system. Its rated flow, rated pressure, and churn characteristics must be compared with the system demand curve.
- Churn Pressure
- Related: Fire Pump, Maximum Working Pressure
The pressure a fire pump produces at zero flow, typically a percentage above rated pressure. It must not exceed the pressure rating of system components downstream.
- Maximum Working Pressure
- Related: Churn Pressure, Pressure Reducing Valve
The highest pressure a component or piping system is rated to withstand in service. Layout must keep pressures from churn and elevation within this limit.
- Pressure Reducing Valve
- Related: Maximum Working Pressure, Churn Pressure
A device that lowers downstream pressure to a set value, protecting sprinklers and fittings where supply or churn pressure exceeds their ratings.
- Riser
- Related: Riser Nipple, Main Drain
The vertical supply pipe connecting the water source or main to the sprinkler system, often housing the riser check valve, main drain, and flow switch.
- Riser Nipple
- Related: Riser, Main Drain
The short pipe section connecting the riser to the system main or alarm components. Its size and fittings affect friction and alarm accuracy.
- Main Drain
- Related: Riser, Flow Test
A valve and drain connection used to flush the system and perform the main drain flow test, which verifies that the supply can deliver the expected flow.
- Flow Test
- Related: Supply Curve, Residual Pressure, Main Drain
A measured test of static and residual pressure at known flow rates, used to build the supply curve for hydraulic layout. Results must be adjusted for elevation and time.
- Gridded System
- Related: Loop, Hydraulic Junction, Tree System
A piping arrangement where branch lines are connected by cross mains and feed mains at both ends, allowing water to reach sprinklers by multiple paths.
- Tree System
- Related: Gridded System, Remote Area
A piping layout where branch lines connect to a single main and flow travels one direction only, simplifying calculations but limiting redundancy.
- Branch Line
- Related: Cross Main, Most Remote Sprinkler
The pipe carrying sprinklers along a single line, usually the smallest pipe in the system and often the location of the most remote sprinkler.
- Cross Main
- Related: Branch Line, Feed Main
The pipe that supplies branch lines and is fed by the feed main or riser. Its size and layout strongly influence pressure at the remote area.
- Feed Main
- Related: Cross Main, Riser
The main pipe that delivers water from the riser or source to cross mains. It is typically larger than cross mains to limit friction loss.
- Pipe Schedule
- Related: Hydraulic Calculation, Branch Line
A sizing method that assigns minimum pipe diameters based on the number of sprinklers served, without hydraulic calculation, limited to defined hazard and system types.
- Hydraulic Calculation
- Related: Pipe Schedule, Remote Area, Hydraulic Junction
A pressure-and-flow analysis proving the system delivers design density over the design area with adequate supply. It documents each node, pipe, and fitting loss.