Question 1Codes, Standards and Plan Review

Under NFPA 13, working plans for a new automatic sprinkler system must be submitted to the authority having jurisdiction at what point?

  1. Only when the system includes a fire pump
  2. Before installation work begins Correct answer.
  3. Within 30 days after the system is placed in service
  4. After the final acceptance test is complete

Explanation

NFPA 13 requires working plans and supporting calculations to be submitted to and approved by the authority having jurisdiction before any equipment is installed or alterations are made. Plan review exists to catch code deficiencies while changes are still inexpensive.

Question 2Codes, Standards and Plan Review

For a light hazard occupancy, the maximum allowable spacing between standard spray sprinklers is:

  1. 12 ft
  2. 15 ft Correct answer.
  3. 20 ft
  4. 25 ft

Explanation

NFPA 13 limits standard spray sprinkler spacing in light hazard occupancies to a maximum of 15 ft (4.6 m) on branch lines and between branch lines, with a corresponding maximum protection area of 225 ft² per sprinkler.

Question 3Codes, Standards and Plan Review

The minimum operating pressure required at the most remote standard spray sprinkler in a hydraulically calculated system is:

  1. 15 psi
  2. 7 psi Correct answer.
  3. 5 psi
  4. 4 psi

Explanation

NFPA 13 establishes 7 psi (0.5 bar) as the minimum operating pressure for standard spray sprinklers, and the hydraulic calculation must show at least that pressure at the hydraulically most remote sprinkler.

Question 4Codes, Standards and Plan Review

Under NFPA 13, a church sanctuary is classified as which hazard?

  1. Ordinary Hazard Group 1
  2. Ordinary Hazard Group 2
  3. Extra Hazard Group 1
  4. Light Hazard Correct answer.

Explanation

NFPA 13 classifies places of assembly such as churches, together with offices, schools, and hospitals, as light hazard occupancies because the quantity and combustibility of contents is low and fires with relatively low rates of heat release are expected.

Question 5Codes, Standards and Plan Review

Under the International Building Code, a high-rise building is one with an occupied floor located more than what height above the lowest level of fire department vehicle access?

  1. 60 ft
  2. 75 ft Correct answer.
  3. 55 ft
  4. 100 ft

Explanation

The IBC defines a high-rise building as one with an occupied floor more than 75 ft (23 m) above the lowest level of fire department vehicle access, which triggers additional requirements such as automatic sprinkler protection and standpipes.

Question 6Codes, Standards and Plan Review

Which standard governs the design and installation of automatic sprinkler systems in one- and two-family dwellings and manufactured homes?

  1. NFPA 13R
  2. NFPA 14
  3. NFPA 13
  4. NFPA 13D Correct answer.

Explanation

NFPA 13D is the standard for the installation of sprinkler systems in one- and two-family dwellings and manufactured homes, where life safety rather than property protection is the design objective.

Question 7Codes, Standards and Plan Review

NFPA 13 classifies sprinkler temperature ratings into ranges. The ordinary-temperature range is:

  1. 175°F to 225°F
  2. 250°F to 300°F
  3. 100°F to 125°F
  4. 135°F to 170°F Correct answer.

Explanation

NFPA 13 groups sprinkler temperature ratings as ordinary (135°F to 170°F), intermediate (175°F to 225°F), and high (250°F to 300°F). The rating selected must be appropriate for the ambient temperature expected at the ceiling.

Question 8Codes, Standards and Plan Review

A waterflow alarm on a sprinkler system shall actuate within what time after a continuous flow equivalent to that of a single sprinkler?

  1. 45 seconds
  2. 30 seconds
  3. 90 seconds Correct answer.
  4. 60 seconds

Explanation

NFPA 13 requires the waterflow alarm to actuate within 90 seconds of a continuous flow equal to or greater than the flow from a single sprinkler, which limits water damage from small leaks while still providing prompt notification.

Question 9Codes, Standards and Plan Review

The minimum hose stream allowance for a light hazard occupancy designed under NFPA 13 is:

  1. 100 gpm Correct answer.
  2. 250 gpm
  3. 150 gpm
  4. 500 gpm

Explanation

NFPA 13 requires the water supply to include a hose stream allowance in addition to the sprinkler demand. Light hazard occupancies use 100 gpm, while ordinary and extra hazard occupancies generally use 250 gpm or more.

Question 10Codes, Standards and Plan Review

For an Ordinary Hazard Group 1 occupancy, the minimum water supply duration required by NFPA 13 is:

  1. 30 minutes
  2. 90 minutes
  3. 60 minutes Correct answer.
  4. 120 minutes

Explanation

NFPA 13 sets water supply durations by hazard: 30 minutes for light hazard, 60 minutes for Ordinary Hazard Group 1, 90 minutes for Ordinary Hazard Group 2, and 90 to 120 minutes for extra hazard occupancies.

Question 11Codes, Standards and Plan Review

In an Ordinary Hazard Group 2 occupancy, the maximum protection area per sprinkler is:

  1. 100 ft²
  2. 90 ft²
  3. 225 ft²
  4. 130 ft² Correct answer.

Explanation

NFPA 13 limits sprinkler protection area to 130 ft² per sprinkler with a maximum spacing of 15 ft for both Ordinary Hazard Group 1 and Group 2 occupancies.

Question 12Codes, Standards and Plan Review

Where a dry pipe system is installed, the hydraulically calculated design area must be increased by:

  1. 30 percent Correct answer.
  2. 10 percent
  3. 20 percent
  4. 15 percent

Explanation

Because water must travel farther to reach the operating sprinklers and more sprinklers are likely to open before water arrives, NFPA 13 requires the design area for dry pipe systems to be increased by 30 percent.

Question 13Codes, Standards and Plan Review

When quick-response sprinklers are used in a light hazard occupancy with the permitted conditions met, the design area may be reduced by up to:

  1. 20 percent
  2. 30 percent
  3. 40 percent Correct answer.
  4. 25 percent

Explanation

NFPA 13 permits a design area reduction where listed quick-response sprinklers are installed, with the largest reduction, 40 percent, allowed in light hazard occupancies and smaller reductions in ordinary hazard groups, subject to the stated conditions and minimum area limits.

Question 14Codes, Standards and Plan Review

NFPA 13 requires hangers supporting 1 in. and smaller steel pipe to be spaced not more than:

  1. 20 ft
  2. 10 ft
  3. 15 ft
  4. 12 ft Correct answer.

Explanation

NFPA 13 limits hanger spacing to 12 ft for 1 in. and smaller steel pipe and 15 ft for larger pipe sizes, unless closer spacing is needed to support the weight of the water-filled pipe or to meet seismic requirements.

Question 15Codes, Standards and Plan Review

The minimum clearance between sprinkler deflectors and the top of storage in a sprinklered area is:

  1. 36 in.
  2. 18 in. Correct answer.
  3. 12 in.
  4. 6 in.

Explanation

NFPA 13 requires a minimum clearance of 18 in. between the sprinkler deflector and the top of storage so the discharge pattern can develop properly and reach the fire. Greater clearance is acceptable and is often required for higher storage arrangements.

Question 16Codes, Standards and Plan Review

The hydrostatic test for new aboveground sprinkler piping is conducted at:

  1. 150 psi for 1 hour
  2. 150 psi for 2 hours
  3. 200 psi for 2 hours Correct answer.
  4. 200 psi for 1 hour

Explanation

NFPA 13 requires a hydrostatic test at 200 psi for 2 hours where the system working pressure is 150 psi or less; where working pressure exceeds 150 psi, the test pressure is 50 psi above working pressure for the same duration.

Question 17Codes, Standards and Plan Review

A standard spray sprinkler has a K-factor of 5.6 and is discharging at 16 psi. What is the flow from the sprinkler?

  1. 89.6 gpm
  2. 22.4 gpm Correct answer.
  3. 14.0 gpm
  4. 11.2 gpm

Explanation

Sprinkler flow is found with the formula Q = K√P, so 5.6 × √16 = 5.6 × 4 = 22.4 gpm. This relationship is the basis for converting the required density at each sprinkler into a pressure demand for the hydraulic calculation.

Question 18Codes, Standards and Plan Review

NFPA 13R systems are limited to residential occupancies that do not exceed:

  1. Five stories and 60 ft in height
  2. Three stories and 60 ft in height
  3. Four stories and 75 ft in height
  4. Four stories and 60 ft in height Correct answer.

Explanation

NFPA 13R may be used for residential occupancies up to and including four stories in height and not more than 60 ft above grade plane. Buildings beyond those limits must be protected under NFPA 13.

Question 19Codes, Standards and Plan Review

A Class I standpipe system provides:

  1. 1½ in. connections intended for fire department use
  2. 2½ in. connections intended for fire department use Correct answer.
  3. 1½ in. connections intended for occupant use
  4. 2½ in. connections intended for occupant use

Explanation

NFPA 14 defines Class I standpipes as systems with 2½ in. hose connections sized for fire department hose lines. Class II systems provide 1½ in. connections for occupant use, and Class III systems provide both.

Question 20Codes, Standards and Plan Review

Which document must be completed after flushing and hydrostatic testing of a new sprinkler system and made available to the authority having jurisdiction?

  1. The hydraulic design information sign
  2. The Contractor's Material and Test Certificate Correct answer.
  3. The water supply flow test report
  4. The owner's inspection, testing, and maintenance manual

Explanation

NFPA 13 requires the installing contractor to complete the Contractor's Material and Test Certificate for Aboveground Piping, documenting flushing, hydrostatic testing, and other acceptance items, and to provide it to the owner and the authority having jurisdiction.

Question 21Codes, Standards and Plan Review

Lateral and longitudinal sway bracing of sprinkler piping is required where the building is assigned to which seismic condition?

  1. Any seismic design category
  2. Seismic Design Category D or greater
  3. Seismic Design Category C or greater Correct answer.
  4. Seismic Design Category E only

Explanation

NFPA 13 requires protection against earthquake damage, including sway bracing, where the structure is assigned to Seismic Design Category C, D, E, or F. Structures in lower categories do not require this bracing.

Question 22Codes, Standards and Plan Review

The NFPA 13 density and design area for Extra Hazard Group 1 occupancies begins at:

  1. 0.20 gpm/ft² over 1500 ft²
  2. 0.25 gpm/ft² over 2000 ft²
  3. 0.40 gpm/ft² over 2500 ft²
  4. 0.30 gpm/ft² over 2500 ft² Correct answer.

Explanation

The density/area curves in NFPA 13 start Extra Hazard Group 1 at 0.30 gpm/ft² over 2500 ft², with higher densities applying over smaller areas. Extra Hazard Group 2 begins at 0.40 gpm/ft² over 2500 ft².

Question 23Codes, Standards and Plan Review

Under NFPA 13, sprinklers may be omitted from a concealed space that is:

  1. of noncombustible construction Correct answer.
  2. less than 24 in. in overall height
  3. entered only through an access panel
  4. protected by a listed smoke detector

Explanation

NFPA 13 permits sprinklers to be omitted from concealed spaces of noncombustible construction that contain no combustible materials, subject to specific exceptions. Concealed spaces of combustible construction generally require protection regardless of depth or access.

Question 24Codes, Standards and Plan Review

Plans show a calculated system demand of 900 gpm at 70 psi, while the water flow test shows only 820 gpm available at 70 psi. The plan reviewer should:

  1. Approve, provided the building is fully sprinklered
  2. Deny approval; the available supply is inadequate Correct answer.
  3. Approve, provided a fire department connection is installed
  4. Approve, since the values are within 10 percent

Explanation

NFPA 13 requires the water supply to equal or exceed the total system demand, including sprinkler flow and hose stream allowance, at the required pressure. A supply that falls short at the demand point leaves the system hydraulically inadequate and the plans cannot be approved as submitted.

Question 25Codes, Standards and Plan Review

Under NFPA 25, water supply and system gauges must be replaced or recalibrated at intervals not exceeding:

  1. 3 years
  2. 10 years
  3. 1 year
  4. 5 years Correct answer.

Explanation

NFPA 25 requires gauges to be replaced or tested and recalibrated at intervals not exceeding 5 years so that hydraulic readings used for inspection and maintenance decisions remain reliable.

Question 26Codes, Standards and Plan Review

Which NFPA document is the standard for the installation of standpipe and hose systems?

  1. NFPA 24
  2. NFPA 13
  3. NFPA 14 Correct answer.
  4. NFPA 20

Explanation

NFPA 14 is the Standard for the Installation of Standpipe and Hose Systems. It addresses system classes, pipe sizing, outlets, and pressure requirements for standpipes.

Question 27Codes, Standards and Plan Review

Which NFPA standard governs the installation of private fire service mains and their appurtenances?

  1. NFPA 25
  2. NFPA 13
  3. NFPA 14
  4. NFPA 24 Correct answer.

Explanation

NFPA 24 is the Standard for the Installation of Private Fire Service Mains and Their Appurtenances. It covers underground supply piping, hydrants, valves, and related components serving fire protection systems.

Question 28Codes, Standards and Plan Review

Which NFPA document establishes the minimum requirements for the inspection, testing, and maintenance of water-based fire protection systems?

  1. NFPA 13
  2. NFPA 20
  3. NFPA 25 Correct answer.
  4. NFPA 72

Explanation

NFPA 25 is the Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. It sets the ongoing ITM requirements that apply after a system has been accepted.

Question 29Codes, Standards and Plan Review

Sprinkler design density is expressed in which units?

  1. psi per square foot
  2. feet per second
  3. gpm per square foot Correct answer.
  4. gallons per minute

Explanation

Design density is the amount of water applied per unit of floor area per unit of time. It is expressed in gallons per minute per square foot (gpm/sq ft).

Question 30Codes, Standards and Plan Review

What is the maximum allowable spacing between standard spray sprinklers in a light hazard occupancy?

  1. 15 ft Correct answer.
  2. 12 ft
  3. 25 ft
  4. 20 ft

Explanation

NFPA 13 limits standard spray sprinklers in light hazard occupancies to a maximum spacing of 15 ft and a maximum protection area of 225 sq ft per sprinkler.

Question 31Codes, Standards and Plan Review

Under NFPA 25, who is ultimately responsible for ensuring that a sprinkler system is inspected, tested, and maintained?

  1. The installing contractor
  2. The authority having jurisdiction
  3. The insurance carrier
  4. The property owner Correct answer.

Explanation

NFPA 25 places the responsibility for inspection, testing, and maintenance on the property owner or the owner's designated representative. The owner may contract the work, but the responsibility remains with the owner.

Question 32Codes, Standards and Plan Review

What is the primary function of a post indicator valve on a sprinkler system?

  1. Regulate system pressure
  2. Drain the system after a test
  3. Show open or closed position Correct answer.
  4. Activate the waterflow alarm

Explanation

A post indicator valve provides a visible OPEN or SHUT indicator above ground so the status of the control valve can be seen without operating it. This supports the valve supervision requirements of NFPA 13 and NFPA 25.

Question 33Codes, Standards and Plan Review

What is the primary purpose of the main drain test?

  1. Check the alarm pressure switch
  2. Measure sprinkler discharge
  3. Test the fire pump at churn
  4. Verify the water supply Correct answer.

Explanation

The main drain test compares static and residual pressures to verify that the water supply is available and that upstream valves are open and unobstructed. A significant change from previous readings can indicate a closed valve or a supply problem.

Question 34Codes, Standards and Plan Review

What is the purpose of a quick-opening device, such as an accelerator, on a dry pipe system?

  1. Speed dry valve opening Correct answer.
  2. Drain condensate from the pipe
  3. Prevent water hammer in the riser
  4. Increase system air pressure

Explanation

An accelerator speeds the opening of the dry pipe valve after a sprinkler operates, reducing the delay before water reaches the sprinklers. This faster water delivery can allow a smaller design area increase for the dry pipe system.

Question 35Codes, Standards and Plan Review

A single-interlock preaction system is arranged so that the preaction valve opens in response to:

  1. Loss of system air pressure
  2. Actuation of a detection device Correct answer.
  3. Actuation of a sprinkler only
  4. Manual operation of a pull station

Explanation

In a single-interlock preaction system, the preaction valve opens when a detection device operates. Water then enters the piping, but discharge occurs only when a sprinkler also operates.

Question 36Codes, Standards and Plan Review

What is the minimum permitted distance from the deflector of a standard spray sprinkler to a smooth, flat ceiling?

  1. 3/4 in.
  2. 1/2 in.
  3. 2 in.
  4. 1 in. Correct answer.

Explanation

NFPA 13 requires standard spray sprinkler deflectors to be located not less than 1 in. and not more than 12 in. below the ceiling, unless specific conditions permit otherwise. The 1 in. minimum helps ensure proper spray development.

Question 37Codes, Standards and Plan Review

In a light hazard occupancy, what is the maximum permitted distance from a standard spray sprinkler to a wall?

  1. 8 ft
  2. 12 ft
  3. 10 ft
  4. 7.5 ft Correct answer.

Explanation

Sprinklers must be located not more than one-half the maximum allowable spacing from a wall. For light hazard with a 15 ft maximum spacing, the maximum wall distance is 7.5 ft.

Question 38Codes, Standards and Plan Review

A hydraulically calculated system has a design area of 2500 sq ft. What is the minimum length of the remote area rectangle?

  1. 55 ft
  2. 72 ft
  3. 60 ft Correct answer.
  4. 50 ft

Explanation

The remote area length must be at least 1.2 times the square root of the design area. For 2500 sq ft, 1.2 × 50 = 60 ft.

Question 39Codes, Standards and Plan Review

What is the minimum residual pressure required at the topmost 2½ in. outlet of a Class I standpipe system when flowing 250 gpm?

  1. 75 psi
  2. 150 psi
  3. 65 psi
  4. 100 psi Correct answer.

Explanation

NFPA 14 requires a minimum residual pressure of 100 psi at the topmost 2½ in. outlet of a Class I standpipe when the system is flowing 250 gpm from that outlet.

Question 40Codes, Standards and Plan Review

What is the function of a check valve installed in a sprinkler system riser?

  1. Serve as the main control valve
  2. Provide a drain path for the riser
  3. Prevent backflow to the supply Correct answer.
  4. Regulate pressure to the system

Explanation

A check valve allows flow in one direction only, preventing water from flowing back into the public supply or another water source. This protects the potable water supply from contamination.

Question 41Codes, Standards and Plan Review

A fire pump is rated at 1000 gpm at 100 psi. At 150 percent of rated flow, the discharge pressure must not be less than:

  1. 60 psi
  2. 65 psi Correct answer.
  3. 62 psi
  4. 50 psi

Explanation

NFPA 20 requires a fire pump to deliver at least 150 percent of rated flow at not less than 65 percent of rated pressure. Sixty-five percent of 100 psi is 65 psi.

Question 42Codes, Standards and Plan Review

What is the maximum allowable churn pressure of a fire pump, expressed as a percentage of rated pressure?

  1. 130 percent
  2. 140 percent Correct answer.
  3. 120 percent
  4. 150 percent

Explanation

Churn is operation at zero flow. NFPA 20 limits churn pressure to no more than 140 percent of the pump's rated pressure for most fire pumps.

Question 43Codes, Standards and Plan Review

When a backflow preventer is installed in the water supply to a sprinkler system, what must the plan reviewer confirm about the hydraulic calculation?

  1. The device is listed for fire service
  2. Its friction loss is in the calculation Correct answer.
  3. The device has a manual bypass
  4. The device is downstream of the alarm valve

Explanation

A backflow preventer adds friction loss to the supply, so that loss must be included in the hydraulic calculation for the system demand to be accurate. Omitting it can make an inadequate supply appear acceptable.

Question 44Codes, Standards and Plan Review

What is the minimum water supply duration required by NFPA 13 for a light hazard occupancy?

  1. 30 minutes Correct answer.
  2. 15 minutes
  3. 60 minutes
  4. 20 minutes

Explanation

NFPA 13 establishes a 30-minute water supply duration for light hazard occupancies. Higher hazard classifications require longer durations.

Question 45Codes, Standards and Plan Review

A sprinkler system riser serves a building 60 ft tall. Using 0.433 psi per foot, what pressure is needed at the base to overcome elevation?

  1. 13 psi
  2. 20 psi
  3. 52 psi
  4. 26 psi Correct answer.

Explanation

Elevation pressure loss is about 0.433 psi per foot of height. For 60 ft, the loss is 60 × 0.433 ≈ 26 psi.

Question 46Codes, Standards and Plan Review

For a Class I standpipe system with 2½ in. outlets, what is the maximum total flow that must be considered when multiple standpipes are in operation?

  1. 1250 gpm Correct answer.
  2. 2500 gpm
  3. 1000 gpm
  4. 1500 gpm

Explanation

NFPA 14 caps the total standpipe flow at 1250 gpm for systems with 2½ in. outlets, even when more standpipes could be supplied. The first standpipe is typically calculated at 500 gpm and each additional at 250 gpm.

Question 47Codes, Standards and Plan Review

A water flow test shows a static pressure of 60 psi and a residual pressure of 50 psi at 1000 gpm. Using the standard fire flow formula, what is the approximate available flow at 20 psi residual pressure?

  1. 1800 gpm
  2. 2500 gpm
  3. 2115 gpm Correct answer.
  4. 1500 gpm

Explanation

The standard formula is Q20 = Qr[(Ps − 20)/(Ps − Pr)]^0.54. Substituting gives 1000 × [(60 − 20)/(60 − 50)]^0.54 = 1000 × 4^0.54 ≈ 2115 gpm.

Question 48Codes, Standards and Plan Review

A hydraulically calculated system has a design area of 3000 sq ft. The remote area length is set at 1.2 times the square root of the design area. What remote area width is required?

  1. 15 ft
  2. 65.7 ft
  3. 45.7 ft Correct answer.
  4. 30 ft

Explanation

The length is 1.2 × √3000 ≈ 65.7 ft. The width is the design area divided by the length: 3000 ÷ 65.7 ≈ 45.7 ft, which exceeds the 15 ft minimum width.

Question 49Codes, Standards and Plan Review

Water flows at 1200 gpm through a 3 in. Schedule 40 steel pipe with an internal area of about 0.0513 sq ft. What is the approximate water velocity?

  1. 13 ft/s
  2. 26 ft/s
  3. 52 ft/s Correct answer.
  4. 39 ft/s

Explanation

Convert the flow to cubic feet per second: 1200 gpm ÷ 448.8 ≈ 2.67 cfs. Divide by the internal area: 2.67 ÷ 0.0513 ≈ 52 ft/s.

Question 50Codes, Standards and Plan Review

A standpipe system serves a building 120 ft tall. The required pressure at the topmost outlet is 100 psi, and pipe friction loss is 35 psi. Using 0.433 psi per foot, what is the minimum pressure required at the base?

  1. 220 psi
  2. 187 psi Correct answer.
  3. 135 psi
  4. 152 psi

Explanation

Base pressure equals outlet pressure plus elevation loss plus friction loss. Elevation loss is 120 × 0.433 ≈ 52 psi, so the total is 100 + 52 + 35 ≈ 187 psi.