NJ Water/Wastewater Operator: Treatment Processes and Process Control

NJ Water/Wastewater Operator · Work through your exam, one topic at a time.

All guide sections

Treatment Processes and Process Control

What you must know

Match treatment to source quality. Conventional surface treatment is coagulation, flocculation, sedimentation, filtration and disinfection. Also understand direct filtration, membranes (MF/UF for particles and pathogens, NF/RO for dissolved contaminants), greensand for iron, manganese and arsenic, granular activated carbon and ion exchange for organics, nitrate, radium and PFAS, lime softening versus ion-exchange softening, aeration and sequestration, fluoridation, and corrosion-control inhibitors such as zinc orthophosphate or silicates.

Process control means watching the right numbers: coagulant dose and pH, alkalinity, filtered-water turbidity plus early-warning tools (particle counts, streaming current), disinfectant residual, temperature, and CT. Backwash on head-loss limit or turbidity breakthrough, with enough bed expansion (roughly 15 to 25 percent) to fluidize the media.

Traps

  • Confusing theoretical detention time with T10 - CT calculations use T10.
  • Forgetting CT requirements rise in colder water and at higher pH, and that chloramines need far more CT than free chlorine.
  • Reading a log credit as removal rather than inactivation: 2-log is 99 percent, 3-log is 99.9 percent, 4-log is 99.99 percent.
  • Mixing dose (mg/L) with mass feed (lb/day).

Worked example

A plant treats 2.5 MGD and doses 1.5 mg/L of coagulant. Mass feed = mg/L x MGD x 8.34 = 1.5 x 2.5 x 8.34, about 31.3 lb/day. For disinfection, 1.2 mg/L free chlorine times 30 min T10 gives CT = 36 mg-min/L; if the required table value for your pH and temperature is 40, you are short and must raise residual or contact time.