New Mexico Low Voltage Practice study materials
New Mexico Low Voltage Practice study resources

New Mexico Low Voltage Practice flashcards

New Mexico Low Voltage Practice · Build recall with a focused review session.

33 cards. Read the term and the definition here. The deck at the top of this page is optional.

Ohm's Law
Current equals voltage divided by resistance (I = E/R). Used to solve for unknown voltage, current, or resistance in any DC or resistive AC circuit.
Three-Phase Power Formula
True power equals the square root of three times line voltage times line current times power factor. Applies to balanced three-phase loads.
Circular Mil
A unit of conductor cross-sectional area equal to the area of a circle one mil in diameter. For a solid round conductor, CM equals the diameter in mils squared.
Voltage Drop Formula
Single-phase drop equals two times K times current times length divided by circular mils. The factor of two accounts for the outgoing and return conductors.
Ampacity Correction Factors
Table ampacity is multiplied by an ambient temperature correction factor and by a conductor bundling adjustment factor. Both apply when conditions require.
Power Factor
The ratio of true power in watts to apparent power in volt-amperes. A value below one indicates reactive load, typically from motors or transformers.
Transformer Turns Ratio
Primary voltage divided by secondary voltage equals primary turns divided by secondary turns. Current ratio is the inverse of the voltage ratio.
Class 2 Circuit
A power-limited circuit classified by NEC Table 725.4 based on source and load. Its limited energy reduces fire and shock hazard.
Class 3 Circuit
A power-limited remote-control or signaling circuit with limits above Class 2 but still energy-limited. Class 3 cable may be substituted where Class 2 is required.
Plenum Rated Cable
Cable listed for installation in environmental air spaces such as return air plenums. Marked CL2P, CL3P, or FPLP depending on circuit class.
Low Voltage Drop Impact
On a 24-volt circuit, a two-volt drop is over eight percent. Low voltage systems require conductor sizing based on distance, not habit.
Power over Ethernet
IEEE 802.3 standards delivering DC power over data cable. 802.3af supplies 15.4 watts, 802.3at 30 watts, and 802.3bt up to 90 watts.
Conduit Fill Rules
NEC Chapter 9 Table 1 limits fill to 53 percent for one conductor, 31 percent for two, and 40 percent for three or more.
Box Fill Calculation
NEC 314.16 assigns volume per conductor: 2.0 cubic inches for 14 AWG, 2.25 for 12 AWG, and 2.5 for 10 AWG, plus device and clamp allowances.
EMT Support Interval
Electrical metallic tubing must be supported at intervals not exceeding 10 feet and within 3 feet of every box or termination fitting.
Communications Cable Support
Category and communications cable must be supported at intervals not exceeding 4.5 feet and within 12 inches of a box or termination.
Working Clearance Depth
NEC 110.26 requires 3 feet of depth for equipment up to 150 volts and 4 feet for 151 to 600 volts, with 30-inch width and 6-foot-6-inch height.
New Mexico Electrical Code
New Mexico adopts the NEC through the Construction Industries Division and publishes it with state amendments as 14.10.4 NMAC.
Authority Having Jurisdiction
The official who enforces the code, interprets its provisions, and may grant written exceptions for alternate methods or materials under NEC 90.4.
NEC 110.3(B) Requirement
Listed and labeled equipment must be installed and used in accordance with the listing and any instructions included in the listing or labeling.
Local Amendment Precedence
Where a locally adopted amendment is stricter than the state or national code, the stricter amendment governs the installation and inspection.
Arc Flash Boundary
The distance at which incident energy equals 1.2 calories per square centimeter. Inside this boundary, arc-rated PPE is required per NFPA 70E.
Test Before Touch
Verify the meter on a known live source, test the target circuit, then re-verify on the known source before trusting a zero reading.
Megohmmeter Test
An insulation resistance test applied at 250, 500, or 1000 volts DC. A reading below one megohm on low voltage wiring indicates damage or moisture.
Lockout Tagout
An energy control procedure requiring a lock, a tag, and verification of zero energy state by the person performing the work before contact.
Certifying Cable Tester
A tester that reports wire map, length, insertion loss, and near-end crosstalk, verifying that a link meets a named category performance standard.
Burdened Labor Rate
The base hourly wage plus payroll taxes, insurance, and benefits, typically 25 to 40 percent above base. Used to price labor in estimates.
Retainage
A percentage of each payment withheld until substantial completion. Commonly 5 to 10 percent on private New Mexico construction projects.
Written Change Order
A signed, priced document authorizing a scope change before work proceeds. Verbal direction should be confirmed in writing within 24 hours.
Smoke Detector Spacing
NFPA 72 permits 30-foot spacing on smooth ceilings, covering about 900 square feet per detector. Spacing is reduced for joisted or sloped ceilings.
Notification Appliance Circuit
A 24-volt DC circuit powering horns and strobes. Voltage drop must be calculated so the end device receives its minimum operating voltage.
T568A and T568B
Two pinout standards for eight-position modular jacks. They differ in pairs two and three, and the same standard must be used at both link ends.
Fail-Safe Versus Fail-Secure
A fail-safe lock releases when power is lost, supporting life safety egress. A fail-secure lock remains locked on power loss and is used where egress is not required.