NM Water/Wastewater Operator study materials
NM Water/Wastewater Operator study resources

NM Water/Wastewater Operator cheat sheet

NM Water/Wastewater Operator · Keep the key ideas within reach.

Quick reference

Water Treatment

  • Chlorine dose, lb/day = mg/L × MGD × 8.34.

  • Detention time, hr = basin volume (gal) ÷ (flow, gpm × 60).

  • Filter loading rate, gpm/ft² = flow (gpm) ÷ filter area (ft²); rapid sand filters normally run 2–4 gpm/ft².

  • Combined filter effluent turbidity must be ≤0.3 NTU in at least 95% of monthly samples and never exceed 1 NTU.

  • CT = disinfectant residual (mg/L) × contact time (min); required CT increases as pH rises and decreases as water temperature rises.

  • A jar test selects coagulant dose, coagulation pH, rapid-mix intensity, and flocculation time before full-scale changes are made.

  • Fluoride: primary MCL 4.0 mg/L, secondary standard 2.0 mg/L; concentrations above about 2 mg/L can cause dental fluorosis.

  • Langelier saturation index: negative = corrosive water, zero = balanced, positive = scale-forming water.

  • Concentration conversion: 1% = 10,000 mg/L; mg/L = (lb/day × 8.34) ÷ MGD.

Quick reference

Water Distribution

  • Head and pressure: 1 ft of water column = 0.433 psi; 1 psi = 2.31 ft of head.

  • Flow: Q = A × V; Q (gpm) = 2.448 × inside diameter (in)² × velocity (ft/s).

  • Maintain a free chlorine residual of at least 0.2 mg/L throughout the distribution system; the maximum residual disinfectant level is 4.0 mg/L.

  • New main disinfection: 50 mg/L chlorine solution held 24 hours, then flushed and sampled for coliform bacteria before the main is placed in service.

  • Backflow protection hierarchy, best to least: air gap, reduced-pressure-zone assembly, double check valve, atmospheric vacuum breaker.

  • Distribution storage: equalizing volume commonly 15–25% of maximum day demand, plus fire flow and emergency reserve.

  • Water hammer is a pressure surge from rapid velocity change; slow-closing valves, surge tanks, and air chambers reduce it.

  • Cavitation occurs when available net positive suction head is less than required NPSH; symptoms are noise, vibration, and impeller pitting.

  • Unaccounted-for water = production metered − authorized metered sales − known system uses.

Quick reference

Wastewater Treatment

  • F/M ratio = lb BOD5 applied per day ÷ lb MLVSS in aeration; conventional activated sludge 0.2–0.4, extended aeration 0.05–0.15.

  • MCRT = lb solids in the aeration tank ÷ lb solids leaving daily (waste sludge plus effluent solids).

  • SVI = (settled sludge volume after 30 min, mL/L ÷ MLSS, mg/L) × 1000; 80–150 indicates good settling.

  • Nitrification consumes about 4.6 lb O2 and 7.14 lb alkalinity (as CaCO3) per lb ammonia-N oxidized; keep dissolved oxygen at 2 mg/L or more.

  • BOD5 is measured over 5 days at 20 °C using seeded dilution water and dissolved oxygen depletion.

  • Sludge yield in conventional activated sludge is roughly 0.5–0.6 lb VSS per lb BOD5 removed.

  • MLSS and MCRT are controlled by waste activated sludge rate; increasing WAS lowers both MCRT and MLSS.

  • Typical secondary effluent limits are 30 mg/L BOD5 and 30 mg/L TSS, with fecal coliform limits set in the discharge permit.

  • Increase return activated sludge rate when sludge blankets rise in the clarifier; decrease when blankets are thin and dilute.

Quick reference

Wastewater Collection

  • Gravity sanitary sewer design velocity: minimum 2 ft/s (self-cleaning) and maximum about 10 ft/s to limit scour and hydrogen sulfide release.

  • Manning equation (English units): V = (1.486/n) × R^(2/3) × S^(1/2).

  • Roughness n: about 0.013 for new concrete or vitrified clay pipe, 0.015 or higher for old or tuberculated pipe.

  • Pipe slope in ft/ft = fall ÷ length; percent slope = ft/ft × 100.

  • Infiltration is groundwater entering through defects; inflow is storm water entering through direct connections such as roof drains and catch basins.

  • Confined space entry requires oxygen 19.5–23.5%, hydrogen sulfide below 10 ppm, combustible gas below 10% of the lower explosive limit, a permit, and an attendant.

  • Use a drop manhole when the incoming sewer invert is more than about 24 in above the outgoing invert.

  • Smoke testing reveals illegal storm connections and broken pipe; dye testing confirms a specific identified connection.

  • Lift station wet well usable volume (gal) = pump capacity (gpm) ÷ (4 × allowable pump starts per hour).