NV Fire Alarm flashcards
NV Fire Alarm · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 72
- National Fire Alarm and Signaling Code; governs installation, inspection, testing, and maintenance of fire alarm systems in the United States and is adopted by reference in Nevada.
- Addressable system
- A fire alarm system where each device has a unique address, allowing the control unit to identify the specific device in alarm or trouble.
- Conventional zone
- A circuit grouping multiple initiating devices so the control unit identifies only the zone, not the individual device, when an alarm occurs.
- Alarm signal timing
- In a protected premises system, the alarm signal must reach notification appliances within 10 seconds of activation per NFPA 72 requirements.
- Ohm's law
- V = I × R; voltage equals current times resistance. Used to calculate voltage drop and verify circuit capacity in fire alarm wiring.
- Voltage drop limit
- NFPA 72 requires notification appliance circuits to not exceed 10 percent voltage drop from the control unit to the last appliance on the circuit.
- Class B circuit
- A circuit that does not return to the control unit; a single open fault disables all devices downstream of the break.
- Class A circuit
- A circuit that returns to the control unit; a single open fault does not disable the circuit, providing higher reliability.
- FPLP cable
- Plenum-rated fire alarm cable required in environmental air spaces; resists flame spread and low smoke production per NEC Article 760.
- Photoelectric detector
- Smoke detector using light scattering to detect larger particles typical of smoldering fires; responds well to slow, smoky fires.
- Ionization detector
- Smoke detector using radioactive source to ionize air; responds quickly to small particles from fast-flaming fires.
- Duct smoke detector
- Detector installed in HVAC ductwork; required where air handling units exceed 2,000 CFM and serve multiple stories or large areas.
- Manual pull station height
- Manual fire alarm pull stations must be mounted 42 to 48 inches above finished floor and within 5 feet of an exit door.
- Waterflow switch
- Device that detects water flow in sprinkler piping and initiates an alarm signal within 90 seconds of flow per NFPA 72.
- End-of-line resistor
- Component at the end of a conventional initiating or notification circuit that allows the control unit to supervise the circuit for open faults.
- Audible appliance level
- Public mode audible appliances must produce at least 65 dBA at 10 feet or 15 dBA above ambient, whichever is greater.
- Visible appliance candela
- Candela rating determines light intensity; NFPA 72 Table 18.5.5.1 specifies minimum ratings based on room size and mounting.
- Synchronization
- Visible appliances visible from a single point must flash in synchronization to avoid seizure risk; requires compatible control or sync modules.
- Voice intelligibility
- Voice evacuation systems must achieve a Speech Transmission Index of at least 0.50 or Common Intelligibility Scale of at least 0.45.
- UL 864
- Listing standard for fire alarm control units; ensures equipment meets performance and reliability requirements for fire protection systems.
- Secondary power
- Battery backup sized for 24-hour standby plus 5 minutes alarm (15 minutes for voice); sealed lead-acid batteries replaced every 4 to 5 years.
- Battery charger requirement
- Charger must restore batteries to 80 percent capacity within 24 hours after a discharge per NFPA 72 requirements.
- Trouble signal timing
- Control unit must annunciate a trouble condition within 200 seconds of a fault such as an open circuit or ground fault.
- Ground fault detection
- Control units must detect and annunciate ground faults on circuits; isolated loops reduce nuisance ground faults in addressable systems.
- Annual testing
- NFPA 72 requires annual testing of all initiating devices, notification appliances, control unit functions, batteries, and remote annunciators.
- Battery load test
- Annual test of battery capacity; batteries must be replaced if capacity falls below 80 percent of rated capacity or manufacturer threshold.
- Record of completion
- NFPA 72 Form 72-1 documenting that the system was installed per plans and tested; required at acceptance testing.
- Impairment procedure
- When a system is out of service, notify the AHJ and occupants, post a fire watch if required, and document restoration of the system.
- Riser diagram
- Document showing all circuits, zones, addressable loops, and interfaces to suppression, HVAC, and elevator systems in a fire alarm system.
- Sequence of operations
- Matrix documenting cause-and-effect for each alarm, supervisory, and trouble condition, including notification and control functions.
- NRS Chapter 477
- Nevada Revised Statutes chapter governing fire protection, including State Fire Marshal authority and fire alarm system requirements.
- NSCB licensing
- Nevada State Contractors Board license required for fire alarm contractors; low-voltage work may require a separate classification.