NV Water/Wastewater Operator flashcards
NV Water/Wastewater Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- CT value
- The product of disinfectant residual concentration in mg/L and effective contact time in minutes. Required CT rises as water temperature falls and depends on pH, disinfectant, and target pathogen log inactivation.
- Chlorine demand
- The difference between the chlorine dose applied and the chlorine residual remaining after a defined contact period. Demand must be satisfied before any free residual can persist in the finished water.
- Four-log inactivation
- Removal or inactivation of 99.99 percent of a target organism, meaning only one organism in 10,000 survives. The SWTR requires 4-log virus and 3-log Giardia treatment for surface water systems.
- Combined filter effluent turbidity
- Under the IESWTR, combined filter effluent must be at or below 0.3 NTU in at least 95 percent of monthly measurements and must never exceed 1 NTU at any time.
- TTHM limit
- The Stage 2 DBPR maximum for total trihalomethanes is 80 micrograms per liter, evaluated as a locational running annual average at each monitoring location in the distribution system.
- Lead action level
- The lead action level is 0.015 mg/L, assessed at the 90th percentile of first-draw samples from high-risk sites. Exceeding it triggers corrosion control evaluation and public education.
- Detention time
- Detention time equals tank or pipe volume divided by flow rate, expressed in consistent units. It describes how long water remains in a basin or pipeline at a given flow.
- Minimum distribution pressure
- Systems must maintain at least 20 psi at all points in the distribution system under normal operating conditions and during main breaks and fire flow events.
- Free chlorine residual
- The concentration of uncombined chlorine remaining after demand is satisfied. A detectable residual is maintained throughout distribution, commonly 0.2 mg/L minimum at the tap.
- Coagulation and flocculation
- Coagulation adds a chemical such as alum to neutralize particle surface charge and destabilize turbidity. Flocculation then gently mixes the water so destabilized particles collide and form settleable floc.
- Jar test
- A bench-scale procedure that doses raw water with coagulant at several concentrations and mixing speeds to identify the dose and pH that best remove turbidity before full-scale plant changes.
- Backwash rate
- The upward flow per unit filter area used to clean media, typically 15 to 20 gallons per minute per square foot. Excessive rates wash media out; low rates leave floc and shorten filter runs.
- Disinfection byproducts
- Compounds such as trihalomethanes and haloacetic acids formed when chlorine reacts with natural organic matter. Precursor removal and reduced contact time help control their formation.
- Cross connection
- Any actual or potential connection between a potable water system and a source of contamination. Backflow prevention devices and air gaps protect the distribution system from such connections.
- Water hammer
- A pressure surge caused by rapid changes in flow velocity, such as sudden valve closure. It can rupture pipes and damage fittings, so valves should be operated slowly.
- Coliform rule
- Total coliform bacteria are used as indicators of distribution system integrity. Presence requires repeat sampling, and E. coli presence triggers public notice and investigation of contamination sources.
- BOD5
- Biochemical oxygen demand measured over five days at 20 degrees Celsius. It estimates biodegradable organic matter, with typical untreated domestic wastewater near 200 to 250 mg/L.
- Secondary treatment standards
- Federal standards require 30-day average effluent BOD5 and TSS of 30 mg/L or less, with at least 85 percent removal of each, unless a stricter permit limit applies.
- F/M ratio
- Food-to-microorganism ratio equals pounds of BOD5 applied daily divided by pounds of MLSS under aeration. Low ratios favor nitrification; high ratios favor rapid BOD removal but poorer settling.
- Mean cell residence time
- MCRT, or sludge age, equals pounds of solids in the aeration basin divided by pounds of solids leaving daily in waste sludge and effluent. Longer MCRT supports nitrification.
- Sludge volume index
- SVI equals the 30-minute settled sludge volume in mL/L times 1000 divided by MLSS in mg/L. Values near 80 to 150 indicate good settling; above 200 indicates bulking.
- Return activated sludge
- Settled biomass returned from the secondary clarifier to the aeration basin to maintain the target MLSS. RAS rate is adjusted based on sludge settleability and clarifier blanket depth.
- Nitrification
- Biological oxidation of ammonia to nitrite and then nitrate by nitrifying bacteria. It consumes alkalinity and oxygen and requires longer solids retention time and warmer water.
- Denitrification
- Conversion of nitrate to nitrogen gas by bacteria in an anoxic zone with a carbon source. It recovers alkalinity and reduces total nitrogen, but can cause rising sludge if it occurs in the clarifier.
- Infiltration
- Groundwater that enters a sewer through defective pipes, joints, and manholes. It adds hydraulic load without organic load and is highest during wet weather and high groundwater periods.
- Inflow
- Direct stormwater or groundwater entries into a sewer, such as roof drains, foundation drains, and unsealed manhole covers. Inflow causes sharp peak flows during rain events.
- Anaerobic digestion
- Biological decomposition of sludge without oxygen, producing methane and carbon dioxide. Stable digesters hold pH near 6.8 to 7.4 and alkalinity above about 2000 mg/L as CaCO3.
- Volatile solids reduction
- The percentage of volatile solids destroyed during digestion, typically 40 to 60 percent in a well-operated anaerobic digester. It indicates digestion efficiency and sludge stabilization.
- Fecal coliform limit
- A common permit limit for disinfected effluent is a monthly geometric mean of 200 colony-forming units per 100 mL for fecal coliform, or 126 for E. coli, depending on the permit.
- Preliminary treatment
- Screening and grit removal that protect downstream equipment. Bar screens capture large debris, while grit chambers settle sand and heavy solids that would damage pumps and clog digesters.
- Primary clarifier
- A settling tank that removes settleable solids before biological treatment, typically achieving 50 to 65 percent TSS removal and 25 to 40 percent BOD5 removal with a hydraulic detention time of about 1.5 to 2.5 hours.
- Dissolved oxygen control
- Aeration basins typically maintain 1.5 to 3.0 mg/L dissolved oxygen for carbonaceous BOD removal. Higher levels waste energy; lower levels can cause filamentous bulking and incomplete treatment.