NY Fire Sprinkler key terms
NY Fire Sprinkler · Get comfortable with the vocabulary.
- Automatic sprinkler
- Related: Sprinkler temperature rating, K-factor, Design area
A heat-activated device connected to a piping network that opens at a preset temperature and discharges water over a defined area to control or extinguish a fire.
- K-factor
- Related: Automatic sprinkler, Residual pressure, Hydraulic calculation
A number expressing the discharge coefficient of a sprinkler or nozzle, relating water flow in gallons per minute to the square root of supply pressure in psi.
- Sprinkler temperature rating
- Related: Automatic sprinkler, Thermal sensitivity, Quick-response sprinkler
The nominal activation temperature marked on a sprinkler's fusible element, selected to exceed expected ambient ceiling temperatures while opening early enough to control a fire.
- Quick-response sprinkler
- Related: Thermal sensitivity, Design area, Sprinkler temperature rating
A sprinkler with a low response time index, typically under 50, whose fast-operating element allows use of smaller design areas and longer spacing in many occupancies.
- Thermal sensitivity
- Related: Quick-response sprinkler, Sprinkler temperature rating
A measure of how rapidly a sprinkler's heat-responsive element reacts to a growing fire, expressed as response time index and classified as quick, standard, or special response.
- Design area
- Related: Hydraulic calculation, Density, Hazard classification
The hydraulically most demanding remote area of sprinkler operation assumed to be flowing simultaneously when calculating system demand; its size depends on occupancy hazard and sprinkler type.
- Density
- Related: Design area, Hazard classification, Hydraulic calculation
The minimum water application rate, in gallons per minute per square foot, that a sprinkler system must deliver over the design area for a given hazard classification.
- Hazard classification
- Related: Density, Design area, Ordinary hazard Group 2
The grouping of occupancies by fire severity and amount of combustibles, such as light, ordinary, or extra hazard, which sets density, spacing, and design area requirements.
- Ordinary hazard Group 2
- Related: Hazard classification, Density
A hazard category for occupancies with moderate to substantial combustible loading and moderate dust or stock, such as certain mercantile and industrial spaces, requiring higher density than light hazard.
- Wet pipe system
- Related: Dry pipe system, Preaction system, Main drain test
A sprinkler system in which automatic supply lines and piping are kept filled with pressurized water at all times so that a opened sprinkler discharges immediately.
- Dry pipe system
- Related: Wet pipe system, Dry pipe valve, Trip test
A sprinkler system in which piping above the control valve is filled with pressurized air or nitrogen; a sprinkler opening releases the air, allowing water to enter and flow.
- Preaction system
- Related: Wet pipe system, Dry pipe system, Deluge system
A system where the piping may be dry and water is admitted only after a fire detection signal, often with a second interlock, to protect areas where accidental discharge is costly.
- Deluge system
- Related: Preaction system, Deluge valve
A system using open sprinklers or nozzles in which a single detector or manual release opens a deluge valve, discharging water simultaneously from all connected heads.
- Dry pipe valve
- Related: Dry pipe system, Trip test, Air pressure maintenance
A clapper-type valve that holds back water supply using air pressure above it and opens when a sprinkler release drops the air pressure, admitting water to the system.
- Deluge valve
- Related: Deluge system, Preaction system
A quick-opening valve that, when actuated by a detection or release device, admits water to a deluge or preaction system's open piping network.
- Hydraulic calculation
- Related: Design area, Residual pressure, K-factor
The mathematical method of summing friction losses, elevation changes, and fitting losses through piping to prove that supply pressure and flow satisfy the required demand.
- Residual pressure
- Related: Static pressure, Hydraulic calculation, Main drain test
The pressure remaining at a hydrant or test outlet while water flows at a measured rate, used with static pressure to estimate the available water supply.
- Static pressure
- Related: Residual pressure, Main drain test
The pressure measured at a point in a water supply system when no water is flowing, reflecting elevation head and the supply's resting pressure.
- Main drain test
- Related: Static pressure, Residual pressure, Wet pipe system
A test that opens the main drain fully and records static and flowing pressure at the gauge, verifying that the water supply and control valves are in proper condition.
- Trip test
- Related: Dry pipe valve, Dry pipe system
A test of a dry pipe valve in which the system air pressure is bled to simulate a sprinkler operation, confirming the valve opens within the required time.
- Air pressure maintenance
- Related: Dry pipe valve, Dry pipe system
The practice of keeping a dry or preaction system's air or nitrogen pressure within specified limits using a compressor and regulator to prevent valve tripping and water entry.
- Spacing
- Related: Coverage area, Hazard classification
The maximum permitted distance between adjacent sprinklers or between a sprinkler and a wall or obstruction, governed by hazard and sprinkler listing.
- Coverage area
- Related: Spacing, Density
The floor area protected by a single sprinkler, determined by its spacing and the required density for the occupancy hazard.
- Obstruction
- Related: Spacing, Deflector
A structural or architectural element such as a beam, duct, or soffit that can block sprinkler spray, requiring added sprinklers or increased clearance beneath it.
- Deflector
- Related: Obstruction, Pendent sprinkler, Upright sprinkler
The component of a sprinkler that breaks up the water jet into a spray pattern; its distance below the ceiling and orientation affect coverage.
- Pendent sprinkler
- Related: Upright sprinkler, Sidewall sprinkler, Deflector
A sprinkler designed to hang below the piping with its deflector facing downward, producing a hemispherical spray pattern below the ceiling.
- Upright sprinkler
- Related: Pendent sprinkler, Sidewall sprinkler, Deflector
A sprinkler mounted above the piping with its deflector facing upward, throwing water in a pattern that then falls from the ceiling.
- Sidewall sprinkler
- Related: Pendent sprinkler, Upright sprinkler, Spacing
A sprinkler with a specialized deflector that discharges water outward from a wall, used where ceiling piping is impractical and coverage limits are tighter.
- Standpipe system
- Related: Class I standpipe, Class II standpipe, Fire department connection
A fixed piping system with hose connections at various levels that delivers water for manual firefighting, classified by whether it supplies water automatically and at what pressure.
- Class I standpipe
- Related: Class II standpipe, Standpipe system, Fire department connection
A standpipe system with 2.5-inch hose connections intended for use by fire department personnel, typically required in tall or large buildings to reduce hose lengths.
- Class II standpipe
- Related: Class I standpipe, Standpipe system
A standpipe system with 1.5-inch hose stations for occupant use on a limited basis, often combined with Class I outlets in a combined system.
- Fire department connection
- Related: Standpipe system, Class I standpipe
An exterior connection with inlets that lets responding pumpers supplement a building's water supply and pressure for sprinklers and standpipes.
- Manual standpipe
- Related: Automatic standpipe, Standpipe system
A standpipe system that relies entirely on fire department pumpers for water and pressure, since it has no permanent automatic supply.
- Automatic standpipe
- Related: Manual standpipe, Standpipe system
A standpipe system connected to a permanent water supply capable of delivering the required pressure and flow without fire department pumping.
- Pressure reducing valve
- Related: Standpipe system, Class I standpipe
A device that lowers high system pressure at an outlet to a level safe for hose and nozzle use, required where static pressure at a hose connection exceeds limits.
- Fire pump
- Related: Hydraulic calculation, Residual pressure
A pump installed to boost water pressure and flow when the public supply cannot meet the sprinkler or standpipe demand, controlled by automatic starting devices.
- Jockey pump
- Related: Fire pump, Air pressure maintenance
A small pressure-maintenance pump that keeps a fire protection system's piping pressurized and prevents the main fire pump from starting during minor leaks.
- Inspector's test valve
- Related: Main drain test, Spacing
A valve, usually at the end of the most remote branch, that opens to simulate a single sprinkler and confirm water reaches the far end of the system.
- Waterflow switch
- Related: Valve tamper switch, Wet pipe system
A device that senses water movement in a pipe and transmits an alarm signal, typically required on each sprinkler system riser and monitored by the fire alarm panel.
- Valve tamper switch
- Related: Waterflow switch, Main drain test
A supervisory device that signals the fire alarm system whenever a control valve is moved from its fully open position, ensuring prompt notification of closure.