EWRB Electrical study materials
EWRB Electrical study resources

EWRB Electrical cheat sheet

EWRB Electrical · Keep the key ideas within reach.

Quick reference

Electrical Theory and Practice

  • Ohm's law: V = I × R; power: P = V × I = I²R = V²/R.

  • Balanced three-phase power: P = √3 × V_L × I_L × cos φ, where V_L and I_L are line values.

  • Impedance: Z = √(R² + X²); inductive reactance X_L = 2πfL; capacitive reactance X_C = 1/(2πfC).

  • Conductor resistance: R = ρL/A; for copper ρ ≈ 1.72 × 10⁻⁸ Ω·m at 20 °C and the temperature coefficient α ≈ 0.00393 per °C.

  • Single-phase voltage drop: V_d = (2 × I × L × R_c)/1000 with R_c in Ω/km and L in metres; substitute √3 for the 2 in three-phase circuits.

  • New Zealand nominal supply values: 50 Hz, 230 V phase-to-neutral, 400 V phase-to-phase.

  • MEN system: neutral is earthed at the transformer star point, at the installation point, and at each separate structure fed by a submain; neutral and earth are separated downstream of each MEN link.

  • Cable current rating is derated by multiplying factors for ambient temperature, grouping, thermal insulation, burial depth and soil thermal resistivity.

  • Power factor correction: capacitive kVAR required = kW × (tan φ₁ − tan φ₂), where φ₁ is the existing and φ₂ the target angle.

Quick reference

Electrical Regulations

  • Prescribed electrical work may only be done by a registered person holding a current practising licence, or by another person under that person's supervision.

  • High-risk prescribed work - including mains work and connecting an installation to supply - must be inspected and covered by an Electrical Safety Certificate issued by a registered electrical inspector.

  • On completion the worker issues a Certification of prescribed electrical work declaring compliance, and the certification and inspection records must be retained and produced on request.

  • A practising licence is renewed annually through the Electrical Workers Registration Board and depends on demonstrated current competence.

  • Work on live conductors is permitted only where de-energising would create greater risk, and only after a hazard assessment with approved test equipment and PPE.

  • Isolation must be verified with an approved voltage tester that is proved on a known source before and after the test; conductors are treated as live until proved dead.

  • NZECP 34 sets minimum safe distances from overhead lines and requires the line owner's written consent before working inside those distances.

  • Electrical equipment supplied in New Zealand must be shown to comply with an approved electrical safety standard, with the supplier responsible for that compliance.

Quick reference

Standards and Certification

  • AS/NZS 3000 (the Wiring Rules) is the governing installation standard and is given legal effect in New Zealand by the Electricity (Safety) Regulations 2010.

  • AS/NZS 3008.1.1 is used to select cable size and to obtain current-carrying capacity, voltage drop and short-circuit ratings for typical installation conditions.

  • AS/NZS 3017 specifies verification by inspection and testing before an installation is connected to supply.

  • AS/NZS 3019 covers periodic verification of existing installations; AS/NZS 3760 covers in-service inspection and testing (test and tag) of electrical equipment.

  • AS/NZS 4836 sets safe working practices for low-voltage work; AS/NZS 3012 sets additional requirements for construction and demolition sites.

  • Harmonised conductor colours are brown, black and grey for phases, blue for neutral and green/yellow for earth; older installations use red, white and blue for phases.

  • AS/NZS 3112 defines the New Zealand/Australian three-pin plug and socket outlet configuration, pin dimensions and insulation requirements.

  • Certification documents form a chain: Certification of prescribed electrical work from the worker, Electrical Safety Certificate from the inspector, and Records of Inspection retained for audit.

Quick reference

Practical Assessment and Safe Working

  • The five safety rules: isolate, secure against re-energisation, verify absence of voltage, earth and short-circuit where required, and protect adjacent live parts.

  • Test sequence for verification: visual inspection, continuity of protective earthing and bonding, insulation resistance, polarity, earth fault loop impedance, RCD operation, then functional tests.

  • Insulation resistance is measured at 500 V DC with loads and sensitive electronics disconnected; the minimum acceptable value for a 230/400 V installation is 1 MΩ.

  • A 30 mA RCD must operate within 300 ms at its rated residual current, and within 40 ms when tested at five times rated residual current.

  • Earth fault loop impedance is measured to confirm the protective device will disconnect the fault within the time required by AS/NZS 3000.

  • Polarity testing confirms that switches and fuses are inserted in the phase conductor and that socket outlet terminals are correctly connected.

  • Lockout/tagout: the isolating device is locked, a danger tag fitted, and the key retained by the worker until the work is finished and the circuit is formally restored.

  • PPE for work near energised equipment includes voltage-rated gloves, insulated tools and arc-rated clothing selected for the assessed incident energy.