EWRB Electrical flashcards
EWRB Electrical · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- Current through a conductor is directly proportional to the voltage across it and inversely proportional to its resistance, written as V = I × R.
- Three-phase power formula
- For a balanced load, total real power equals √3 multiplied by line voltage, line current and power factor: P = √3 × V_L × I_L × cos φ.
- Impedance formula
- Impedance is the total opposition to alternating current and combines resistance with reactance: Z = √(R² + X²), measured in ohms.
- Inductive reactance
- The reactance of an inductor increases with frequency according to X_L = 2πfL, where f is in hertz and L is inductance in henrys.
- Conductor resistance formula
- Resistance equals resistivity times length divided by cross-sectional area, R = ρL/A; copper has a resistivity of about 1.72 × 10⁻⁸ Ω·m at 20 °C.
- Power factor correction
- The capacitive reactive power needed to raise power factor equals kW × (tan φ₁ − tan φ₂), where φ₁ is the existing and φ₂ the target phase angle.
- MEN system
- Multiple earthed neutral: the neutral is earthed at the transformer star point, at the installation point and at each separate structure, with neutral and earth kept separate downstream.
- Voltage drop formula
- Single-phase voltage drop equals 2 × I × L × R divided by 1000, with R in ohms per kilometre and L in metres; three-phase calculations use √3 instead of 2.
- Prescribed electrical work
- Work on electrical installations and equipment that the Electricity (Safety) Regulations 2010 require to be done by, or under the supervision of, a registered and licensed person.
- High-risk prescribed electrical work
- Categories such as mains work and connecting an installation to supply, which must be inspected and covered by an Electrical Safety Certificate issued by a registered electrical inspector.
- Certification of prescribed electrical work
- The document a registered worker issues on completion, declaring the work complies with the Wiring Rules and regulations, with copies retained for inspection.
- Practising licence
- The annual licence issued by the Electrical Workers Registration Board that legally entitles a registered person to carry out or supervise prescribed electrical work.
- Live work justification
- Live work is allowed only where de-energising would create greater risk, and only after a hazard assessment with approved test equipment and suitable personal protective equipment.
- NZECP 34
- The New Zealand Electrical Code of Practice for electrical safe distances, which sets minimum approach distances to overhead lines and requires the line owner's consent for closer work.
- Supervision duty
- A licensed supervisor must ensure the trainee's work is done competently and safely, remain accountable for it, and certify the completed prescribed electrical work.
- Isolation verification
- Prove the tester on a known live source, test the conductors to be worked on, then re-prove the tester; conductors stay live until proven otherwise.
- AS/NZS 3000
- The Wiring Rules, the joint Australian and New Zealand standard for designing and constructing electrical installations, given legal force in New Zealand by regulation.
- AS/NZS 3008.1.1
- The standard used to select cable size and to determine current-carrying capacity, voltage drop and short-circuit withstand for typical New Zealand installation conditions.
- AS/NZS 3017
- The standard for verification of electrical installations by inspection and testing, describing the required tests and acceptable results before connection to supply.
- AS/NZS 3760
- The standard for in-service safety inspection and testing of electrical equipment, forming the basis of the test-and-tag regime for appliances and flexible leads.
- AS/NZS 3019
- The standard for periodic verification of existing electrical installations, used to judge whether an installation remains safe and compliant throughout its service life.
- AS/NZS 4836
- The standard for safe working on low-voltage electrical installations and equipment, covering isolation, testing, protective equipment and emergency response procedures.
- Harmonised conductor colours
- New Zealand uses brown, black and grey for phase conductors, blue for neutral and green/yellow for earth; older installations use red, white and blue for phases.
- AS/NZS 3112
- The standard defining the New Zealand and Australian three-pin plug and socket outlet, including pin configuration, pin dimensions and insulation requirements.
- Five safety rules
- Isolate, secure against re-energisation, verify absence of voltage, earth and short-circuit where required, and protect or barricade adjacent live parts.
- Prove-test-prove
- Confirm the voltage tester works on a known live source, test the target conductors to prove they are dead, then re-prove the tester afterwards.
- Insulation resistance test
- Measure between conductors and between live conductors and earth at 500 V DC with loads disconnected; a 230/400 V installation should read at least 1 MΩ.
- RCD trip time limit
- A 30 mA residual current device must operate within 300 milliseconds at rated residual current, and within 40 milliseconds at five times rated residual current.
- Polarity test
- Confirms that switches and fuses are inserted in the phase conductor and that active, neutral and earth are connected to the correct socket outlet terminals.
- Earth fault loop impedance
- The total impedance of the path from a fault back to the supply transformer, measured to confirm the protective device will disconnect within the required time.
- Lockout tagout
- The isolating device is locked and fitted with a danger tag, with the key held by the worker so the circuit cannot be re-energised until work is complete.
- Arc flash PPE
- Arc-rated clothing, face protection and voltage-rated gloves worn when working near energised equipment, selected to suit the assessed incident energy level.